Using
the
On/Off
Button
(Continued)
Shut
off:
Press the on/off button for more than 3 seconds.
Self
test:
When the unit is connected to line power, press the on/off button.
Buzzer
off:
Except for the low battery and overload alarms, turn off the buzzer by pressing the on/off button for 1 second.
Alarms
and
Troubleshooting
This unit has several audible alarms. To turn off the alarm, press the power button.
Slow
Alarm
(1
beep
every
2
seconds):
Most alarms except for low battery and overload. See the troubleshooting table.
Low
Battery
Alarm
(1
beep
every
1
/
2
second):
The unit is operating on battery power and the battery is almost
discharged. This alarm cannot be shut off.
Overload
(continuous
beeping):
The unit is overloaded and it automatically turns itself off. Disconnect unnecessary loads
and restart the unit. This alarm cannot be shut off.
Symptom
Troubleshooting
Table
Causes
Action
Unit
does
not
turn
on,
the
LED
is not on.
The power switch is not
pushed.
Push it for more than 1 second
Battery voltage less than 20
VDC.
Plug the unit into the line for at
least 6 hours to recharge the
battery then restart.
Load less than 20W when
unit is in battery mode.
This is normal. The unit's "green
mode" is active.
PCB failure.
Contact AOE.
Unit
is
always
in
battery
mode.
Power cord loose.
Plug it in.
AC fuse blown or breaker
tripped.
Replace the fuse or reset the
breaker.
PCB failure.
Contact AOE.
Backup
time
less
than
predicted
Battery is not charged.
Plug the unit into the line for at
least 6 hours to recharge the
battery then restart.
PCB failure.
Contact AOE.
The
buzzer
is
continuously
beeping
The unit is overloaded.
Turn off some of the loads.
Page
3
to
7