Power Connectivity Planning
4-3
SG-9500 Hardware Guide
•
The cord must have insulation material suitable
for at least 75 °C
•
The cord must have local safety approvals, and preferable additional
approvals such as UL, CSA, TUV or VDE.
•
The flexible cord and attachment plug cap length must not exceed 4.5 m
(15 ft.).
•
For a cord set assembly, the cords must be protected against physical
damage and arranged in appropriate cable ducts.
•
Connector:
Wall outlet end - Cords must be terminated in an industrial grounding-
type male plug designed for use in your region.
Connector unit end - The connectors that plug into the AC receptacle
on the unit must be an approved IEC 320, C13 type female connector.
DC Cable Specifications
Allot does not provide DC power cables.
WARNING OVER CURRENT PROTECTION FOR THE SYSTEM MUST BE PROVIDED AT
THE INSTALLATION SITE FOR EACH SUPPLY CIRCUIT.
AVERTISSEMENT IL CONVIENT DE PRÉVOIR UNE PROTECTION CONTRE LES
SURINTENSITÉS DU SYSTÈME SUR LE SITE DE L'INSTALLATION POUR
CHAQUE CIRCUIT D'ALIMENTATION.
ATTENTION
All Input power and return wiring should be specified, configured, and
installed by a qualified electrician in order to prevent damage to the
equipment or safety risks.
ATTENTION
Tout le câblage d'alimentation et de retour doit être spécifié, configuré,
et installé par un électricien qualifié pour éviter d'endommager
l'équipement ou prévenir les risques liés à la sécurité.
The DC power cords must meet the following specifications:
•
Use copper conductors only.
•
The cord must have the appropriate cross-sectional dimension for the rack
rating.
•
The cord must have insulation material suitable for at least 75°C.
•
The cord must have local safety approvals, and preferable additional
approvals such as UL, CSA, TUV or VDE.
•
For a cord set assembly, the cords must be protected against physical
damage and arranged in appropriate cable ducts.