Model 

TST220 

TST232 

rated Amps 

20A 

32A 

Dimension 

19"2U (87x483x259mm -- HxWxD) 

Weight 

6kgs 

Input voltage 

220

±

15% 

Output voltage 

220

±

15% 

Input rated frequency 

50Hz/60Hz 

Overload Capability 

150% 

<4ms - synchronization 

transfer time 

<10ms - non-synchronization 

Efficiency 

>99% 

Transfer mode 

Break before make 

Peak factor 

4:1 

Operation Temp 

.-5C-40C 

Storage Temp 

.-25C-60C 

Humidity 

<93% non condensing 

Communication 

  RS485 + Dry contacts 

 

2

2

.

.

3

3

 

 

S

S

y

y

s

s

t

t

e

e

m

m

 

 

P

P

r

r

i

i

n

n

c

c

i

i

p

p

l

l

e

e

 

 

MAIN  CNTROL

CUR

LED 

DRY CONTACT

RS485

CUR

K1-3

INPUT1-L

INPUT1-N

INPUT2-L

INPUT2-N

OUTPUT-L

K1

S1

S2

K2

K3

OUTPUT-N

T1

1

3

2

4

 

Note:   

1.

 

K3 

 automatic bypass switch. When system  error,  INPUT 1  offer  uninterrupted  power  to the 

load. 

2.

 

K2 

 output relay. When input1 and INPUT 2 have issue at the same time, the system cut down 

the output by K2. 

3.

 

K1 

 switch relay between INPUT 1 and INPUT 2. 

4.

 

S1 

 input switch of INPUT 1 

5.

 

S2 

 input switch of INPUT2. 

Содержание TST200 series

Страница 1: ...TST200 User s Manual 1 11 TST200 series Static Transfer Switch USER MANUAL Version 1 0 Date Nov 2009...

Страница 2: ...sting and burn in through out the production process Power is certified by TUV in accordance with ISO9001 and can be your reliable power solution provider D Di is sc cl la ai im me er r Unless special...

Страница 3: ...de well for later reference The TST200 needs to be installed by professionals and please pay attention to the following points prior to installation 1 Please check the input voltage or voltage of batt...

Страница 4: ...o commencing the installation Please follow the local stipulation meantime Any operation against safety requirement or against design manufacture safety standard and are out of the manufacturer warran...

Страница 5: ...of STS maintenance l Hot pluggable l Transfer time less than 4ms when input power are synchronization and transfer time is less than 10ms in case of input non synchronization l Integrated Maintenance...

Страница 6: ...ion Temp 5C 40C Storage Temp 25C 60C Humidity 93 non condensing Communication RS485 Dry contacts 2 2 3 3 S Sy ys st te em m P Pr ri in nc ci ip pl le e MAIN CNTROL CUR LED DRY CONTACT RS485 CUR K1 3 I...

Страница 7: ...e in synchronization Green input 1 normal 2 Input 1 Red input 1 fault 3 Output 1 Green output using input 1 Green Output normal 4 Output Red Output fault 5 Switch switching between input 1 and input 2...

Страница 8: ...on fault 1 Dry contact Left 4 Input 2 fault 2 Circuit breaker Input 1 circuit breaker 3 Connector Input 1 L 4 Connector Input 1 N 5 Connector Earth 6 Connector Input 2 L 7 Connector Input 2 N 8 Circui...

Страница 9: ...dule and subrack is same to that on outer carton 4 4 2 2 L Lo oc ca at ti io on n Please install the equipment in a location of Dry Clean Cool with good ventilation l Working temperature 0 40 l Storag...

Страница 10: ...nd repeat the above action until it is firmly secured 4 4 4 4 2 2 C Co on nn ne ec ct ti in ng g t th he e c ca ab bl le e For the user operation safety cut off the power before installation Connect A...

Страница 11: ...e input 1 switch the STS will resume to input 1 At auto position you can not manually choose input 1 or input 2 5 5 4 4 M Ma ai in nt te en na an nc ce e B By yp pa as ss s T Te es st t Plug out the S...

Отзывы: