053-996-B0 Rev D
Page 24 of 26
10.
Log on to the CXC and go to
Logs and Files > Manage Configuration File > Upload Site Configuration
and select the saved *.cfg file. After the upload do a
Submit Changes
. Make sure the site information is
checked to save it, and click
Accept
.
11.
Go to
Logs and Files > Manage Editable Text Files > Upload Dynamic Text File
and select the saved
*.tfg file. You do not need to submit changes; it is already saved.
12.
Use a meter to verify the bus voltage and current shunt. Recalibrate as required due to differences in the new
CXCI+.
13.
Replace converters and remove LVD bypass.