CONNECTING POWER TO ALPHA-PAGE

                                                                              

Alpha-Page receives primary power from a 12VAC, 20VA power transformer. DO NOT

               

use any power transformer with a secondary voltage

                                                                                     rating of anything other than 12VAC.

                                                            

Connect the transformer secondary terminals to the two "AC" terminals on the MLS-SPU1
board, polarity does not matter. Use 18 AWG wire. Refer to drawing C022397-5. If the 12V, 7
amp-hour battery is to be used (for power back-up) it should be connected according to drawing
C022397-5. Make sure the red wire of the MLS-H1 battery cord (included with battery) is
connected to the positive (+) terminal of the battery via the quick-disconnect connector. The
black wire of the MLS-H1 battery cord must be connected to the negative (-) terminal of the
battery. The other end of the MLS-H1 cord is connected to the MLS-SPU1 board. Connect the
red wire to the "B+" terminal

                                               . Connect the black wire to the "B-" terminal.

                                                   

    

MLS-H1 may be

factory connected. Place the battery in the battery tray located in the bottom, center of the MLS-
EC1 enclosure.

MESSAGE PROGRAMMING

                                                     

A nurse call paging system would be of little use if the messages being sent to pagers

could not be user programmed to include information such as a patients name and the exact
location (room number) the patient is calling from. Alpha-Page allows you to program a specific

             

message for each room 

                                      that will be sent to your pagers when a call is placed.

Before the user does any custom message programming, the system contains generic

programming which allows the system to function immediately without needing to be
programmed. Input 1 is programmed as "Input 001", input 2 as "Input 002", etc. The system will
be much more useful with your custom programming.

To enter the programming mode, simply plug a standard "PS/2" type computer keyboard

into the keyboard receptacle located on the MLS-SPU1 board (see drawing C022397-4). The
programming screen appears on the LCD display automatically. The top two rows comprise the
message field. This is where messages (up to 40 characters) will be entered. You may enter any
number, any letter (upper and lower case, use shift for upper case), and most punctuation
symbols. Some keys on the keyboard will not function. To update a message, simply type over
the old message. Use the <backspace> key to move the cursor back one position. Use the <space
bar> to erase the character located at the cursor position.

Enter message on top
two lines of display

P 01,99

D5

Input 001

Current input number 001-256

Delay (minutes) until 2nd page

Pager numbers

1st page

2nd page

Содержание ALPHA-PAGE v4.0

Страница 1: ...MLS Micro Logic Systems ALPHA PAGE v4 0 Nurse call Emergency Call Pocket Paging System installation owners manual APV40125 Toll Free Phone 866 MLS FREE Micro Logic Systems...

Страница 2: ...municating messages it must only be used as supplemental call annunciation in life safety applications such as nurse call emergency call Alpha Page should only be used to enhance the efficiency of a w...

Страница 3: ...pha Page system except transmitter and pagers fits in the MLS EC1 surface wall mount enclosure Determine a suitable location for the MLS EC1 Remember one wire for each room or patient needs to be run...

Страница 4: ...cessor board The data will go through two MLS 485 s then after a protocol conversion will be feed into the TX125 ENC paging transmitter The MLS 485 devices also function as short haul modems This mean...

Страница 5: ...4 076 108 140 172 204 236 13 013 045 077 109 141 173 205 237 14 014 046 078 110 142 174 206 238 15 015 047 079 111 143 175 207 239 16 016 048 080 112 144 176 208 240 17 017 049 081 113 145 177 209 241...

Страница 6: ...lude information such as a patients name and the exact location room number the patient is calling from Alpha Page allows you to program a specific message for each room that will be sent to your page...

Страница 7: ...delay Alpha Page can send a second and repeating page for a call if the call isn t cancelled within a specified time period Use the tab key to move the cursor from the pager field to the delay field E...

Страница 8: ...g for calls on the MLS 32L input boards This indicates normal operation PAGER MEMORY Messages sent to pagers are stored in the memory of the pager This memory can become full When this occurs older me...

Страница 9: ...capcode are not 08782 All pages sent by this version of Alpha Page are programmed to be sent to pager capcodes beginning with 08782 If MLS did not provide your pagers make sure the pagers are program...

Страница 10: ...station 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 input number Room station 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58...

Страница 11: ...8 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 input number Room station 97 98 99 100 101 102 103 104 105 106 107 108 109 110 111 112 113 114 115 116 117 118 119...

Страница 12: ...136 137 138 139 140 141 142 143 144 145 146 147 148 149 150 151 152 153 154 155 156 157 158 159 160 input number Room station 161 162 163 164 165 166 167 168 169 170 171 172 173 174 175 176 177 178 17...

Страница 13: ...200 201 202 203 204 205 206 207 208 209 210 211 212 213 214 215 216 217 218 219 220 221 222 223 224 input number Room station 225 226 227 228 229 230 231 232 233 234 235 236 237 238 239 240 241 242 24...

Страница 14: ......

Страница 15: ......

Страница 16: ......

Страница 17: ......

Страница 18: ......

Страница 19: ......

Страница 20: ......

Страница 21: ......

Страница 22: ......

Страница 23: ......

Страница 24: ......

Страница 25: ...DAMAGES Some states do not allow this exclusion or limitation of incidental or consequential damages so the above limitation or exclusion may not apply STATEMENT OF REMEDY In the event that the produc...

Отзывы: