Alpha ESS Co., Ltd.
Page 57 of 74
Your Smart Energy
When the safety regulation is set as AS4777.2, the secondary sub-options can be se-
lected according to the region or local grid company (Please refer to Appendix 2). If
end user wants to change or view the safety regulation, please contact the manufac-
turer or your installer.
Step 6:
The max feed-in can be set after chosen the safety regulation in the same
page.
Step 7:
After finishing the WIFI setting, all the status can be found on the main page.
The firmware version also can be checked in the ‘Firmware information’ and the safety
regulations/regional application standard can be checked in the ‘Inverter information’
(only the installer or service engineer can change the safety regulation and regional
application standard after commissioning).
8.4
Generation Limit Control *
2. Enter the account and password, login your account
3.
Storage System Maintenance
and
Instruction Management
.
4. Command Type: Software Limit Enable/Disable, Hardware Limt Enable/Disable or
S&H Limit Enable/Disable and enter the inverter SN