Connecting the TRI POWER X33 HE to the Battery Box (optional)
THE CONNECTION BETWEEN THE TRI POWER X33 HE AND THE BATTERY BOX MUST BE MADE
WITH THE DEVICES SWITCHED OFF AND UNPLUGGED FROM THE MAINS
Tri Power X33 HE shutdown procedure:
Turn off all the devices connected to the USP, or use (if installed) the remote bypass option.
Turn
off the TRI POWER X33 HE following the correct procedure (see “Switching off the TRI POWER X33
HE”, in the “USE” section).
Open all isolators and fuse holders in the TRI POWER X33 HE.
Isolate the TRI POWER X33 HE completely from the mains power supply, by opening all the external
protection devices located on the input and output lines.
Wait a few minutes before working on the TRI POWER X33 HE.
Remove the TRI POWER X33 HE terminal cover (see “Operations to access the terminals of the TRI
POWER X33 HE").
Connecting the battery box:
Make sure that the battery voltage of the Battery Box corresponds to that allowed by the TRI POWER X33
HE (check the data plate on the Battery Box and the TRI POWER X33 HE manual)
IMPORTANT:
make sure that SWBATT fuse holders of the TRI POWER X33 HE and Battery Box are open.
Before making any connection read carefully the instructions in the Battery Box manual.
Connect the cables coming from the Battery Box to the TRI POWER X33 HE terminal board (see figure
below), making sure to respect the polarisation. The first connection to be made is that of the yellow-green
protection cable.
Once all these operations have been carried out, replace the previously removed terminal covers on the TRI
POWER X33 HE and on the Battery Box
Checking installation:
Insert the fuses in the SWBATT fuse holders of the Battery Box.
Close the SWBATT fuse holders of the Battery Box and the TRI POWER X33 HE.
Carry out the TRI POWER X33 HE start-up procedure indicated in this manual.
After about 30 seconds, check that the TRI POWER X33 HE is operating correctly: simulate a black-out by
opening the SWIN input isolator of the TRI POWER X33 HE. The load should continue to be powered, and
the “battery power” LED should light up on the TRI POWER X33 HE control panel. The latter should beep at
regular intervals. Once the SWIN input isolator has been closed again, the TRI POWER X33 HE should
resume operating on mains power.