29
9400016-J0 Rev D
Table E — Cable size equivalents (AWG to Metric)
Cable size
(see notes 1 and 2)
Circular mils
Square millimeters
Equivalent metric cable
0 AWG (or 1/0)
105600
53.48
50 or 70
00 AWG (or 2/0)
133100
67.42
70
0000 AWG (or 4/0)
211600
107.2
120
313 MCM (or kcmil)
313600
159
150 or 185
350 MCM (or kcmil)
350000
177.36
185
373 MCM (or kcmil)
373700
189
185 or 240
500 MCM (or kcmil)
500000
253.36
300
535 MCM (or kcmil)
535300
271
300
750 MCM (or kcmil)
750000
380.00
400
777 MCM (or kcmil)
777700
394
400
7.1.2 Recommended Torque Values
7.2 Grounding
Connect the isolated power system battery return bus (BRB) to the building master ground bus (MGB), or floor
ground bus (FGB) in a larger building. This acts as a system reference and as a low impedance path to the ground
for surges, transients, noise, etc. The MGB or FGB must have a direct low impedance path to the building grounding
system.
The cable from the power system to the MGB or FGB must be sized to provide sufficient ampacity to clear the larg-
est fuse or breaker on the power system, excluding the battery protection fuse or circuit breaker. This is the mini-
mum requirement. Other factors including length of cable and special grounding requirements of the load must also
be factored in. The insulated cable must be equipped with two-hole crimp type lugs and must not have any tight
bends or kinks.
Table G — Typical ground reference conductor selection
Power system ampacity
Recommended ground reference conductor size
< 30A
#10
30 – 100A
#6-2
100 – 400A
0000
400 – 800A
350 MCM
>800A
700 MCM
The power system frame must also be connected to the MGB or FGB. This is done for personnel safety and to meet
many telecom grounding requirements. Each bay must have its own frame or site ground connection. Refer also to
the customer connections drawing at the back of the manual.
• Clear hole connections (nut and bolt)
• PEM studs
• PEM threaded inserts
• Thread formed connections (in copper bus bar)
Grade 5 rated hardware is required for these torque values.
Table F lists the recommended torque values for
connection to the power system with the following
hardware:
Table F — Recommended torque values
1/4"
8.8 ft-lbs
3/8"
32.5 ft-lbs
1/2"
73 ft-lbs