Measurements and Recording
P846/EN MR/D
MiCOM P846
(MR) 8-5
MR
Alarm Condition
Event Text
Event Value
Battery Fail
Battery Fail ON/OFF
Bit position 0 in 32 bit field
Field Voltage Fail
Field Volt Fail ON/OFF
Bit position 1 in 32 bit field
Setting Group via Opto
Invalid
Setting Grp. Invalid ON/OFF Bit position 2 in 32 bit field
Protection Disabled
Prot’n. Disabled ON/OFF
Bit position 3 in 32 bit field
Frequency out of Range
Freq. out of Range ON/OFF
Bit position 4 in 32 bit field
VTS Alarm
VT Fail Alarm ON/OFF
Bit position 5 in 32 bit field
CB Trip Fail Protection
CB Fail ON/OFF
Bit position 7 in 32 bit field
The previous table shows the abbreviated description that is given to the various alarm
conditions and also a corresponding value between 0 and 31. This value is appended to
each alarm event in a similar way as for the input and output events previously described. It
is used by the event extraction software, such as MiCOM S1, to identify the alarm and is
therefore invisible if the event is viewed on the LCD. Either ON or OFF is shown after the
description to signify whether the particular condition has become operated or has reset.
1.2.1.4 Protection element starts and trips
Any operation of protection elements, (either a start or a trip condition) will be logged as an
event record, consisting of a text string indicating the operated element and an event value.
Again, this value is intended for use by the event extraction software, such as MiCOM S1,
rather than for the user, and is therefore invisible when the event is viewed on the LCD.
1.2.1.5 General events
A number of events come under the heading of ‘General Events’ - an example is shown
below:
Nature of Event
Displayed Text in Event
Record
Displayed Value
Level 1 password modified,
either from user interface,
front or rear port.
PW1 modified UI, F, R or R2
0 UI=6, F=11, R=16, R2=38
A complete list of the ‘General Events’ is given in the Relay Menu Database (P846/EN MD),
which is a separate document, available for downloaded from our website.
1.2.1.6 Fault records
Each time a fault record is generated, an event is also created. The event simply states that
a fault record was generated, with a corresponding time stamp.
Note that viewing of the actual fault record is carried out in the "Select Fault’" cell further
down the "VIEW RECORDS" column, which is selectable from up to 5 records. These
records consist of fault flags, fault location, fault measurements etc. Also note that the time
stamp given in the fault record itself will be more accurate than the corresponding stamp
given in the event record as the event is logged some time after the actual fault record is
generated.
The fault record is triggered from the ‘Fault REC. TRIG.’ signal assigned in the default
programmable scheme logic to the ‘Fault Detected’ DDB. Note the fault measurements in
the fault record are given at the time of the protection start. Also, the fault recorder does not
stop recording until the trip condition resets in order to record all the protection flags during
the fault.
It is recommended that the triggering contact (relay 3 for example) be ‘self reset’ and not
latching. If a latching contact were chosen the fault record would not be generated until the
contact had fully reset.
Содержание MiCOM P846
Страница 2: ......
Страница 4: ......
Страница 5: ...Safety Section P846 EN SS H11 SS SAFETY SECTION...
Страница 6: ...P846 EN SS H11 Safety Section SS...
Страница 8: ...P846 EN SS H11 Safety Section SS 2 SS...
Страница 16: ...P846 EN IT D Introduction MiCOM P846 IT...
Страница 18: ...P846 EN IT D Introduction IT 1 2 MiCOM P846 IT...
Страница 26: ...P846 EN TD D Technical Data MiCOM P846 TD...
Страница 38: ...P846 EN GS D Getting Started MiCOM P846 GS...
Страница 58: ...P846 EN ST D Getting Started MiCOM P846 ST...
Страница 60: ...P846 EN ST D Settings ST 4 2 MiCOM P846 ST...
Страница 78: ...P846 EN OP D Operation MiCOM P846 OP...
Страница 104: ...P846 EN OP D Operation OP 5 26 MiCOM P846 OP...
Страница 106: ...P846 EN AP D Application Notes MiCOM P846 AP...
Страница 108: ...P846 EN AP D Application Notes AP 6 2 MiCOM P846 AP...
Страница 122: ...P846 EN AP D Application Notes AP 6 16 MiCOM P846 AP...
Страница 124: ...P846 EN PL D Programmable Logic MiCOM P846 PL...
Страница 126: ...P846 EN PL D Programmable Logic PL 7 2 MiCOM P846 PL...
Страница 144: ...P846 EN MR D Measurements and Recording MiCOM P846 MR...
Страница 146: ...P846 EN MR D Measurements and Recording MR 8 2 MiCOM P846 MR...
Страница 160: ...P846 EN FD D Firmware Design MiCOM P846 FD...
Страница 182: ...P846 EN CM D Commissioning MiCOM P846 CM...
Страница 228: ...P846 EN CM D Commissioning CM 10 46 MiCOM P846 CM...
Страница 230: ...P846 EN MT D Maintenance MiCOM P846 MT...
Страница 232: ...P846 EN MT D Maintenance MT 11 2 MiCOM P846 MT...
Страница 238: ...P846 EN TS D Troubleshooting MiCOM P846 TS...
Страница 240: ...P846 EN TS D Troubleshooting TS 12 2 MiCOM P846 TS...
Страница 252: ...P846 EN SC D SCADA Communications MiCOM P846 SC...
Страница 272: ...P846 EN SG D Symbols and Glossary MiCOM P846 SG...
Страница 280: ...P846 EN SG D Symbols and Glossary SG 14 8 MiCOM P846 SG...
Страница 282: ...P846 EN IN D Installation MiCOM P846 IN...
Страница 284: ...P846 EN IN D Installation IN 15 2 MiCOM P846 IN...
Страница 293: ...Installation P846 EN IN D MiCOM P846 IN 15 11 7 P846 CASE DIMENSIONS Figure 3 Case dimensions IN...
Страница 295: ...Installation P846 EN IN D MiCOM P846 IN 15 13 P1756ENa IN Figure 5 Model B with 32 output contacts and 24 digital inputs...
Страница 296: ...P846 EN IN D Installation IN 15 14 MiCOM P846 IN...
Страница 297: ......