9 DIAGNOSTICS AND FAULT CODES

Alpha SolarSmart 90 - Diagnostics and Fault Codes

Codes 71, 72 and 80 will stop the solar system working: 

The cause must be rectified before the system will

operate. When the cause has been rectified the system will start by itself.

Code 71

Collector sensor fault

Temperature of the collector is below -40°C or above 250°C.
Check the collector sensor: does it operate (check sensor  resistance in table on next
page).
Sensor cable damaged or short circuited.
Sensor is faulty.

Code 72

Upper cylinder sensor fault

Temperature of the cylinder is below 0°C or above 100°C.
Check the upper cylinder sensor: does it operate (check sensor  resistance in table on
next page).
Sensor cable damaged or short circuited.
Sensor is faulty.

Code 80

Lower cylinder sensor fault

Temperature of the cylinder is below 0°C or above 100°C.
Check the lower cylinder sensor: does it operate (check sensor  resistance in Section
7.3).
Sensor cable damaged or short circuited.
Sensor is faulty.

Code 77 is the only code displayed that is not actually a fault: 

The code will disapear if the button is pressed.

Code 77

The system is not turned on

The control has not been operating for 30 days.
Check the collector sensor and the lower cylinder sensor, do they operate (check
sensor  resistance in Section 7.3).

Codes 74 and 75 will lock the solar system: 

The cause must be rectified before the system will operate. When the

cause has been rectified the system control can be reset by pressing the button.

Code 74

No circulation in the
collector

Check water level in drain back unit.
Check the difference in height between the drain back unit pump and the upper most
side of the collector. This can be a maximum of 3 metres.
Check the collector sensor and the lower cylinder sensor, do they operate (check
sensor  resistance in Section 7.3).
Check the collector tubes, are they blocked with dirt? Is the decline of the pipes within
the 40 mm per metre requirement.
Check the electrical connection and operation of the drain back unit pump and the
cylinder pump.

Code 75

Collector temperature too
high

After 5 minutes the collector temperature is still too high (above 130°C) with the drain
back unit pump operating.
Check the level of water in the drain back unit. Refer to filling procedure in Section
5.2.
Check the difference in height between the drain back unit pump and the upper most
side of the collector. This can be a maximum of 3 metres.
Check the collector sensor and the lower cylinder sensor, do they operate (check
sensor  resistance in Section 7.3).
Check the collector tubes, are they blocked with dirt? Is the decline of the pipes within
the 40 mm per metre requirement.
Check the electrical connection and operation of the drain back unit pump and the
cylinder pump.

9.1

FAULT CODES

The solar system is fully controlled by the electronic control on the cylinder. Fault codes will be displayed at the cylinder
by means of a flashing fault code (71 to 80). The following codes can be displayed.

Содержание SolarSmart 90

Страница 1: ...Solar System and Wall Mounted Unvented Hot Water Solar Cylinder for use with an Alpha Combination Boiler Nepicar House London Road Wrotham Heath Sevenoaks Kent TN15 7RS For Technical help or for Serv...

Страница 2: ...storage systems and the Local Authority must be notified of the intention to install Therefore the installation must be carried out by a person competent to install unvented hot water systems The ins...

Страница 3: ...Area m Aperture Area m Length x Width x Thickness mm Water Content L Lift Weight kg Hydraulics Maximum Pressure bar Absorber Aluminium Cover and Copper Pipe Length x Width x Depth mm Spectral Selectiv...

Страница 4: ...earances for Servicing Top Bottom Sides Front DBU Min Clearances for Servicing Top Bottom Side Front Lift Weight Cylinder Assembly Lift Weight DBU Weight Full and Operational Cylinder Assemby Weight F...

Страница 5: ...8 Filter 9 Diffuser 10 DHW outlet pipe 11 Solar valve 12 Flow to boiler 13 Flow to tap 14 Temperature sensors 15 Insulation casing 16 Bottom tray 17 Unvented kit 18 Tundish 19 Non return valve 20 Expa...

Страница 6: ...rature is controlled to a maximum of 70 C To prevent high temperatures at the hot water taps it is recommended that a thermostatically controlled mixing valve is fitted after the boiler 3 3 UNVENTED H...

Страница 7: ...supply Thermostat sensor Thermostat sensor Unvented cylinder Thermostat sensor Solar collector Drain back unit Drain back unit pump Cylinder pump Heat exchanger Drain point Thermostatically controlled...

Страница 8: ...of 22 mm copper discharge pipe D2 from a G temperature relief valve is 9 m Subtract the resistance for four 22 mm elbows of 0 8 m each 3 2 m Therefore the maximum permitted length equates to 9 3 2 5...

Страница 9: ...ce containing a bath or shower When the cylinder is installed in a room containing a bath or shower it must not be possible for a person using the bath or shower to touch any electrical switch or cyli...

Страница 10: ...ions The dimensions of the DBU and clearances required for servicing are shown in Fig 6 Water connections The connections at the top and bottom of the DBU are shown in Fig 6 Alpha SolarSmart 90 Genera...

Страница 11: ...itable to ensure that the installation is weatherproof Full details of this type of installation are provided in the instructions supplied with the kit b Positioning of a landscape collector onto a fl...

Страница 12: ...Box 3 Unvented kit and Solar valve Contents 2 5 bar pressure reducing valve 8 litre expansion vessel Expansion vessel mounting bracket Tundish Expansion relief valve check valve Solar valve kit Fittin...

Страница 13: ...rails 1 Decide on the position of the cylinder taking into consideration the clearances and the maximum allowed distances from the drain back unit and collector 2 Using the template supplied mark the...

Страница 14: ...the minimum 40 mm per metre downward slope of the collector tubing If the collector has not yet been fitted ensure that there is 200 250 mm between the centre of the break through hole and the upper...

Страница 15: ...n the direction of flow 5 Connect the mains water supply to the pressure reducing valve and thoroughly flush out the water pipework Refer to Domestic Hot Water System Sections 3 2 and 3 3 Fig 13 4 7 F...

Страница 16: ...e a single hot water supply immediately after boiler installation 4 A self adhesive label is supplied in the Solar Valve Kit This label must be located as shown in Fig 16 over the boiler hot water the...

Страница 17: ...nd remove the cover See Fig 17 Remove the front cover of the cylinder by pulling it forwards Remove the screws securing the front of the control box to provide access to the terminals on the control b...

Страница 18: ...rain back unit is pre filled and should not need any water added It is important to prime the drain back unit pump unscrew the centre cap and rotate the spindle using a small screwdriver Replace the c...

Страница 19: ...modes on the display The push button provides the means to operate the cylinder During normal operation the system can be turned on and off using the button When the button is held in for 5 seconds t...

Страница 20: ...eat exchanger Drain back unit pump Cylinder pump Mains cold water inlet Warm water to boiler Hot water to taps Solar valve Alpha SolarSmart 90 System Operation 6 1 WORKING PRINCIPAL Fig 21 The solar c...

Страница 21: ...d possible solutions Temperature display The display see Fig 20 will display the solar cylinder temperature 10 70 C for 4 seconds followed by the operating mode on or oF for 2 seconds after which the...

Страница 22: ...d check the operation 2 Ensure that all system connections and fittings are sound Remake any joints and check the tightness of any fittings that may be leaking 3 Inspect and clean if required the filt...

Страница 23: ...G Y G Y G Y W Br Br Br Bl Bl Bl Bl W W Br Br Br Br Cylinder Pump G Y Bl Br DBU Pump Br Brown Bl Blue W White G Y Green Yellow NOTE Do not connect any other external controls Upper Cylinder Sensor Lowe...

Страница 24: ...ll operate When the cause has been rectified the system control can be reset by pressing the button Code 74 No circulation in the collector Check water level in drain back unit Check the difference in...

Страница 25: ...normal operating display 9 3 COLLECTOR SENSOR TEMPERATURE AND RESISTANCE DATA C 0 5 10 15 20 25 30 C 35 40 45 50 55 60 65 C 70 75 80 85 90 95 100 Ohm 32 15 26 31 19 86 15 89 12 49 10 00 8 06 Ohm 6 53...

Страница 26: ...p PCB Set of two cylinder temperature sensors Front housing cylinder Top cover cylinder Bottom cover and screw cylinder Cylinder manifold seal kit Temperature pressure relief valve 90 C 7 bar Pressure...

Страница 27: ...you complete the inspection record below Note Always use the manufacturer s specified spare parts when replacing any parts Date of Installation Name of Installer Address Postcode Telephone No Cylinder...

Страница 28: ...n carefully prepared but we reserve the right to alter the specification at any time in the interest of product improvement Alpha Therm Limited 2006 Alpha Therm Limited NepicarHouse LondonRoad Wrotham...

Отзывы: