6. Installation and Commissioning
GEM80-500 Series Controller
GEM80-500 Technical Manual (T2025En)
(08/04)
Page 6-8
9720-4020 1st Module
GEMCAN I/O Scanner
TP4
1
2
3
9720-4020 2nd Module
GEMCAN I/O Scanner
TP4
1
2
3
Figure 6-4
GEMCAN I/O Scanner Module showing Jumper Link Positions
6.8.4
Setting FIP Module Subscriber Address
The GEM80-500 Controller FIP network subscriber address is set using two BCD
switches on the FIP Module 9715-4020. These switches are shown in Figure 6-5. The
address is an 8-bit hexadecimal value. SW2 is the low nibble and SW3 is the high
nibble. For example, if SW3 is set to 5 and SW2 is set to 1, the FIP network subscriber
address will be @51, i.e. hexadecimal value 51.
9715-4020
FIP network subscriber address
BCD switches
1
5
1
5
SW3
SW2
SW2 Low nibble
SW3 High nibble
Figure 6-5
FIP Port Subscriber Address Configuration