Touch screen controller

ALNOR Systemy Wentylacji Sp. z o.o. Knowledge Base | www.alnor.com.pl

5

Commissioning

Please follow below parameters table information to do the commissioning. It is recommended that

commissioning should be done by professional technician, and technician should discuss with client before

setting the correct parameters to the ventilation system.

No.

Contents

Range

Default

Unit

Record 

Position

00

Power to auto restart

0-1

1

Main control

01

Electrical heater available

0-1

0

Main control

02

Bypass opening temperature X

5-30

19

°C

Main control

03

Bypass opening temperature

range Y

2-15

3

°C

Main control

04

Defrosting interval

15-99

30

Minuta

Main control

05

Defrosting entering temperature

-9-5

- 1

°C

Main control

06

Defrosting duration time

2-20

10

Minuta

Main control

07

CO2 sensor function value

Main control

08

ModBus address

1-16

1

Main control

21

HRU-ERGO models match/selection

0-7

0

Main control

22

Defrosting modes

0-4

0

Main control

23

Fan speed display selection

0: 2 speed (H L)

1: 3 speed (H M L)

2: 10 speed (DC fan)

0

24

Multiple function setting

0: Reserved

1: Filter alarm clearance

2: Weekly timer clearance

0

Parameters introduction

Number 00– range 0 or 1, 0 means power to auto restart function is not available, 1 means power to

auto restart function is ON.

Number 01– this function is not available now.

Number 02 and 03– number 02 range from 5C to 30C, default value 19C is bypass open temperature X,

Number 03 range from 2C to 15C, default value 3C is the auto bypass open temperature Y, when OA

temperature is less than X or higher than X+Y, then bypass off, when OA temperature is between X and

X+Y, then bypass on.

Number 04– range from 15 to 99 minutes, default value 30 means the defrosting interval time is 30

minutes.

Number 05– range from –9C to 5C, default value –1C means in Winter when exhaust air temperature

lower than –1C, then ventilator enter the auto defrosting mode.

Number 06– range from 2 to 20 minutes, default value 10 minutes, this means defrosting duration time

is 10 minutes.

Number 07– CO2 sensor function value, this value is to allow the ventilator automatically change to high

speed when CO2 contraction is higher than setting value.

Содержание HRU-CONTR-TPAD

Страница 1: ...User s manual Touch Screen Controller...

Страница 2: ...Touch screen controller ALNOR Systemy Wentylacji Sp z o o Knowledge Base www alnor com pl 1 User s manual of Touch Screen Controller...

Страница 3: ...y lights off Without operation for 1 minute controller enter the auto lock mode by pressing ON OFF button for 6 seconds to unlock the controller Mode Button Press Mode button to display different temp...

Страница 4: ...10 then repeat when pressing Down button fan speed change from 10 to 1 then repeat SET button SET button is the combination button under the main interface press the SET button for short can check the...

Страница 5: ...meter setting interface After entering the parameter setting interface press SET button shortly to change the parameter number every pressing will increase 1 parameter number until number 24 then repe...

Страница 6: ...election 0 2 speed H L 1 3 speed H M L 2 10 speed DC fan 0 24 Multiple function setting 0 Reserved 1 Filter alarm clearance 2 Weekly timer clearance 0 Parameters introduction Number 00 range 0 or 1 0...

Страница 7: ...ogram on PCB to the HRU ERGO model refer to below table Code Models Code Models 6 1 HRU ERGO 800 5 HRU ERGO 250 2 HRU ERGO 1000 4 HRU ERGO 350 1 3 HRU ERGO 500 2 0 HRU ERGO 650 Number 22 this function...

Страница 8: ...ashes press UP and DOWN button to change hour After setting hour press MODE button for short to switch to minute setting at this time minute flashes press Up and Down button to change minute After tim...

Страница 9: ...r hour setting press MODE button to enter minute setting After minute setting press SET button to save and switch to the next day timer on setting and repeat the above steps to set all days and period...

Страница 10: ...save and switch to the next day timer off setting and repeat the above steps to set all days and periods timer off After setting all the timer off press SET button to save the data e Attention Under t...

Отзывы: