508297-01
Page 31 of 57
Issue 2219
6. On field supplied terminations, a minimum distance
between the end of the exhaust pipe and the end of
the intake pipe without a termination elbow is 8” and a
minimum distance of 6” with a termination elbow. See
7. If intake and exhaust piping must be run up a side
wall to position above snow accumulation or other
obstructions, piping must be supported every 24” (610
mm) as shown in Figure 39. When exhaust and intake
piping must be run up an outside wall, the exhaust
piping must be terminated with pipe sized per Table 8.
The intake piping may be equipped with a 90° elbow
turndown. Using turndown will add 5 feet (1.5 m) to the
equivalent length of the pipe.
8. A multiple furnace installation may use a group of up to
four terminations assembled together horizontally, as
Figure 40.
Figure 41.
Figure 42. Direct Vent Concentric Rooftop
Termination
71M80, 69M29 or 60L46 (US)
44W92 or 44W93 (Canada)
Minimum
Above Average
Snow
Accumulation
SHEET METAL STRAP
(Clamp and sheet metal strap
must be field installed to support
the weight of the termination kit.)
FLASHING
(Not Furnished)
CLAMP
FIELD-PROVIDED
REDUCER MAY BE REQUIRED
TO ADAPT DIFFERENT VENT
PIPE SIZE TO TERMINATION
1 1/2” (38mm) accelerator
provided on 71M80 & 44W92
kits for -045 and -070 models
12” (305mm)
INTAKE
AIR
EXHAUST
VENT
Figure 43. Direct Vent Concentric Wall Termination
71M80, 69M29 OR 60L46 (US)
44W92 or 44W93 (Canada)
12” (305mm) Min.
above grade or
average snow
accumulation.
INTAKE
AIR
INTAKE
AIR
INTAKE
AIR
OUTSIDE
WALL
GRADE
CLAMP
(Not Furnished)
FIELD-PROVIDED
REDUCER MAY BE REQUIRED
TO ADAPT DIFFERENT VENT
PIPE SIZE TO TERMINATION
EXHAUST
VENT
1-1/2” (38mm) accelerator
provided on 71M80 & 44W92
kits for -045 and -070 models
EXHAUST
VENT
NOTE:
Do not discharge exhaust gases directly into any chimney
or vent stack. If vertical discharge through an existing unused
chimney or stack is required, insert piping inside chimney until
the pipe open end is above top of chimney and terminates as
illustrated. In any exterior portion of chimney, the exhaust vent
must be insulated.
Figure 44. Direct Vent Application Using Existing
Chimney
STRAIGHT-CUT OR
ANGLE-CUT IN DIRECTION
OF ROOF SLOPE *
EXHAUST VENT
1/2” (13mm)
WEATHERPROOF
INSULATION
SHOULDER OF FITTINGS
PROVIDE SUPPORT
OF PIPE ON TOP PLATE
ALTERNATE
INTAKE PIPE
INTAKE PIPE
INSULATION (optional)
EXTERIOR
PORTION OF
CHIMNEY
INSULATE
TO FORM
SEAL
SHEET
METAL TOP
PLATE
8” - 12”
(203mm - 305mm)
* SIZE TERMINATION
PIPE PER EXHAUST
PIPE TERMINATION
SIZE REDUCTION
TABLE
3” - 8”
(76mm -
203mm)
3” - 8”
(76mm -
203mm)
Minimum 12” (305mm)
above chimney top
plate or average snow
accumulation