DNP3 Manual 

 

M6xxD/EN M/B

 

M6xx  

Page 27

 

 

Bitronics Legacy DNP3 Point Assignments 

 

DNP Point 

Contents 

Data 

Scale 

Ind  Values/Dependencies

Type 

Min 

Max 

Step 

Class 

 

AI:48 

  Demand (Min) Watts Total 

T6 

Amp Scale * Volt 
Scale 

 

Data 

-32768  32767  ((1/32768) * 4500 * Amp Scale * Volt Scale )  W 

 

AI:49 

  Demand VARs Total 

T6 

Amp Scale * Volt 
Scale 

 

Data 

-32768  32767  ((1/32768) * 4500 * Amp Scale * Volt Scale )  vars 

 

AI:50 

  Demand (Max) VARs Total 

T6 

Amp Scale * Volt 
Scale 

 

Data 

-32768  32767  ((1/32768) * 4500 * Amp Scale * Volt Scale )  vars 

 

AI:51 

  Demand (Min) VARs Total 

T6 

Amp Scale * Volt 
Scale 

 

Data 

-32768  32767  ((1/32768) * 4500 * Amp Scale * Volt Scale )  vars 

 

AI:52 

  Demand VAs Total 

T6 

Amp Scale * Volt 
Scale 

 

Data 

32767  ((1/32768) * 4500 * Amp Scale * Volt Scale )  VAs 

 

AI:53 

  Demand (Max) VAs Total 

T6 

Amp Scale * Volt 
Scale 

 

Data 

32767  ((1/32768) * 4500 * Amp Scale * Volt Scale )  VAs 

 

AI:54 

  Demand (Min) VAs Total 

T6 

Amp Scale * Volt 
Scale 

 

Data 

32767  ((1/32768) * 4500 * Amp Scale * Volt Scale )  VAs 

 

AI:55 

  Meter Type 

T1 

600  Legacy points list 

Data 

600 

602 

 AI:56 

 

Protocol 

Version 

T21 

 

 

Data  0 

65536 

0.001 

 

AI:57 

  Factory Version Software 

T21   

 

Data 

65536  0.001 

 AI:58 

 

Reserved 

T21 

 

 

Data  0 

65536 

0.001 

 

AI:59 

  Volts N-G 

T4 

Volt Scale 

 

Data 

32767  ((1/32768) * 150 * Volt  Scale)  V 

Never 

 

AI:60 

  Volts A-B 

T23  Volt Scale 

 

Data 

32767  ((1/32768) * 300 * Volt  Scale)  V 

Never 

 

AI:61 

  Volts B-C 

T23  Volt Scale 

 

Data 

32767  ((1/32768) * 300 * Volt  Scale)  V 

Never 

 

AI:62 

  Volts C-A 

T23  Volt Scale 

 

Data 

32767  ((1/32768) * 300 * Volt  Scale)  V 

Never 

 

AI:63 

  System Frequency (1mHz) 

T24   

 

Data 

-32768  32767  0.001Hz 

Never 

 

AI:65 

  Reserved 

T4 

Volt Scale 

 

Data 

32767  ((1/32768) * 150 * Volt  Scale)  V 

Never 

 

AI:66 

  Reserved 

T4 

Volt Scale 

 

Data 

32767  ((1/32768) * 150 * Volt  Scale)  V 

Never 

 

AI:67 

  Reserved 

T4 

Volt Scale 

 

Data 

32767  ((1/32768) * 150 * Volt  Scale)  V 

Never 

 

AI:68 

  Reserved 

T4 

Volt Scale 

 

Data 

32767  ((1/32768) * 150 * Volt  Scale)  V 

Never 

 

AI:69 

  Reserved 

T4 

Volt Scale 

 

Data 

32767  ((1/32768) * 150 * Volt  Scale)  V 

Never 

 

AO:04 

  BiLF Class 0 Mask 

T1 

 

 

Setting 

65536  1 

Always

 AO:06 

 

Tag 

Register 

T1 

 

 

Setting 

0 65536 

Always

 BO:00 

 

Reset 

Energy 

T22 

 

Normal 

Setting 

0  1 

Always

Reset  Energy 
Counters 

Содержание M65B

Страница 1: ...ty of their respective companies The technical and other data contained in this document is provided for information only Neither ALSTOM its officers or employees accept responsibility for or should b...

Страница 2: ......

Страница 3: ...1 5 Configuration 9 1 5 1 Setting CT and VT Ratios 9 1 5 2 Resetting Energy and Demands 9 1 5 3 Tag Registers 10 1 6 Converting Data to Engineering Units 10 1 7 Primary Units 12 1 8 Data Sets and Data...

Страница 4: ...ER ETHERNET TCP 21 3 1 DNP IP 21 4 0 DNP3 EVENTS OVERVIEW 22 4 1 ANALOGUE CHANGE EVENTS 22 4 2 FROZEN COUNTER EVENTS 23 4 3 BINARY INPUT CHANGE EVENTS 23 Appendix A Bitronics Legacy DNP3 Point Assignm...

Страница 5: ...lation and maintenance As with any product of this nature installation and maintenance can present electrical hazards and should be performed only by properly trained and qualified personnel If the eq...

Страница 6: ...d Bethlehem PA 18017 Schneider Automation Inc One High Street North Andover MA 01845 Triangle MicroWorks Inc 2213 Middlefield Court Raleigh NC 27615 Freescale Semiconductor Inc 6501 William Cannon Dri...

Страница 7: ...ULD NOT be written continuously Four legacy values are also presented They are CT Scale Factor Normalized Ratio and Divisor and VT Scale Factor Normalized Ratio and Divisor They are derived from the P...

Страница 8: ...th status word The DNP protocol allows each device to determine the best method of data transfer The M6xx meters support this by selecting the most appropriate response variation when either the reque...

Страница 9: ...aturation 4500 Float Value Integer Value 32768 Scale 4500 Example 90 0 kW stored as 8192 when Volt Scale 20 1 Amp Scale 4 1 T7 Signed 16 Bit Integer 2 s Complement 3 Decimal Places Example 12 345 stor...

Страница 10: ...ation 15 Float Value Integer Value 2047 2048 Scale 15 Example 11 79 A stored as 2369 when Amp Scale 5 1 T18 Unsigned 16 Bit Integer 12 Bit Offset Binary 1 Decimal Place Float Value Integer Value 2047...

Страница 11: ...te a CT and VT ratio for Phase A from the data stored in the M6xx meters use the following equation RA T IO RA T IO Phase A C T V alue A O 21 Phase A C T Phase A C T Ratio D ivisor A O 22 Phase A V T...

Страница 12: ...equations BASIC EQUATION FOR NORMALIZED ANALOGUE INPUTS 32768 SECONDARY Value Normalized Scale Factor Engineering Units Default Full Scale Scale Factor Divisor The Value referred to in the equations w...

Страница 13: ...Value x 150 x VOLTs PT 32768 Min Max Min Max RATIO t Demand RATIO RATIO TOTAL Inst Demand PER PHASE Inst Value SCALED x 150 x x 3 VOLTs PT 32768 Value WATTs VARs VAs x x x 4500 CT PT 32768 Value WATTs...

Страница 14: ...ull scale and therefore independent of CT and VT settings The Primary Units mode creates protocol values that include CT and VT settings which requires the user to choose a scaling factor in multiples...

Страница 15: ...n types are unaffected as they represent their values such as Frequency Power factor in primary units even in Optimal Resolution mode Also since the 12 bit calculation types are not included in the su...

Страница 16: ...emulate the response of a Bitronics MultiComm or PowerPlex unit 1 8 1 Configuring the Class 0 Response The Class 0 request is a very short request to give all essential data Since the M6xx is capable...

Страница 17: ...58 AO 0 3 10 14 Bit 14 Include all data in Class0 poll Include all data in Class0 poll 1 8 2 Configuring Class 1 Class 2 and Class 3 Events ANALOGUE INPUT points can be monitored for ANALOGUE CHANGE...

Страница 18: ...ibration of inputs 12 Indicates firmware download in progress and measurements are offline 15 Protocol configuration error 1 10 Heartbeat State Counter M6xx meters provide a Heartbeat State Counter Re...

Страница 19: ...17 The DNP Points List Configuration summary page is displayed by object Select the DNP object you would like to edit from the DNP Type dropdown box The properties of the selected object appear in se...

Страница 20: ...DNP3 Manual M6xxD EN M B M6xx Page 18 Click on the Edit List button to modify the list...

Страница 21: ...ighlighted item If no items are highlighted in the Selected list items are added to the end of the list NOTES Highlights all measurement data items in Available list Places highlighted measurement dat...

Страница 22: ...The physical layer is responsible for transmission of raw 8 bit bytes octets across the network medium The data link layer is responsible for reliably maintaining connectivity between two devices The...

Страница 23: ...ers share an IP address each Master must connect to a unique IED Listen port For each protocol session the Master IP address and the IED Listen Port number may be specified The current Settings for ea...

Страница 24: ...iggered by any change of an enabled binary input point Each of the three DNP sessions has storage for 200 Analogue Input Events 100 Frozen Counter Events and 20 Binary Input events Events can be repor...

Страница 25: ...his communication session allocates a dedicated set of FROZEN COUNTERs specifically for the new DNP3 master When the DNP3 master issues a FREEZE or FREEZE AND CLEAR command only the FROZEN COUNTERs al...

Страница 26: ...Amp Scale Data 0 32767 1 32768 10 Amp Scale A Always AI 02 Amps B T2 Amp Scale Data 0 32767 1 32768 10 Amp Scale A Always AI 03 Amps C T2 Amp Scale Data 0 32767 1 32768 10 Amp Scale A Always AI 04 Vo...

Страница 27: ...10 100 1000 3 AI 19 Amps Residual T3 Amp Scale Data 0 32767 1 32768 15 Amp Scale A Always CT 0 Watt Hrs Normal High Word T1 Data 0 65536 65536 KiloWattHours 0 CT 1 Watt Hrs Reverse High Word T1 Data 0...

Страница 28: ...cale Data 0 32767 1 32768 10 Amp Scale A 2 AI 34 Demand Max Amps C T2 Amp Scale Data 0 32767 1 32768 10 Amp Scale A 2 AI 35 Demand Amps Residual T3 Amp Scale Data 0 32767 1 32768 15 Amp Scale A 2 AI 3...

Страница 29: ...55 Meter Type T1 600 Legacy points list Data 600 602 0 3 AI 56 Protocol Version T21 Data 0 65536 0 001 3 AI 57 Factory Version Software T21 Data 0 65536 0 001 3 AI 58 Reserved T21 Data 0 65536 0 001 3...

Страница 30: ...00 Volt Scale V Never AI 75 Demand Max Volts AB T23 Volt Scale Data 0 32767 1 32768 300 Volt Scale V Never AI 76 Demand Max Volts BC T23 Volt Scale Data 0 32767 1 32768 300 Volt Scale V Never AI 77 De...

Страница 31: ...1500 Amp Scale Volt Scale VAs Never AI 92 Max Average VAs C T6 Amp Scale Volt Scale Data 0 32767 1 32768 1500 Amp Scale Volt Scale VAs Never AI 93 Average Watts A T5 Amp Scale Volt Scale Data 32768 3...

Страница 32: ...olt Scale Data 32768 32767 1 32768 1500 Amp Scale Volt Scale VARs Never AI 106 Min Average VARs B T6 Amp Scale Volt Scale Data 32768 32767 1 32768 1500 Amp Scale Volt Scale VARs Never AI 107 Min Avera...

Страница 33: ...ether or not to validate source address in received frames DNP3 frames contain both a source address field and a destination address field If the box is not checked DNP3 does not validate the source a...

Страница 34: ...mary Units mode deadbands are in per count integers 1 00 Power Reactive In Optimal Resolution mode deadbands are in percents with a minimum value of 01 In Primary Units mode deadbands are in per count...

Страница 35: ...ed before an unsolicited response is generated Default is 5 maximum is 255 Class2 Timeout ms When unsolicited response is enabled the maximum amount of time in ms after an event before an unsolicited...

Страница 36: ...CRCs Default is 292 max Receive Frame Timeout ms Maximum amount of time ms to wait for a complete frame after receiving valid frame sync characters Default is 15 000 milliseconds First Character Timeo...

Страница 37: ...stination IP address for UDP broadcast requests This is only used by a DNP Master when TCP and UDP are supported If UDP ONLY is configured IP Address will be used as destination for all requests Defau...

Страница 38: ...equested Frozen Counter Events may be requested The read function code for Object 50 Time and Date variation 1 is supported Maximum Data Link Frame Size octets Transmitted 292 Received 292 Maximum App...

Страница 39: ...any operation Reports Binary Input Change Events when no specific variation requested Never Only time tagged Only non time tagged Configurable Reports time tagged Binary Input Change Events when no sp...

Страница 40: ...DNP3 Manual M6xxD EN M B M6xx Page 38 BLANK PAGE...

Страница 41: ......

Страница 42: ...for information only Neither ALSTOM its officers or employees accept responsibility for or should be taken as making any representation or warranty whether express or implied as to the accuracy or com...

Отзывы: