010-619-J0 Rev B
Page 10
3.2
Distribution
3.2.1
4.8kW System Distribution Module
0300165 (Cordex CXRF-HP 48-1.2kW center mounting 2RU shelf for systems up to 4.8kW)
The distribution component uses up to four bullet-type breakers that can be factory configured for either
4 load breakers or 2 load/2 battery breakers, and up to ten GMT fuse positions. The distribution module
also allows for termination of two battery strings and includes a 150A battery shunt. Also available as
an option is a 100A low voltage battery disconnect.
This module contains a unique sliding connection point system to allow for the several dual-hole lug
terminations in a compact space. See Wiring and Connections chapter of this manual for more details.
Figure 5:
4.8kW System Distribution Module
3.2.2
3.6kW System Distribution Module
030-851-20 (Cordex CXRF-HP 48-1.2kW, 19" 1RU shelf, 3 modules, w/ GMT fuses up to 3.6kW)
The shelf incorporates a distribution module for DC fuse output as well as battery connections. The
module accommodates up to eight GMT fuse positions (limited to 40A maximum). Two battery-landing
positions and an 80A battery shunt are also provided.
The module has low voltage disconnect (LVD) options, which are in series with either the battery or the
load.
The GMT fuse output connection points are accessible from the front of the module via plug-in connec-
tors. The battery connections are accessible from the rear of the module via 2-hole lug inputs.
Figure 6:
3.6kW System Distribution Module
Содержание Cordex HP 48 1.2kW
Страница 2: ......
Страница 4: ......
Страница 10: ...vi...
Страница 14: ...010 619 J0 Rev B Page 4...
Страница 16: ...010 619 J0 Rev B Page 6 Figure 1 Single Shelf Figure 2 Dual Shelf Figure 3 2RU Shelf...
Страница 28: ...010 619 J0 Rev B Page 18...
Страница 30: ...010 619 J0 Rev B Page 20...
Страница 46: ...010 619 J0 Rev B Page 36...
Страница 56: ...010 619 J0 Rev B Page 46...
Страница 58: ...010 619 J0 Rev B Page 48...