Battery installation / Battery replacement procedure
1.
Press finger tab to release battery cover and connect the wire harness to the battery.
2. Install the battery into the compartment ensuring the battery retaining clip secures the battery (for
batteries up to 8Ah).
3. Replace the battery cover.
4. Plug the unit into AC power. The green AC PRESENT LED should illuminate.
5. Verify proper function by unplugging the AC line cord from the AC receptacle. Within approximately 30
seconds the alarm should sound for 1 second (it may take longer to trigger this alarm if the load is very
light or not connected). AC mode LED (Green) will display then turn off and the ON-BATTERY LED
(Green) will illuminate.
6. Reconnect the unit to an AC receptacle (if no AC power is present and if the battery is installed, press DC
start button for 2 seconds). The unit is ready to be placed into service.
Risk of explosion if battery is replaced by an incorrect type. Recycle spent batteries in
accordance with local regulations.
WARNING!
FlexPoint Audible alarms/Visual indicators
010-353-B8-001 Rev. B (06/2015)
AUX
SILENT
ALARM
DC START
AUX
SILENT
ALARM
DC START
AUX
SILENCE
ALARM
DC START
AUX
SILENCE
ALARM
DC START
AUX
SILENCE
ALARM
DC START
AUX
SILENCE
ALARM
DC START
AUX
SILENCE
ALARM
DC START
AUX
SILENCE
ALARM
DC START
AUX
SILENCE
ALARM
DC START
AUX
SILENCE
ALARM
DC START
AUX
SILENCE
ALARM
DC START
AUX
SILENCE
ALARM
DC START
AUX
SILENCE
ALARM
DC START
AUX
SILENCE
ALARM
DC START
2
Condition
Status LED
Audible Alarm
Description
AC PRESENT
LED (Green)
steady ON
N/A
Condition normal; AC powers load, charges battery.
ON BATTERY
LED (Green)
steady ON
1 second beep on loss
of AC
Input fails; battery powers load.
LOW BATTERY
LED (Green)
flashing
1 beep every 15
seconds
Alarm is triggered when AC fails and battery is
running low (<11.7 V).
REPLACE
POWER SUPPLY
LEDs (Green)
flashing
N/A
If both Green LEDs are flashing, the power supply
needs to be replaced.
REPLACE BATT
LED (Red)
steady ON
2 beeps, every
15 minutes
The unit automatically initiates a battery test every
180 days. If the unit fails the test, this alarm is
triggered.
BATT MISSING
LED (Red)
steady ON
N/A
The alarm is triggered when the battery is not
installed or not connected.
MUTE
LED (Green)
steady ON
N/A
Green LED is lit when Silence Alarm button is pressed
and an audible alarm is active.
Mounting holes for customer-supplied #12 hardware or equivalent
Keyhole slots for easy mounting
1
2
Always mount unit vertically as shown in Fig. 2.
NOTICE
:
Table 2, FlexPoint battery options
2
2
1
Battery Options
Part
Description
AX-STDBAT-5
Battery 5.1Ah AGM, 1-year Warranty
AX-STDBAT-7
Battery 7.2Ah AGM, 1-year Warranty
AX-LONGBAT-7
Battery 7.2Ah AGM, 3-year Warranty
AX-LONGBAT-8
Battery 8Ah AGM, 3-year Warranty
Fig. 2, FlexPoint Dimensions (in/[mm])
(viewed from back/right side)
Fig. 3, FlexPoint AC input, DC output power connector locations
Coaxial connector
7-pin output
cable connector
Table 1, 7-pin connector and pin-outs
Pin
Connection
Wire Gauge
1
Positive (+)
16AWG
2
Negative (-)
16AWG
3
Signal Return
24AWG
4
AC failure
24AWG
5
Replace Battery
24AWG
6
Battery Missing
24AWG
7
Battery Low
24AWG
7
1
Line cord
connector
Coaxial
connector
Line cord
connector
FlexPoint 1208-F
FlexPoint 1232-D, 1250-D