For XM3 units in service, backup battery power will not be available during this procedure.

Before removing the Inverter Module, verify the power supply device address is correct.

The power supply device address must not be set to zero and no two power supplies monitored by a single DM3 Series Transponder can have the same address. Power supplies must have 1, 2, 3, 4 or 5 as an
address.

To verify the power supply’s address, go to the LCD display on the inverter module and enter the “PWR CNFG” menu. Scroll to the “Device Address” menu item and verify the device address is set to something
other than 0 (Zero).

If power supply data will not display.

Removing the Inverter Module:

Service personnel must verify the Inverter Module battery breaker remains in the OFF position until instructed to return the unit to service.

Содержание AlphaNet DM3 Series

Страница 1: ...AlphaNet DM3 Series Transponder Installation Quick Start Guide AlphaNet DM3 Series Transponder...

Страница 2: ...DM3 DM3...

Страница 3: ...DM3X...

Страница 4: ...e SNMPv3 Notification settings IPv6 while DM3 Series proprietary options may be set through type 11 TLV entries The SCTE HMS MIBs may need to be compiled into a MIB browser before it can be used to mo...

Страница 5: ...If SNMP traps not received Installation Replacement Procedure...

Страница 6: ...can have the same address Power supplies must have 1 2 3 4 or 5 as an address To verify the power supply s address go to the LCD display on the inverter module and enter the PWR CNFG menu Scroll to th...

Страница 7: ...recommended that the screws be tightened alternately a few turns at a time so the transponder aligns in parallel to the Inverter Module When connecting the DM3 Series Transponder to the power supply...

Страница 8: ...and powered by utility AC 2 Switch battery breaker ON 3 The transponder LEDs will all blink in unison upon initial power up The RDY LED will then begin blinking steadily indicating normal processor a...

Страница 9: ...address field The General Configuration page will appear and display connectivity power levels and power supply status information such as alarms output voltage output current and individual battery v...

Страница 10: ...porary Static IP address to be manually configured to 192 168 100 2 Remote Web Server Access Connect the computer to the cable modem network launch an Internet browser e g Internet Explorer and enter...

Страница 11: ...AlphaNet DM3 Series Transponder Installation Quick Start Guide...

Страница 12: ...e right to make changes to the products and information contained in this document without notice Copyright 2020 Alpha and Outback Energy GmbH All Rights reserved Headquarter Germany Hansastrasse 8 D...

Отзывы: