APL48-50LFP liFePO

Battery Operation Manual 

  

 

 

2.3

 

– Battery Management System (BMS)

 

 

Integrated Smart BMS technology is adopted for battery modules of APL-LFP to assure smart 
automatic management for batteries. Features of BMS are shown as below: 

 

Overcharge Protection

 

When the voltage of any cell is greater than the overcharge detection voltage and the duration 
exceeds  the  delay  time  of  the  overcharge  detection,  the  protective  plate  judges  that  the  over-
voltage  state  occurs  and  the  charging  MOSFET  is  closed,  charging  to  the  battery  pack  is 
prohibited. 

 

When the voltage of the highest cell after overvoltage occurs restores to the overcharge recovery 
voltage or below, the protection plate judges that the over-charge state has been relieved. At the 
same time, the charging MOSFET is turned on, the charger can charge to the battery  pack, and 
the green RUN light on the protection plate shines during charging. 
The battery pack can still discharge to the load when the overvoltage state occurs. 

 

 

Over-discharge Protection

 

When the voltage of any cell is less than the over-discharge detection voltage and the duration 
exceeds  the  delay  time  of  the  discharge  detection,  the  protective  plate  judges  that  the  over-
discharge state occurs. The green RUN lamp and red ALM lamp are both extinguished, discharge 
MOSFET is closed, and the battery pack is prohibited to discharge to the load. 

 

When discharge under-voltage occurs, the protection plate goes to sleep, and the charging input 
can be waked up by adding a charger. 

 

Overcurrent/short circuit protection and recovery

 

When  the  discharge  current  exceeds  the  short-circuit  protection  current  and  the  duration 
exceeds  the  delay  time  of  the  short-circuit  detection,  the  red  ALM  lamp  is  glitter,  and  the 
protection  plate  enters  the  over-current  protection/short-circuit  protection  state,  under  which 
charge-discharge is prohibited. 

 

After the protection plate enters the overcurrent/short circuit state, it will lock the state until the 
charging input can be activated by adding a charger. 

 

Heat Management

 

With the function of cell and environment temperature detection, when the temperature is too 
high  or  too  low  the  product  will  start  up  alarming  and  protection  function.  The  temperature 
sampling  accuracy  is  less  than 

± 

2

°

C  within  the  operating  temperature  range.  Four  battery 

temperature  detection  points  and  one  ambient  temperature  detection  point  (maximum  16 
battery temperature detection points) are supported by default. 

 

 

 

Содержание APL 48-50 LFP

Страница 1: ...Moorebank NSW 2170 Australia Alpha Power Systems T 02 9602 8331 F 02 9602 9180 E admin alphapower com au W www alphapower com au APL 48 50 LFP Lithium ion Battery Operation Manual APL 48 50 LFP Lithi...

Страница 2: ...Charge Performance 8 3 3 Constant Current Discharge Table 8 3 4 Constant Power Discharge Table 8 Part 4 Operation Maintenance 9 4 1 Requirements for Operation Environment 9 4 2 Parameter Settings of P...

Страница 3: ...ndles Do not place tools or metal objects on the battery Do not direct access to the battery system to the mains grid power outlet Do not put the battery system into fire do not use or storage the bat...

Страница 4: ...ithium iron phosphate battery units in series with the dedicated high performance and high reliability battery management system BMS The output terminal of the battery is connected to the terminal of...

Страница 5: ...elay time of the discharge detection the protective plate judges that the over discharge state occurs The green RUN lamp and red ALM lamp are both extinguished discharge MOSFET is closed and the batte...

Страница 6: ...he equalization function Battery supports up to 7 channels simultaneously to turn on equalization The maximum equalization current is about 75mA Balance will stop when charging stops or the voltage di...

Страница 7: ...able to conduct charging and discharging Note 1 Please refer to Specification of each models for detail BMS parameter setting value 2 LCD display screen is provided as option 3 Anti theft function is...

Страница 8: ...of Cells 15 cells Limited Charge Voltage 54 0 V Discharge Cut off Voltage 42 V Standard Charge Current 10 A Standard Discharge Current 10 A Max Continuous Charge Current 50 A Max Continuous Discharge...

Страница 9: ...liFePO4 Battery Operation Manual Part 3 Technical Characteristics 3 1 Discharge Performance Fig 3 1 Constant Current Discharge Curve of APL LFP 25 Fig 3 1 Discharge Curve of different temperature of...

Страница 10: ...3 33 2 49 1 98 1 65 1 23 0 98 42 0 10 08 4 96 3 97 3 31 2 47 1 96 1 64 1 21 0 96 43 5 10 00 4 92 3 94 3 27 2 45 1 94 1 62 1 19 0 95 45 0 9 91 4 85 3 88 3 22 2 40 1 90 1 58 1 17 0 92 3 4 Constant Power...

Страница 11: ...cid batteries can be replaced by lithium battery of APL48 50LFP if power is matched Table 4 2 Parameter settings of power plant for lithium ion battery No Parameters Units Defaults 1 Charge voltage V...

Страница 12: ...Charge Current 1 0C No Charge Allowed 25 50 Charge Current 0 5C Charge Current 0 75C 1C Charge is allowed when voltage is lower than 3 65V 50 60 Charge Current 0 1C 60 No Charge Allowed Table 4 4 Dis...

Страница 13: ...n port It is adopting RS 232 series port to upload data Contents of data transmit include BMS parameters battery running status alarms etc Generally speed rate of RS 232 is 1200bps RS232 up link commu...

Страница 14: ...ation Batteries shall not be placed in direct sunshine or close to heat source Batteries shall be installed in place with good ventilation to assure enough heat dissipation Batteries shall be placed i...

Страница 15: ...etween battery module and power plant shall be less than 2 0m To make sure similar voltage drop of cable for each battery length of all positive and negative cables should be the same Color for cable...

Страница 16: ...on cable between battery module and power plant shall be less than 0 5V 4 7 Storage The battery storage shall be in the clean and dry ventilation room at the temperature of 0 40 C and shall keep out o...

Страница 17: ...ged Normal charge management Do not need to solve Protection against over voltage Do not need to solve Protection against over temperature or under temperature Ambient temperature is lowerthan 10 or h...

Страница 18: ...lash 1 Flash 2 Alarm light goes off after a few seconds Over temperature under temperature over current protection Flash 1 Flash 2 Discharge Normal Normally on OFF According to the SOC Alarm Normally...

Страница 19: ...ave PACK ON OFF OFF ON OFF OFF PACK 10 001001 Slave PACK OFF ON OFF ON OFF OFF PACK 11 001010 Slave PACK ON ON OFF ON OFF OFF PACK 12 001011 Slave PACK OFF OFF ON ON OFF OFF PACK 13 001100 Slave PACK...

Страница 20: ...CK OFF OFF OFF OFF ON ON PACK 49 110000 Slave PACK ON OFF OFF OFF ON ON PACK 50 110001 Slave PACK OFF ON OFF OFF ON ON PACK 51 110010 Slave PACK ON ON OFF OFF ON ON PACK 52 110011 Slave PACK OFF ON OF...

Страница 21: ...system uses through 6Pin straight PCB welding socket RJ11 to provide RS 232 protocol the pin assignment of RJ11 is defined as follows Table 1 RJ11 Pin Assignment 2 RS 485 The system uses through 8Pin...

Отзывы: