Allstyle 4AC13018ASA1 Скачать руководство пользователя страница 5

Table 1.  Vapor line sizing chart.

Model

Total Length (ft.)

15 - 25

26 - 50

51 - 75

4AC13018

3/4”

3/4”

3/4”

4AC13024

3/4”

3/4”

3/4”

4AC13030

3/4”

3/4”

3/4”

4AC13036

3/4”

3/4”

7/8”

4AC13042

7/8”

7/8”

1/8

4AC13048

7/8”

7/8”

1/8

4AC13060

7/8”

1/8

3/8

• 

For length greater than 75 ft., contact factory

• 

All models use 3/8” liquid line, unless otherwise stated

Model

Number

Phase

Freq.

(Hz)

Voltage

(Volts)

Compressor

Fan Motor

Full Load

Amps 

(FLA)

Minimum

Circuit

Amperes

Max

Fuse/ HACR

Ckt. Bkr.

Rated Load

Amperes 

(RLA)

Locked Rotor 

Amperes 

(LRA)

4AC13018ASA1

1

60

208/230

10.0

48

0.8

13.3

20

4AC13024ASA1

1

60

208/230

14.3

58.3

0.8

18.7

30

4AC13030ASA1

1

60

208/230

14.3

64

0.8

18.7

30

4AC13036ASA1

1

60

208/230

18.6

79

1.5

24.8

40

4AC13042ASA1

1

60

208/230

20.0

112

1.5

26.5

45

4AC13048ASA1

1

60

208/230

24.3

117

1.5

31.9

50

4AC13060ASA1

1

60

208/230

29.4

134

1.8

38.6

60

Installer’s Information Manual

Page 5

Table 2.  Electrical Specifications

BRAZING JOINTS

1.  Remove the valve core from the Schrader port.  Wrap 

a wet rag around the valve body and copper stub 

before brazing.

2. 

Flux the copper tube and the stub with silphos rod 

containing at least 10% silver.  Braze the joint, and then 

use a second wet rag to cool joint before removing first 

rag wrapped around service valve.

3.  Replace the valve core to the Schrader port.

4.  All  joints  and  fittings  must  be  properly  leak 

tested  at  all  braze  joints  as  per  EPA  guidelines.                                          

NOTE:  Do not use air to leak test braze joints.  Dry 

nitrogen should be used.

5. 

Purge  and  evacuate  the  lines  to  29.96”  Hg  (1000 

microns) or lower when all joints and fittings are leak 

free.

6.  This is not a back-seating valve.  To open the valve cap, 

use an adjustable wrench.  To open the valve, insert an 

adjustable wrench.  To open the valve, insert a hex 

wrench (3/16” for the liquid line, 5/16” for the vapor 

line) into the stem and back out counterclockwise until 

the valve stem just touches the retaining ring.  Do not 

over tighten.  This opens the valve completely.  The 

gauge port is (open) accessible at all times.

 CAUTION:

  Extreme care should be used 

when brazing joints.  Keep torch away from condenser 

cabinet, aluminum coil and plastic top.

 

WARNING:  

If the valve stem is backed out 

past the retaining ring, system pressure could force the 

valve stem out of valve body and possibly cause personal 

injury.  In the event the retaining ring is missing, do not 

attempt to open the valve.

7.     Replace the valve cap finger-tight, then tighten an additional     

        1/12” turn or 1/2” hex flat.  A metal-to-metal seal is now        

         complete.

SECTION 5.  ELECTRICAL CONNECTION

1.  The installer shall check available power to make certain it 

matches the unit (Name Plate Rating) and that constant voltage 

can be maintained to the unit.  Unsatisfactory performance 

would otherwise result.  The local power company should be 

contacted on any problems or questions concerning power 

supply.

2. 

Install a line service disconnect switch within sight of the 

condensing unit.  The line voltage service wiring for the 

condensing unit should include a fused disconnect switch.

3.  Use correct wire size and fuse size.  To ensure that adequate 

voltage will be available at the condensing unit, the line 

voltage service wiring MUST be of adequate size.  Minimum 

recommended wire ampacities and maximum fuse sizes are 

listed on the unit name plate (See also Table 2).

4. 

Two holes are provided in the control box.

 

•   One is for the connection of the line voltage  

 

 

     conduit or cable.  The hole is sized for 1 

1/8

” conduit.

 

•   One is for low-voltage wiring. (Refer to the  

 

 

     wiring diagram attached to the electrical box  

 

 

     cover for connection)

5.  Be sure to ground the condensing unit by securing the ground 

wire to the grounding lug inside the control box.

6.  Be sure to follow National Electrical Code and all local codes.

NOTE:  Use copper conductors only.

 WARNING:

  Electrical equipment should be 

installed by a qualified, licensed electrician.  Disconnect 

all power to the unit before installing or servicing.  Failure 

to follow this warning may result in property damage, 

personal injury or death due to electrical shock.

Содержание 4AC13018ASA1

Страница 1: ...documents listed above You should become familiar with these instructions as it will be helpful in avoiding any needless service costs or operational problems Keep these instructions as long as you k...

Страница 2: ...ou to potential hazards we use the signal words WARNING and CAUTION throughout this manual WARNING alerts you to situations that could cause or result in serious injury or death CAUTION alerts you to...

Страница 3: ...n Agency EPA has issued various regulations regarding the introduction and disposal of refrigerants in this unit Failure to follow these regulations may harm the environment and can lead to the imposi...

Страница 4: ...d be give to water drainage away from the outdoor unit Drain holes in the base pan must be kept clear SECTION 4 REFRIGERANT PIPING CONNECTIONS Undersizedlinesetswillincreasetherefrigerantpressure drop...

Страница 5: ...ighten This opens the valve completely The gauge port is open accessible at all times CAUTION Extreme care should be used when brazing joints Keep torch away from condenser cabinet aluminum coil and p...

Страница 6: ...hich have Thermostatic Expansion Valve TXV as the expansion device For proper sub cooling readings a standard high side gauge is required for pressure readings 1 Measure the outdoor air temperature T1...

Страница 7: ...ing unit for unusual noise and undue vibration 5 Allow the system to operate until it is balanced or stabilized approximately 30 minutes before making further checks 6 Remove manifold gauge hoses and...

Страница 8: ...t Installer s Information Manual Page 8 SUB COOLING CHART FOR UNITS WITH THERMOSTATIC EXPANSION VALVES 18 16 14 12 10 8 6 4 60 65 70 75 80 85 90 95 100 105 110 115 Remove Refrigerant Add Refrigerant S...

Страница 9: ...ect voltage Defective overload protector Refrigerant undercharge At compressor terminals voltage must be 10 of nameplate marking when unit is operating Replace check for correct voltage Add refrigeran...

Страница 10: ...Installer s Information Manual Page 10...

Страница 11: ...Installer s Information Manual Page 11 NOTES...

Страница 12: ...Since the manufacturer has a policy of continuous product and product data improvement it reserves the right to change design and specification without notice Installer s Information Manual Rev 8 2015...

Отзывы: