Allmand LSC100 Скачать руководство пользователя страница 7

7

WI-LSC905/3003-02

ALLMAND LSC  Light Sequence Controller

 SEQUENCING ON

Generally an engine-driven generator is required to start with a load connected. It is not uncommon for the
load to be applied to the generator all at one time as the engine is coming up to speed. It is also common for a
generator set to have a fixed RPM in order to maintain a required frequency, usually 1800 or 3600 RPM. As a
result of these requirements the engine starting system can have additional loads that can result in premature
failures of the starter motor due to overcranking. In addition the typical diesel engine would include a fuel
solenoid that controls the flow of fuel to the engine electrically. The fuel solenoid typically includes a pull coil
that retracts a mechanism to allow fuel flow when the engine starter is cranked. Excessive engine cranking
and excessive engagement of the pull coil in the fuel solenoid can result in overheating and burnout of the pull
coil.

By having no load, or sequencing the loads on, the engine starter and solenoid will not be affected.

Benefits of Sequencing the Loads ON:

1. Potentially less requirements on the engine starter.
2. Less cranking of the starter and faster starts results in less coil failures in the solenoid.
3. A smaller horsepower rated engine may be adequate due to no load during engine start.
4. A smaller horsepower rated engine may be used as the loads can be sequenced on as some types of

loads have higher starting loads than running loads such as electric motors etc.

5. A smaller generator may be used as the loads can be sequenced on. Some types of loads require a

significant inrush to start such as electric motors, etc.

6. The engine can be started and allowed to warm up before loads are applied.
7. The engine oiling system will be allowed to build up to normal oil pressures before the load is applied.

AUTOMATIC LOAD SEQUENCING OFF

Generally an engine generator set will have the potential to be shut down while under load. This could be the
result of the operator’s failure to disconnect the load prior to shut down or as a result of the automatic
shutdown due to low oil pressure, high water temperature, or running out of fuel. Loads applied to the genera-
tor during engine shutdown can result in failure of the generator regulation system as the regulator attempts to
maintain the generator output while the RPM is decreasing to zero.

By automatically sequencing the loads off before the engine is shut down, the generator regulation system will
not be affected. Sequencing the loads off can occur during manual shutdown or during any automatic shut-
down such as low oil pressure, high water temperature, or low fuel.

Benefits of sequencing the loads OFF.

1. Regulation system is not damaged as no loads are applied during shutdown.
2. Engine can be allowed to cool down with no load before shutdown. This can be especially important in

turbocharged applications to prevent cooking the oil in the turbo.

3. Generator can be allowed to cool down with no load before shutdown.

By combining the automatic load sequencing ON and OFF with an engine auto start control any machine
attended or unattended can be assured of these benefits.

Not 

for 

Reproduction

Содержание LSC100

Страница 1: ...LSC905 01 LSC100 LIGHT SEQUENCE COMMANDER Operation Testing and Troubleshooting Information ALLMAND BROS INC P O BOX 888 HOLDREGE NE 68949 PHONE 308 995 4495 1 800 562 1373 ALLMAND FAX 308 995 5887 ALLMAND PARTS FAX 308 995 4883 LSC100 Light Sequence Commander N o t f o r R e p r o d u c t i o n ...

Страница 2: ...ctions for Optional Timer Page 5 LSC100 Features and Benefits Page 6 Description of Load Sequencing Page 7 LSC100 Testing Procedure Page 8 Parts List Page 9 Wiring Schematic for Kubota LSC100 Pages 10 14 Wiring Schematic for Cat Perkins LSC100 Pages 15 19 LSC100 Logic Sequence Flow Chart Page 20 N o t f o r R e p r o d u c t i o n ...

Страница 3: ...Down Automatic Start Instructions 1 Turn power switch ON 2 Turn light circuit breakers ON 3 Turn Auto Manual switch to AUTO Start sequence will begin when photocell senses preset light value NOTE Glow plugs are automatic as required Engine will start or make 5 attempts Lights will come on when engine water temperature reaches 120 F Shut Down 1 Turn Auto Manual switch OFF 2 Turn power switch OFF 1 ...

Страница 4: ...t occurs and the red LED flashes Once the water temperature reaches 120 F the light relays begin to close sequentially with a three second delay in between NOTE Light circuit breakers must be in the ON position or the lights will not come on If the fuel level in the tank falls below 1 10 full the shut down sequence will begin The low fuel fault will be indicated by a flashing red LED It will remai...

Страница 5: ... hour and the MIN key to set the minute NOTE You may never need to use more than 1 event ON and OFF per day However the timer is capable of 8 event pairs per day Always set an OFF time for each ON time NOTE To clear the event press the TIMER key until you get to the event you want to clear and hold then press the DAY key until the setting clears Always set an OFF time for each ON time It is possib...

Страница 6: ...e engine will not require bleeding of the fuel system and the possible starter and solenoid failures as a result of overcranking 6 Sequenced light control Lights will come on automatically after the engine is started and will turn off automatically before engine is shut down This provides protection for the generator because the load will be OFF before the engine is shut down 7 Diagnostic LED Faul...

Страница 7: ...motors etc 5 A smaller generator may be used as the loads can be sequenced on Some types of loads require a significant inrush to start such as electric motors etc 6 The engine can be started and allowed to warm up before loads are applied 7 The engine oiling system will be allowed to build up to normal oil pressures before the load is applied AUTOMATIC LOAD SEQUENCING OFF Generally an engine gene...

Страница 8: ...Low Fuel Level Sequenced shutdown can be checked by starting the engine and allowing the lights to turn on After the lights are on remove the wire from the Fuel Sender and the unit will begin to sequence the lights OFF at three second intervals 2 Lights at a time if the machine has two lights on each breaker The red LED will also be flashing Within 30 seconds from the time the wire is removed the ...

Страница 9: ...itch 650744 1 Temperature sender 3 8 NPT 650745 1 Engine harness 650746 3 Red LED lens 650747 1 Green LED lens 650748 1 Yellow LED lens 650749 1 ABS Plastic box 650750 1 Single pin connector for Starter 650741 1 Two pin connector for Alternator 650742 1 Three pin connector for Fuel Solenoid 650743 1 Photocell 650755 1 Timer Optional 352471 N o t f o r R e p r o d u c t i o n ...

Страница 10: ...10 WI LSC905 3003 02 Wiring Schematic for Kubota LSC100 LIGHT SEQUENCE CONTROLLER with Photocell and Optional Timer N o t f o r R e p r o d u c t i o n ...

Страница 11: ...11 WI LSC905 3003 02 Wiring Schematic for Kubota LSC100 LIGHT SEQUENCE CONTROLLER with Photocell and Optional Timer N o t f o r R e p r o d u c t i o n ...

Страница 12: ...12 WI LSC905 3003 02 Wiring Schematic for Kubota LSC100 LIGHT SEQUENCE CONTROLLER with Photocell and Optional Timer N o t f o r R e p r o d u c t i o n ...

Страница 13: ...13 WI LSC905 3003 02 Wiring Schematic for Kubota LSC100 LIGHT SEQUENCE CONTROLLER with Photocell and Optional Timer N o t f o r R e p r o d u c t i o n ...

Страница 14: ...14 WI LSC905 3003 02 Wiring Schematic for Kubota LSC100 LIGHT SEQUENCE CONTROLLER with Photocell and Optional Timer N o t f o r R e p r o d u c t i o n ...

Страница 15: ...15 WI LSC905 3003 02 Wiring Schematic for Cat Perkins LSC100 LIGHT SEQUENCE CONTROLLER with Photocell and Optional Timer N o t f o r R e p r o d u c t i o n ...

Страница 16: ...16 WI LSC905 3003 02 Wiring Schematic for Cat Perkins LSC100 LIGHT SEQUENCE CONTROLLER with Photocell and Optional Timer N o t f o r R e p r o d u c t i o n ...

Страница 17: ...17 WI LSC905 3003 02 Wiring Schematic for Cat Perkins LSC100 LIGHT SEQUENCE CONTROLLER with Photocell and Optional Timer N o t f o r R e p r o d u c t i o n ...

Страница 18: ...18 WI LSC905 3003 02 Wiring Schematic for Cat Perkins LSC100 LIGHT SEQUENCE CONTROLLER with Photocell and Optional Timer N o t f o r R e p r o d u c t i o n ...

Страница 19: ...19 WI LSC905 3003 02 LSC100 LIGHT SEQUENCE CONTROLLER Logic Sequence Flow Chart N o t f o r R e p r o d u c t i o n ...

Страница 20: ...20 WI LSC905 3003 02 N o t f o r R e p r o d u c t i o n ...

Отзывы: