1.3  Operating Conditions

Because SMU-HR batteries, which are valve regulated and virtually sealed, do not give off 

perceptible amounts of gas under normal operating conditions, they can be installed in the 

same environment where people live and work.

Acceptable ambient operating temperature: -40ºF to 131ºF (-40ºC to 55ºC)

• 

Ideal ambient operating temperature: 68ºF to 77ºF (20ºC to 25ºC)

• 

Ambient humidity: ≤ 95%

• 

Operating room or area: ventilated and not fully sealed 

• 

1.4  Capacity

Battery capacity is rated in Ampere hours (Ah) and is the quantity of electricity that can be 

supplied during discharge (See Table 1-1).

The actual capacity is related to the utilization ratio of the active positive and negative 

materials within the battery. The utilization ratio is influenced by the depth of discharge, the 

structure of the battery, and the manufacturing technology. During normal usage, the factors 

that influence the actual capacity are discharge rate, depth of discharge, end voltage, and 

temperature.

The higher the discharge rate, the lower the available capacity.

• 

As batteries get colder, the available capacity is reduced. This is related to the kinetics of 

• 

the electrochemical reactions and the resistivity of the electrolyte (See Fig. 1-1).

NOTE:

Although the battery can be operated at temperatures below 5ºF (-15ºC), the capacity and ability to 

discharge will be dramatically decreased. Similarly, temperatures approaching 122ºF (50ºC) will increase 

water loss and corrosion of the plates, resulting in a shorter battery life.

1.0 

Introduction, 

continued

Fig. 1-1, Available Capacity vs. Ambient Temperature

Capacity (%)

Ambient Temperature (ºC)

-40

-30

-20

-10

0

10

20

30

40

50

60

   0

 20

 40

 60

 80

100

Содержание AlphaCell SMU-HR 12-100

Страница 1: ...AlphaCellTM SMU HR Series Batteries Technical Manual Effective July 2010...

Страница 2: ......

Страница 3: ...s manual are for illustrative purposes only These photographs may not match your installation NOTE Operator is cautioned to review the drawings and illustrations contained in this manual before procee...

Страница 4: ...rature and Battery Life 10 1 6 Internal Resistance and Short circuit Current 10 2 0 Charging Procedures 11 2 1 Float Charge 11 2 2 Recharge Following Discharge 12 3 0 Storage 13 4 0 Maintenance 15 4 1...

Страница 5: ...Current Limit 13 Fig 3 1 Capacity vs Storage Time 14 Fig 4 1 VRLA Battery Regular Maintenance Record 16 Table 1 1 General Electrical and Mechanical Specifications by Model 8 Table 1 2 Internal Resista...

Страница 6: ...this product the following symbols have been placed throughout this manual Where these symbols appear use extra care and attention The use of ATTENTION is only for specific regulatory code requirement...

Страница 7: ...type and rating Never install old or untested batteries Do not charge batteries in a sealed container Each individual battery should have at least 0 5 inches of space between it and all surrounding su...

Страница 8: ...asy terminal access for installation and maintenance and can be upright side or end mounted The SMU HR series includes eight models to make it easier to install and maintain the batteries 1 1 Features...

Страница 9: ...ttery The utilization ratio is influenced by the depth of discharge the structure of the battery and the manufacturing technology During normal usage the factors that influence the actual capacity are...

Страница 10: ...k for shorted cells improperly set voltages filter cleaning on ventilation systems etc 1 6 Internal Resistance and Short circuit Current The internal resistance of the battery is affected by temperatu...

Страница 11: ...t value 1 Maintain the pre set voltage and decrease the current until a minimum defined value is 2 reached Complete the recharge at a final constant voltage value equal to or less than that defined fo...

Страница 12: ...7Vpc at 68F 20C see Table 2 1 and a maximum charge current of 0 25 C8 amperes Fast Charge If it is necessary to reduce the recharge time charge with a maximum voltage of 2 4Vpc at 68F 20C and a maximu...

Страница 13: ...lf discharge is about 23 per month at 77F 25C During prolonged storage it is necessary to boost charge the battery at least every 6 months to maintain a fully charged condition of the battery see Sect...

Страница 14: ...an ambient temperature of 32 F to 95 F 0 C to 35 C It is important to track open circuit voltage which is related to the density of the electrolyte If the open circuit voltage is lower than 12 6V blo...

Страница 15: ...m Quarterly Maintenance Measure and record the floating voltage of every on line battery If the voltage of more than two cells is less than 13 0V after temperature adjustment discharge the battery and...

Страница 16: ...A Battery Regular Maintenance Record No Voltage V No Voltage V 1 13 2 14 3 15 4 16 5 17 6 18 7 19 8 20 9 21 10 22 11 23 12 24 Visual check Type Place Test Status Qty Total Voltage V Room Temperature C...

Страница 17: ...7 35 8 14 7 9 50 4 75 2 60 5 1 Discharge Data with Constant Current Amperage values for each battery model as a function of time and voltage 77 F 25 C 5 0 Discharge Specifications SMU HR 12 9 End volt...

Страница 18: ...276 193 142 80 2 55 8 23 9 15 5 9 20 4 65 1 85V 244 184 128 73 9 52 0 23 1 14 5 9 07 4 52 SMU HR 12 100 End voltage 5Min 10Min 15Min 30Min 1h 3h 5h 10h 20h 1 60V 320 218 180 114 75 0 30 0 19 1 10 0 5...

Страница 19: ...2 06 1 85V 118 89 5 62 0 36 3 21 8 9 41 5 89 4 05 2 03 5 2 Discharge Data with Constant Power Wattage values for each battery model as a function of time and voltage with constant Watts per cell 77 F...

Страница 20: ...538 390 283 160 107 44 7 28 0 18 9 9 32 1 85V 488 370 256 150 100 43 3 27 1 18 6 8 95 SMU HR 12 100 End voltage 5Min 10Min 15Min 30Min 1h 3h 5h 10h 20h 1 60V 740 518 405 254 154 58 0 43 3 23 7 10 5 1...

Страница 21: ...Forms 6 1 Discharge Recording Form Cell Inital Voltage Cell Voltage at Time Period End 15min 30min 1hr 2hr 3hr 4hr 4 30hr 5 hr Model of Battery Date Battery Bank No Room Temperature Charging Current T...

Страница 22: ......

Страница 23: ...s Stortford Hertfordshire CM22 7PA United Kingdom Tel 44 1279 501110 Fax 44 1279 659870 Alphatec Ltd 339 St Andrews St Suite 101 Andrea Chambers P O Box 56468 3307 Limassol Cyprus Tel 357 25 375 675...

Отзывы: