The ADSx Series of AC Surge Protection Devices are ANSI/UL 1449 -3rd 

Edition defined as Type 1/2 protective devices. Type 1 SPDs are suitable for 
direct installation on the supply line of the service disconnect. Type 2 SPDs 
are installed on the load side of the service disconnect and may be ordered 
with UL1283 Listed EMI/RFI filter. 

The SPDs are parallel mounted transient surge suppression devices 
intended to be installed either at an AC Main Service, Distribution Panel 
or a critical load. They may also be mounted directly within equipment 
enclosures such as SCADA Control Panel Systems.

The SPD should be part of a coordinated surge suppression system that 
includes primary protection at the main service entrance, secondary 
protection at distribution panels, and at point of use for sensitive electronic 
equipment. Proper system design should also include protecting all other 
copper data lines or control signals that leave or enter the equipment site 
building.

DANGER!

ONLY QUALIFIED PERSONNEL SHOULD INSTALL OR SERVICE 
THIS SYSTEM. ELECTRICAL SAFETY PRECAUTIONS MUST BE 
FOLLOWED WHEN INSTALLING OR SERVICING THIS EQUIPMENT. 
TO PREVENT RISK OF ELECTRICAL SHOCK, TURN OFF AND 
LOCK OUT ALL POWER SOURCES TO THE UNIT BEFORE 
MAKING ELECTRICAL CONNECTIONS OR SERVICING.

DANGER!

SEULEMENT LE PERSONNEL QULIFIE DOIT INSTALLER OU 
MAINTENIR CE SYSTEME. DES PRECAUTIONS DE SECURITE EN 
ELECTRICITE DOIVENT ETRE SUIVIS LORS DE L’INSTALLATION 
OU DE LA MAINTENANCE DE CET EQUIPMENT. POUR EVITER 
TOUL RISQUE DE CHOC ELECTRIQUE, DEBRANCHEZ ET 
VEROUILLER TOUTES LES SOURCES D’ALIMENTATION DE CET 
EQUIPMENT AVANT DE LE BRANCHER OU LE MAINTENIR.

DANGER!

HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH

Thoroughly read and comprehend all instructions before commencing 
installation.
This equipment must be installed by qualified electrical personnel in accordance 
with all applicable codes which supersede these instructions.
Improper installation or misapplication of these devices may result in death or 
serious injury.
Failure to follow these instructions could result in damage to the electrical 
system or related equipment.

Содержание DynaShield ADS 2F Series

Страница 1: ...ADSx 2F Series DynaShield Surge Protection Devices User Manual and Installation Instruction Guide Surge Protection Device for AC Power Applications ...

Страница 2: ...t site building DANGER ONLY QUALIFIED PERSONNEL SHOULD INSTALL OR SERVICE THIS SYSTEM ELECTRICAL SAFETY PRECAUTIONS MUST BE FOLLOWED WHEN INSTALLING OR SERVICING THIS EQUIPMENT TO PREVENT RISK OF ELECTRICAL SHOCK TURN OFF AND LOCK OUT ALL POWER SOURCES TO THE UNIT BEFORE MAKING ELECTRICAL CONNECTIONS OR SERVICING DANGER SEULEMENT LE PERSONNEL QULIFIE DOIT INSTALLER OU MAINTENIR CE SYSTEME DES PREC...

Страница 3: ...s equipment To prevent risk of Electrical Shock turn off and lock out all power sources to the unit before making electrical connections or servicing General Safety This document provides detailed information on how to install and operate the ADSx Series of Surge Protection Devices SPDs IMPORTANT INSTALLATION OF THIS DEVICE SHOULD ONLY BE PERFORMED BY A LICENSED ELECTRICIAN Incorrect installation ...

Страница 4: ...95 non condensing It is encouraged to avoid direct sun loading OVERCURRENT PROTECTION For ease of maintenance it is recommended that the SPD be connected to the service panel using a multi pole 20 A or 30 A circuit breaker MOUNTING The SPD uses a NEMA 4X enclosure suitable for use in indoor or outdoor installations Locate the SPD on the wall next to the service panel Locate the available disconnec...

Страница 5: ... 4 in 89 mm 3 5 in 263 mm 10 4 in Figure 2 Dimensional Drawing ADSx200 2F ADSx300 2F Models MOUNTING BRACKETS ADSx models are supplied with two mounting brakets with mounting holes Attach mouting brackets to rear of unit as required by installation location B A For ADSx050 ADSx100 Models A 60 3 mm 2 4 in B 89 mm 3 5 in For ADSx200 ADSx300 Models A 100 mm 3 9 in B 130 mm 5 1 in Figure 3 Mounting Br...

Страница 6: ...not carry the supply current They only conduct the short duration current associated with the suppression of transient surge events Installation Instructions Before starting the installation measure the Line voltage with an AC voltmeter to ensure the correct device has been selected for the current application The MCOV maximum continuous operating voltage must not exceed the maximum limits for the...

Страница 7: ...conduit If metallic conduit is used adequate electrical continuity must be maintained at all connections including electrical enclosures Three Phase Wye 4 Wire Ground 120 208 V 127 220 V 220 385 V 240 415 V 277 480 V or 347 600V PHASE C PHASE B PHASE A 120 127 220 240 277 or 347 V NEUTRAL L N Voltage GND Requires a 3 Pole Breaker 208 220 385 415 480 or 600 V Three Phase Delta 3 Wire Ground 240V 48...

Страница 8: ...crews on front of unit remove cover and turn over 2 Locate the terminal connections and connect using 18 22 AWG wires Route wires out thru pipe nipple 3 Close cover taking care not to pinch any wires or ribbon cable 4 Tighten screws Wiring for the Alarm Contacts must meet or exceed the rating of the wiring provided for the mains OPTIONAL INSTALLATION 1 It is possible for an end user to add their o...

Страница 9: ...n NOTE BEFORE ENERGIZING THE SPD ENSURE ALL CONNECTIONS ARE CORRECT STATUS INDICATORS PHASE LED INDICATOR S When the SPD is securely connected and operating properly the Blue Phase LEDs will be illuminated Replacement of the SPD is required if any Blue phase LED is not illuminated Apply power The SPD is fully operational when the BLUE LED on the front panel are illuminated If the Blue LED are exti...

Страница 10: ...s R NC NO Form C Contacts F EMI Noise Filter Type Part ADSx KKK VVVV O Figure 7 Part Numbering System DESCRIPTIONS ADSx 2F T KKK VVVV EL ADSx Model Name K kA Rating V Voltage Configuration O Options Delta Configurations do not come with a filter so the 2F is dropped from the part number kA Rating Surge Capacity 3 numeric charactors define the kA rating per phase Voltage Configuration 3 numeric 1 a...

Страница 11: ......

Страница 12: ...CORPORATE HEADQUARTERS 64 Catalyst Drive Canton North Carolina 28716 USA TEL 1 828 646 9290 EMAIL online info alltecglobal com www alltecglobal com ...

Отзывы: