1 General Information
1.1 Installation Environment
1. The Allied Electronics NeXGen Controller (NeXGen) operates on 115 VAC @60Hz,
36 Watts. The NeXGen controller is supplied with approximately 8 feet of 115 VAC
power cord, and should be connected to an approved isolated ground receptacle on
its own dedicated circuit. The NeXGen must be installed in a temperature controlled
environment (between 32
0
F and 100
0
F).
2. The controller must be installed in accordance with the National Electrical Code
(NFPA 70), the Automotive and Marine Service Station Code (NFPA 30A), and all
state and local electrical codes.
3. The controller must be installed indoors, above the Class 1, Division 2 Hazardous
location.
4. The controller is designed for use with peripheral devices which are UL Listed.
1.2 Wiring
1.2.1
Field Wiring
All field wiring (that is, all wiring connected directly to dispensing devices) should be
oil and gas resistant, as required by Paragraph 501-13 of the NEC, and should be
sealed in accordance with Article 500 of the NEC.
1.2.2
Internal Wiring
1.2.2.1 Introduction
a. The purpose of this section is to provide a list of installation practices that we feel are
crucial to ensure error-free communications.
b. All cabling must comply with Local, State, and Federal building codes.
c. Data connections between the Forecourt Controller (SSC or NeXGen) are to be made with
CAT-5 Cable compliant with TIA/EIA-568-B or better.
d. Proper cable installation techniques go a long way to preventing data loss.
1.2.2.2 Planning
a. Pull cables in continuous runs.
b. Do not splice any communications cables.
c. Separate all cables from fluorescent lighting ballasts and neon sign transformers by at least 4
feet.
d. Separate all cables from electrical supply conductors by at least 2 feet.
e. Provide extra wire for service loops at the termination points but do not leave more than is
required.