Electric Rim Strike
AL150
INSTRUCTIONS Read all instructions before starting installation
INSTALL ON TIMBER DOOR FRAME
x3
DOOR LATCH POSITION
As shown in Figure 1, there must be a
1mm gap between the door latch and
the front face of strike keeper to prevent
the door from exerting pressure on the
keeper when door is closed.
MOUNTING STEPS OF STRIKE
1
2
3
4
Note: There’s no polarity on power input, AL150 is not equipped with DSS sensor.
RED
YELLOW
BLUE
BLACK
RED
YELLOW
BLUE
BLACK
12 vDC/ 200 mA
24 vDC/ 100 mA
DSS (Door Status Sensor), BLACK (COM), BLUE (NO), ORANGE (NC)
DSS contact rating: max, current 100 mA, max. voltage 30 vDC
PACK CONTENTS
POWER INPUT 12 VDC or 24VDC SUPPLY
Figure 1
Figure 2
Figure 3
Position the strikes against the frame, mark and drill the hole sizes as
shown on Figure 2 and 3.
Drill cable exit hole on door frame.
Make sure electrical connections are followed correctly.
When the door is closed, ensure that there is no pressure on the front
face of strike keeper.