Turning the Novus FXM On and Off

Under normal operation, the FXM is always powered ON to supply 

uninterruptible power to the load. By turning off the FXM, the power 

supply to the load will also be disconnected. If for any reason you 

need to turn off the FXM while maintaining power to your critical 

load, make sure that you have a plan in place to provide an alternate 

source of power.

Turn Off Procedure

Turn off the AC input circuit breaker.

1. 

Turn off the battery circuit breaker. The status LED turns off and 

2. 

the LCD panel goes blank.

The FXM is now turned off and no backup power is supplied to the 

load.

Turn On Procedure (LINE mode)

Before you put the FXM back into commission, make sure that the 

line is qualified and the batteries are fully charged.

Turn on the battery circuit breaker. The LCD displays 

1. 

STANDBY

 

and the fan turns on for about a minute.

  Notes

If the temperature is below –15ºC, the LCD display may not func-

i. 

tion. See "Troubleshooting" on page 88.
Turn on the AC input circuit breaker. The FXM qualifies the line 

ii. 

power. The LCD displays 

RETRAN

, then shows 

LINE

BUCK

 or 

BOOST

. The status LED turns on.

If there is no line power, the FXM will remain in STANDBY mode 

iii. 

until it the line power is qualified. If you need to provide backup 

battery power to the load, perform a manual start by using the 

inverter command (See “Operating the Novus FXM Inverter” on 

page 40).
The FXM has auto-frequency detection. When it is first turned 

iv. 

on, it senses the line frequency and adjusts its output frequency 

to match that of the input (Also see "Specifications" on page 89). 

The load should be receiving power, If not, perform troubleshoot-

ing on page 87.

37

Operation

Doc# 017-201-B0 Rev 0408

17                                                                                                                                    Doc# 017-201-BO Rev 0408

Содержание FXM 650

Страница 1: ...interruptible Power Supplies Operator s Manual Rev 0408 Power Novus FXM 650 1100 2000 Total Power Solutions by Alpha Technologies Power Novus FXM 650 1100 2000 Total Power Solutions by Alpha Technologies ...

Страница 2: ...s All units operate in the same way unless stated otherwise in this manual The FXM 650 is available in the following two version FXM 650 24VDC with a 24 VDC battery string voltage FXM 650 48VDC with a 48 VDC battery string voltage The FXM 1100 is available in the following version FXM 1100 48VDC with a 48 VDC battery string voltage The FXM 2000 is available in the following version FXM 2000 48VDC ...

Страница 3: ...FXM operation 2 Battery Connector This connects the external batteries to the FXM 3 Internal Fan This microprocessor controlled fan regulates the FXM s internal temperature for optimum performance It must not be blocked If the fan fails an Alarm is generated See Troubleshooting on page 87 4 LAN This optional RJ 45 connector is the FXM s Ethernet connector 14 FXM UPS Operator s Manual Doc 017 201 B...

Страница 4: ...easure the voltage Note The battery voltage test points are not and should not be used as a power outlet 7 RS 232 This DE 9 connector allows you to use a straight through DE 9 to DE 9 connector cable to connect the FXM to a computer for remote control and monitoring See Communicating with the RS 232 Interface on page 44 8 Battery Temp This connector attaches the battery temperature sensor 6 7 8 FX...

Страница 5: ...1 See also Novus User Software Operations Relay and Load Shed on page 63 For Contact C6 the default factory configuration for the FXM 650 48 FXM 1100 and FXM 2000 is 48VDC output FXM 650 24 is 24VDC but it can be factory configured as a dry contact Figure 3 5 shows the contact s layout while Figure 3 6 shows the 48VDC or 24VDC terminal block layout The contacts have a maximum rating of 1A at 250V ...

Страница 6: ... as a dry contact 48VDC 500mA FXM 1100 2000 650 48 or 24VDC FXM 650 24 from the external batteries Microprocessor 18 16 17 Contact C6 Figure 3 6 48VDC 24VDC Contact Layout De energized Shown Factory Default for C6 10 Contacts C7 and C8 These optically isolated inputs let you attach an external switch panel for remote control of the FXM or have the FXM control Alpha Technologies s optional Automati...

Страница 7: ...omatic Transfer Switch ATS is connected it will cause the ATS to switch the load from line power to the FXM s battery backup power 48VDC or 24VDC from the external batteries Contact C8 Microprocessor 23 24 Figure 3 8 ATS Layout 11 Status and Alarm LEDs Status When this green LED is on the FXM is in Line mode and line power is provided to the load When it is flashing it is in Inverter mode and back...

Страница 8: ...s input protection It must be on for proper FXM operation 13 Input Terminal Block This terminal block is the FXM s AC line power input 14 Output Terminal Block This terminal block is the FXM s AC power output 12 14 13 13 14 12 Figure 3 9 Front Panel Description cont d 19 Overview Doc 017 201 B0 Rev 0408 8 ...

Страница 9: ... treated as an Isolated DC 4 return DC I as defined in GR 1089 CORE Procedure For FXM 650 48 1100 2000 48 V battery string number the 1 batteries from 1 to 4 with labels or tape For FXM 650 24 24 V battery string number the batteries from 1 to 2 See Figure 3 11 Battery 4 Battery 3 Battery 2 Battery 1 To Positive Terminal To Negative Terminal Optional in line fuse Tape the battery temperature senso...

Страница 10: ... connector polarity and DC voltage with a DC volt 4 meter If correct attach it to the FXM s external battery connec tor Otherwise perform troubleshooting before connecting it to the FXM Route the sensor end of the battery temperature cable to the 5 batteries Tape it to the side of battery as shown in Figure 3 11 If multiple battery strings are used repeat steps 1 to 4 as re 6 quired 29 Installatio...

Страница 11: ... Figure 3 4 User Inputs 10 in Figure 3 4 Connect the load to the FXM s Output terminal block 3 14 in Fig ure 3 9 Torque to 12 0 lb in 1 4 N m Connect the line power to the FXM s AC Input terminal block 4 13 in Figure 3 9 Torque to 12 0 lb in 1 4 N m WARNING Before proceeding verify that the line wire is attached to the line terminal block the ground wire is attached to the ground terminal block an...

Страница 12: ...e the loads are directly connected to the line power without any conditioning The ATS and GTS can be used alone or together to allow the use of 3 different back up sourc es line batteries and or generator Refer to the ATS GTS Installation Manual Alpha P N 020 161 B0 for details WARNING Make sure you have read and understood the instructions given in the ATS GTS Installation Manual before making an...

Страница 13: ... panel on page 34 Turning the FXM On and Off on page 37 Replacing the batteries on page 83 Operating the Novus FXM on page 40 Making measurements on page 42 Viewing the 25 event log on page 43 Communicating with the RS 232 interface on page 44 33 Doc 017 201 B0 Rev 0408 13 Doc 017 201 BO Rev 0408 ...

Страница 14: ...ency 50 Hz or 60 Hz Sense Type setting Normal N or Generator G see Operating the Novus FXM Sense Type on page 40 C Present operating mode LINE mode shown See Figure 7 2 D Control buttons SELECT Pressing SELECT moves you down 1 level in the menu tree Figure 7 3 or accepts a change when programming See page 40 SCROLL Pressing SCROLL moves you through the submenus Figure 7 3 or toggles between choice...

Страница 15: ...is transferring from the state it is now in into Inverter mode STANDBY The FXM is on and waiting for the line power to qualify or the user clear some faults CAUTION Do not touch the AC output terminals which may be still energized BYPASS This mode is manually set with the Control Menu See Figure 7 4 Control Menu INV BYPASS This locks the unit into line mode and turns off the battery charger so the...

Страница 16: ...S menu Figure 7 5 lets you measure various inputs outputs and other values The available measurements are VIN VOUT IOUT AC BATT TEMP FREQ IN OUTPUT PWR BATT VOLT CHGR CUR DATE TIME INV COUNT INV TIMER SHED TIMER 1 2 OR 3 VERSION The ALARM and FAULT menus Figures 9 1 and 9 2 are invisible and disabled until the FXM has a malfunction When the front panel s alarm LED is on or flashing press SELECT On...

Страница 17: ...rn on the battery circuit breaker The LCD displays 1 STANDBY and the fan turns on for about a minute Notes If the temperature is below 15ºC the LCD display may not func i tion See Troubleshooting on page 88 Turn on the AC input circuit breaker The FXM qualifies the line ii power The LCD displays RETRAN then shows LINE BUCK or BOOST The status LED turns on If there is no line power the FXM will rem...

Страница 18: ...e load until the batteries are drained to a preset level which triggers the FXM to shutdown automatically If it is not necessary to operate the FXM in inverter mode you should switch the FXM back to Line mode as soon as possible Procedure Turn on the input circuit breaker The FXM qualifies the line 1 power The LCD displays RETRAN then shows LINE BUCK or BOOST The status LED turns on Note If the FX...

Страница 19: ...rger and makes the output voltage equal to the input voltage This is done to Replace the batteries See page 83 OR Allow the use of a break before make manual bypass switch so the FXM can be shut off for maintenance or replacement without interrupting power to the load SELF TEST Self Test This is the FXM s self test When it is turned on the FXM is forced to verify its proper operation by providing ...

Страница 20: ...fied technician acting under the instructions of Alpha Technologies customer service department Failure to contact Alpha technologies before doing this procedure could result in voiding of the warranty QUAL TIME Line Qualify Time This lets you set how long it takes for the FXM to return to Line mode after the line has become requalified to make sure the line is stable It can be set to 3 10 20 30 4...

Отзывы: