COMMISSIONING
(1)
Fill the DHW pipework.
Open the cold mains inlet valve. Turn on all the hot water taps and allow water
to flow until there is no air present. Turn off the taps and check for water
soundness, rectifying if necessary.
(2)
Fill the DH circuit pipework.
Open the DH flow and return isolation valves.
Manually open the DHW valve to allow water to flow by pushing the white lever
down to midway and in on the valve’s actuator. This will hold the valve in the
open position. Check for water soundness, rectifying if necessary.
(3)
Fill the Direct Central Heating system.
Open the CH flow and return isolation valves and allow DH water to flow into the
system. Vent each radiator etc to remove any air and check for water
soundness, rectifying if necessary.
(4)
Turn on the electrical supply.
Open a hot water tap and check that the DHW valve opens, the CH valve closes
and hot water is supplied. Set the outlet temperature as required by adjusting
the thermostat’s knob (Setting 9 gives approximately 55 to 60’C). Turn off the
tap and check the DHW valve closes and the CH valve opens.
6/
SERVICING and COMPONENT REPLACEMENT
Each component is easily removable for replacement or cleaning without needing
to remove other components