24
HM680 Hydronic Manometer
Pump Law Brake Power
This Calculations Menu option allows for determination of required pump brake power. The calculation is
based upon the following affinity law: Pump brake power varies as the cube of flow.
Figure 13: Pump Law Brake Power Screen
Inputs
The following inputs are necessary for calculating the required pump brake power. Use the
▲
and
▼
keys to select the parameter to be updated, and the
◄
and
►
keys to change the value of the
highlighted field. Units for the inputs are driven by what was last set in the Pressure and Flow
Measurement screens (with the exception of brake power).
Flow1
The actual system flow rate.
BP1
The actual pump brake power.
Flow2
The desired system flow rate.
Output
The calculated required pump brake power (
BP2
) to achieve the desired flow will automatically
update as the input parameters are changed. Using the
▲
and
▼
keys to scroll, and the
◄
and
►
keys to change the selected field, the unit of measure for pump brake power may be adjusted.
Available units for pump brake power are: bhp, W and kW.
Actual Flow
Actual Pump
Brake Power
Desired Flow
Battery Status or
Power Input Type
Required Pump
Brake Power