Table 4. 

Piping and Fittings Specifications

Schedule 40 PVC (Pipe) 

D1785

Schedule 40 PVC (Cellular Core Pipe) 

F891

Schedule 40 PVC (Fittings) 

D2466

Schedule 40 CPVC (Pipe) 

F441

Schedule 40 CPVC (Fittings) 

F438

SDR-21 PVC or SDR-26 PVC (Pipe) 

D2241

SDR-21 CPVC or SDR-26 CPVC (Pipe)

 F442

Schedule 40 ABS Cellular Core DWV 

(Pipe) 

F628

Schedule 40 ABS (Pipe) 

D1527

Schedule 40 ABS (Fittings) 

D2468

ABS-DWV (Drain Waste & Vent) 

(Pipe & Fittings)

D2661

PVC-DWV (Drain Waste & Vent) 

Pipe & Fittings)

D2665

PRIMER & SOLVENT CEMENT

ASTM 

SPECIFICATION

PVC & CPVC Primer 

F656

PVC Solvent Cement 

D2564

CPVC Solvent Cement 

F493

ABS Solvent Cement 

D2235

PVC/CPVC/ABS All Purpose Cement For 

Fittings & Pipe of the same material

D2564, D2235, 

F493

ABS to PVC or CPVC Transition Solvent 

Cement

D3138

CANADA PIPE & FITTING & SOLVENT 

CEMENT

MARKING

PVC & CPVC Pipe and Fittings

ULCS636

PVC & CPVC Solvent Cement 

ABS to PVC or CPVC Transition Cement

POLYPROPYLENE VENTING SYSTEM

ULC-S636

PolyPro® by Duravent 

InnoFlue® by Centrotherm 

ULC-S636

ECCO Polypropylene Vent

TM

ULC-S636

Pipe & Fittings Specifications

All pipe, fittings, primer and solvent cement must conform 

with American National Standard Institute and the American 

Society for Testing and Materials (ANSI/ASTM) standards. 

The  solvent  shall  be  free  flowing  and  contain  no  lumps, 

undissolved particles or any foreign matter that adversely 

affects  the  joint  strength  or  chemical  resistance  of  the 

cement. The cement shall show no gelation, stratification, 

or separation that cannot be removed by stirring. Refer to 

Table 4 for approved piping and fitting materials.

Solvent cements for plastic pipe are flammable liquids 

and should be kept away from all sources of ignition. 

Do not use excessive amounts of solvent cement when 

making joints. Good ventilation should be maintained to 

reduce fire hazard and to minimize breathing of solvent 

vapors. Avoid contact of cement with skin and eyes.

 CAUTION

The exhaust and intake connections are made of PVC. 

Use PVC primer and solvent cement when using PVC 

vent pipe. When using ABS vent pipe, use transitional 

solvent cement to make connections to the PVC fitting 

in the unit.

 IMPORTANT

Use PVC primer and solvent cement or ABS solvent 

cement  meeting  ASTM  specifications,  refer  to  Table  4. 

As an alternate, use all purpose cement, to bond ABS, 

PVC, or CPVC pipe when using fittings and pipe made of 

the same materials. Use transition solvent cement when 

bonding ABS to either PVC or CPVC.

Low temperature solvent cement is recommended during 

cooler weather. Metal or plastic strapping may be used as 

vent pipe hangers. Uniformly apply a liberal coat of PVC 

primer for PVC or use a clean dry cloth for ABS to clean 

inside  socket  surface  of  fitting  and  male  end  of  pipe  to 

depth of fitting socket.

Canadian Applications Only

Pipe,  fittings,  primer  and  solvent  cement  used  to  vent 

(exhaust) this appliance must be certified to ULC S636 and 

supplied by a single manufacturer as part of an approved 

vent (exhaust) system. When bonding the vent system to 

the furnace, use ULC S636 approved One-Step Transition 

Cement to bond the pipe to the flue collar. In addition, the 

first three feet of vent pipe from the furnace flue collar must 

be accessible for inspection.

Table 5 lists the available exhaust termination kits. All vent 

terminations are PVC.

Joint Cementing Procedure

All  cementing  of  joints  should  be  done  according  to  the 

specifications outlined in ASTM D 2855.

NOTE: 

A  sheet  metal  screw  may  be  used  to  secure  the 

intake pipe to the connector, if desired. Use a drill or self 

tapping screw to make a pilot hole.

Содержание 92G1DFE

Страница 1: ...mage personal injury or loss of life Installation and service must be performed by a licensed professional installer or equivalent service agency or the gas supplier WARNING As with any mechanical equipment personal injury can result from contact with sharp sheet metal edges Be careful when you handle this equipment CAUTION Table of Contents Unit Dimensions 2 Parts Arrangement 3 Gas Furnace 4 Ship...

Страница 2: ...507868 01 Page 2 of 48 Issue 1912 Unit Dimensions Model A93DF1E 92G1DFE A B C in mm in mm in mm 045 12 070 12 17 1 2 446 16 3 8 416 16 406 090 16 21 533 19 7 8 504 19 1 2 495 ...

Страница 3: ... Heating Compartment Access Panel Blower Access Panel Cold End Header Box Control Box includes integrated control transformer and door switch Blower Assembly Bag Assemblies Cabinet Blower Deck Heat Exchanger Combustion Air Inducer E X H A U S T IN T A K E Parts Arrangement ...

Страница 4: ...eaded street elbow Check equipment for shipping damage If you find any damage immediately contact the last carrier Please refer to specification sheets for available accessories Safety Information DANGER OF EXPLOSION There are circumstances in which odorant used with LP Propane gas can lose its scent In case of a leak LP Propane gas will settle close to the floor and may be difficult to smell An L...

Страница 5: ...t must be equipped to prevent operation of either the heating or the cooling unit unless it is in the full HEAT or COOL setting When installed this furnace must be electrically grounded according to local codes In addition in the United States installation must conform with the current National Electric Code ANSI NFPA No 70 The National Electric Code ANSI NFPA No 70 is available from the following...

Страница 6: ...rafts might blow directly into it This could cause improper combustion and unsafe operation When the furnace is installed in a non direct vent applications do not block the furnace combustion air opening with clothing boxes doors etc Air is needed for proper combustion and safe unit operation When the furnace is installed in an attic or other insulated space keep insulation away from the furnace W...

Страница 7: ...combustion and ventilation depend largely on whether the furnace is installed in an unconfined or a confined space Unconfined Space An unconfined space is an area such as a basement or large equipment room with a volume greater than 50 cubic feet 1 42 m per 1 000 Btu 29 kW per hour of the combined input rating of all appliances installed in that space This space also includes adjacent rooms which ...

Страница 8: ...nsion of rectangular air ducts shall be no less than 3 inches 75 mm In calculating free area the blocking effect of louvers grilles or screens must be considered If the design and free area of protective covering is not known for calculating the size opening required it may be assumed that wood louvers will have 20to 25 percent free area and metal louvers and grilles will have 60 to 75 percent fre...

Страница 9: ...d Space all Air from Outside Shipping Bolt Removal Units with 1 2 hp and 3 4 hp blower motors are equipped with three flexible legs and one rigid leg The rigid leg is equipped with a shipping bolt and a flat white plastic washer rather than the rubber mounting grommet used with a flexible mounting leg See Figure 11 The bolt and washer must be removed before the furnace is placed into operation Aft...

Страница 10: ...Do not drag the unit across the floor in the downflow position Floor and furnace flange damage will result Refer to Figure 14 for clearances in downflow applications Improper installation of the furnace can result in personal injury or death Combustion and flue products must never be allowed to enter the return air system or air in the living space Use sheet metal screws and joint tape to seal ret...

Страница 11: ... 2 After opening is cut set the combustible flooring base into opening 3 Check fiberglass strips on the combustible flooring base to make sure they are properly glued and positioned 4 Lower supply air plenum into the combustible flooring base until plenum flanges seal against fiberglass strips NOTE Be careful not to damage fiberglass strips Check for a tight seal 5 Set the furnace over the plenum ...

Страница 12: ...external static pressure which exceeds 0 5 inches w c Operation at these conditions may result in improper limit operation Supply Air Plenum If the furnace is installed without a cooling coil a removable access panel should be installed in the supply air duct The access panel should be large enough to permit inspection by reflected light of the heat exchanger for leaks after the furnace is install...

Страница 13: ...rces of ignition Do not use excessive amounts of solvent cement when making joints Good ventilation should be maintained to reduce fire hazard and to minimize breathing of solvent vapors Avoid contact of cement with skin and eyes CAUTION The exhaust and intake connections are made of PVC Use PVC primer and solvent cement when using PVC vent pipe When using ABS vent pipe use transitional solvent ce...

Страница 14: ...s Termination kits 44W92 and 44W93 are approved for use in Canadian installations to meet CSAB149 The 44W92 Concentric kit is provided with a 1 1 2 accelerator which must be installed on the exhaust outlet when this kit is used with this furnace NOTE When using 1 1 2 piping and terminating with a flush mount kit or concentric kit the pipe must be transitioned to 2 pipe before attaching to the flus...

Страница 15: ... condition 3 Close all building doors and windows and all doors between the space in which the appliances remaining connected to the common venting system are located and other spaces of the building Turn ON clothes dryers and any appliances not connected to the common venting system Turn ON any exhaust fans such as range hoods and bathroom exhausts so they will operate at maximum speed Do not ope...

Страница 16: ...outdoors and flue gases are discharged outdoors Intake and exhaust pipe sizing Size pipe according to Table 6 and Table 7A through Table 7B Table 6 lists the minimum vent pipe lengths permitted Table 7A and Table 7B list the maximum pipe lengths permitted Regardless of the diameter of pipe used the standard roof and wall terminations described in section Exhaust Piping Terminations should be used ...

Страница 17: ...16 65 50 13 97 97 78 8 26 11 60 45 n a 92 92 73 9 21 n a 55 40 87 87 68 10 16 50 35 82 82 63 Concentric Termination Elevation 0 10 000 ft Number of 90 Elbows Used 1 1 2 Pipe 2 Pipe 2 1 2 Pipe 3 Pipe Model Model Model Model 045 070 090 045 070 090 045 070 090 045 070 090 1 15 10 n a 53 38 22 90 70 39 111 111 104 2 10 n a 48 33 17 85 65 34 106 106 99 3 n a 43 28 12 80 60 29 101 101 94 4 38 23 n a 75...

Страница 18: ...9 11 45 60 67 67 48 10 6 40 55 62 62 43 NOTE Additional vent pipe and elbows used to terminate the vent pipe outside the structure must be included in the total vent length calculation Figure 23 Typical Exhaust Pipe Connections TYPICAL EXHAUST PIPE CONNECTIONS Pipe size determined in table 7 2 TOP VIEW EXHAUST INTAKE 2 2 2 2 or TRANSITION 3 2 2 1 1 2 or TRANSITION EXHAUST EXHAUST NOTE 1 1 2 Vent P...

Страница 19: ...o the furnace from the surrounding space the indoor air quality must be considered Guidelines listed in Combustion Dilution and Ventilation Air section must be followed Follow the next two steps when installing the unit in Direct Vent applications where combustion air is taken from outdoors and flue gases are discharged outdoors The provided air intake screen must not be used in direct vent applic...

Страница 20: ...ir to Outside Roof Terminated Exhaust Pipe Furnace Ventilation Louvers Crawl Space Intake Debris Screen Provided Inlet Air Minimum 12 in 305mm above Crawl Space Floor Coupling or 3 in to 2 in Transition Field Provided See Maximum Vent Lengths table NOTE The inlet and outlet air openings shall each have a free area of at least one square inch per 4 000 Btu 645mm2 per 1 17kW per hour of the total in...

Страница 21: ... in Unconditioned Space for Winter Design Temperatures Single Stage High Efficiency Furnace Winter Design Temperatures1 ºF ºC Vent Pipe Diameter Unit Input Size 045 070 090 32 to 21 0 to 6 PVC 2 PP PVC 2 PP PVC 2 PP 1 1 2 in 25 N A 20 N A N A N A 2 in 18 16 31 28 50 48 2 1 2 in 13 N A 24 N A 42 N A 3 in 9 9 18 18 35 35 20 to 1 7 to 17 1 1 2 in 15 N A 20 N A N A N A 2 in 9 8 18 16 32 29 2 1 2 in 5 ...

Страница 22: ...earance under veranda porch deck or balcony 12 Equal to or greater than soffit depth 3 feet 9m 12 3 feet 9m within a height 15 feet 4 5m above the meter regulator assembly 3 feet 9m 6 inches 152mm for appliances 10 000 Btuh 3kw 12 inches 305mm for appliances 10 000 Btuh 3kw and 100 000 Btuh 30kw 36 inches 9m for appliances 100 000 Btuh 30kw 3 feet 9m above if within 10 feet 3m horizontally 6 feet ...

Страница 23: ...es 152mm for appliances 10 000 pliances 10 000 Btuh 3kw and 50 000 pliances 50 000 Btuh 15kw 6 inches 152mm for appliances 10 000 Btuh 3kw 12 inches 305mm for appliances 10 000 Btuh 3kw and 100 000 Btuh 30kw 36 inches 9m for appliances 100 000 Btuh 30kw 3 feet 9m above if within 10 feet 3m horizontally 6 feet 1 8m 7 feet 2 1m 12 inches 305mm 1 In accordance with the current ANSI Z223 1 NFPA 54 Nat...

Страница 24: ...ation is 3 76 mm on roof terminations and 6 152 mm on side wall terminations 3 On roof terminations the intake piping should terminate straight down using two 90 elbows see Figure 31 4 Exhaust piping must terminate straight out or up as shown A reducer may be required on the exhaust piping at the point where it exits the structure to improve the velocity of exhaust away from the intake piping See ...

Страница 25: ...ENT PIPE SIZE TO TERMINATION 1 1 2 38mm accelerator provided on 71M80 44W92 12 305mm INTAKE AIR EXHAUST VENT Figure 36 Direct Vent Concentric Wall Termination 12 305mm Min above grade or average snow accumulation INTAKE AIR INTAKE AIR INTAKE AIR OUTSIDE WALL GRADE CLAMP Not Furnished FIELD PROVIDED REDUCER MAY BE REQUIRED TO ADAPT LARGER VENT PIPE SIZE TO TERMINATION EXHAUST VENT 1 1 2 38mm accele...

Страница 26: ...n tee should be connected to the 2 or 3 PVC flue pipe as shown in the illustration Do not use an accelerator in applications that include an exhaust termination tee The accelerator is not required 2 As required Flue gas may be acidic and may adversely affect some building materials If a side wall vent termination is used and flue gases will impinge on the building materials a corrosion resistant s...

Страница 27: ...n Figure 42 When exhaust piping must be run up an outside wall any reduction in exhaust pipe size must be done after the final elbow Figure 40 Non Direct Vent Roof Termination Kit UNCONDITIONED ATTIC SPACE 3 76MM OR 2 51MM PVC PROVIDE SUPPORT FOR EXHAUST LINES 12 305MM ABOVE AVE SNOW ACCUMULATION SIZE PER EXHAUST PIPE TERMINATION SIZE REDUCTION TABLE Figure 41 Non Direct Vent Field Supplied Wall T...

Страница 28: ...Termination Drain Trap assembled Figure 44 Kit 51W18 USA 15Z70 Canada Parts Identification and Assembly Exhaust from Furnace To Termination Exhaust from Furnace To Termination Kit 51W18 is shown Figure 45 Crawl Space Vent Pipe Drain Trap Assembled Incorrectly Figure 46 Upflow or Downflow Furnace with Exhaust through Crawl Space KIT 51W18 USA Basement Floor To Termination 1 2 PVC to Code Approved D...

Страница 29: ...condensate drain Tubing must be 1 1 4 ODx1 ID and should be attached to the drain on the trap using a hose clamp Figure 47 Condensate Trap and Plug Locations 5 Figure 49 shows the furnace and evaporator coil using a separate drain If necessary the condensate line from the furnace and evaporator coil can drain together See Figure 50 The field provided vent must be a minimum 1 to a maximum 2 length ...

Страница 30: ...507868 01 Page 30 of 48 Issue 1912 Figure 49 Evaporator Coil Using a Separate Drain Figure 50 Evaporator Coil Using a Common Drain Figure 51 Condensate Trap with Optional Overflow Switch ...

Страница 31: ...507868 01 Page 31 of 48 Issue 1912 Figure 52 Trap Drain Assembly Using 1 2 PVC or 3 4 PVC ...

Страница 32: ...rip leg in vertical pipe runs to serve as a trap for sediment or condensate 5 A 1 8 N P T plugged tap or pressure post is located on the gas valve to facilitate test gauge connection See Figure 53 6 In some localities codes may require installation of a manual main shut off valve and union furnished by installer external to the unit Union must be of the ground joint type Compounds used on threaded...

Страница 33: ...54 118 3 34 110 3 11 103 2 92 1 25 4 1 049 26 645 680 19 25 465 13 17 375 10 62 320 9 06 285 8 07 260 7 36 240 6 80 220 6 23 205 5 80 195 5 52 1 1 4 31 75 1 380 35 052 1400 39 64 950 26 90 770 21 80 660 18 69 580 16 42 530 15 01 490 13 87 460 13 03 430 12 18 400 11 33 1 1 2 38 1 1 610 40 894 2100 59 46 460 41 34 1180 33 41 990 28 03 900 25 48 810 22 94 750 21 24 690 19 54 650 18 41 620 17 56 2 50 ...

Страница 34: ... long enough to facilitate future removal of blower for service Complete the wiring connections to the equipment Use the provided unit wiring diagram and the field wiring diagram shown in Figure 58 Use 18 gauge wire or larger that is suitable for Class II rating for thermostat connections Electrically ground the unit according to local codes or in the absence of local codes according to the curren...

Страница 35: ...or blower will run continuously on the heating speed when there is no cooling or heating demand 2 When the furnace is running in the heating mode the indoor blower will run on the heating speed 3 When there is a cooling demand the indoor blower will run on the cooling speed Generator Use Voltage Requirements The following requirements must be kept in mind when specifying a generator for use with t...

Страница 36: ...507868 01 Page 36 of 48 Issue 1912 Figure 59 Typical Wiring Diagram ...

Страница 37: ... next to the floor because some gas is heavier than air and will settle on the floor The gas valve on the unit is equipped with a gas control switch lever Use only your hand to move switch Never use tools If the switch will not move by hand do not try to repair it Force or attempted repair may result in a fire or explosion Placing the Furnace into Operation This furnace is equipped with an automat...

Страница 38: ...llow the gas supplier s instructions If you do not smell gas go to next step 8 Move gas valve switch to ON See Figure 61 9 Replace the heating compartment access panel 10 Turn on all electrical power to the unit 11 Set the thermostat to desired setting NOTE When unit is initially started steps 1 through 11 may need to be repeated to purge air from gas line 12 If the appliance will not operate foll...

Страница 39: ...rt unit and allow 5 minutes for unit to reach steady state 3 While waiting for the unit to stabilize observe the flame Flame should be stable and should not lift from burner Natural gas should burn blue 4 After allowing unit to stabilize for 5 minutes record manifold pressure and compare to value given in Table 13 NOTE Shut unit off and remove manometer as soon as an accurate reading has been obta...

Страница 40: ... Kit All 11K50 73W80 51W01 11K45 Conversion requires installation of a gas valve regulator spring which is provided with the gas conversion Kit LP Kits include low line pressure switch A93DF1E 92G1DFE Pressure Switch at Varying Altitudes Capacity 0 4500 ft 0 1371m 4501 7500 ft 1371 2286m 7501 10000 ft 2286 3048m 045 No Change 11U65 11U66 070 090 Pressure switch is factory set No adjustment necessa...

Страница 41: ... 2 Visually inspect the venting system for proper size and horizontal pitch Determine there is no blockage or restriction leakage corrosion or other deficiencies which could cause an unsafe condition 3 To the extent that it is practical close all building doors and windows and all doors between the space in which the appliances connected to the venting system are located and other spaces of the bu...

Страница 42: ...mostat Heat Anticipation Set the heat anticipator setting if adjustable according to the amp draw listed on the wiring diagram that is attached to the unit Electrical 1 Check all wiring for loose connections 2 Check for the correct voltage at the furnace with furnace operating Correct voltage is 120 VAC 10 3 Check amp draw on the blower motor with the blower compartment access panel in place Motor...

Страница 43: ...0 10 1380 351 1265 276 1140 202 860 109 700 73 0 20 1345 360 1240 285 1090 208 810 119 645 79 0 30 1325 371 1215 291 1060 218 770 124 590 84 0 40 1295 380 1175 302 1025 228 710 132 530 91 0 50 1260 392 1135 318 985 236 670 138 490 94 0 60 1235 402 1105 320 955 247 620 146 440 102 0 70 1185 411 1080 333 910 254 585 152 395 106 0 80 N A N A 1040 342 865 261 540 157 340 113 A93DF1E090C16A 92G1DF090CE...

Страница 44: ...e____________Actual____________ Winterizing and Condensate Trap Care 1 Turn off power to the furnace 2 Have a shallow pan ready to empty condensate water 3 Remove the clean out cap from the condensate trap and empty water Inspect the trap then reinstall the clean out cap Cleaning Heat Exchanger If cleaning the heat exchanger becomes necessary follow the below procedures and refer to Figure 1 when ...

Страница 45: ...p in center of burner ports 34 Reinstall gas valve manifold assembly Reconnect gas supply line to gas valve 35 Reconnect 2 wires to gas valve 36 Replace the blower compartment access panel 37 Refer to instruction on verifying gas and electrical connections when re establishing supplies 38 Follow lighting instructions to light and operate furnace for 5 minutes to ensure that heat exchanger is clean...

Страница 46: ...ode limit switch open longer than 3 minutes 8 Flashes Rollout switch open 9 Flashes Pressure switch failed to close or opened during heat demand 10 Flashes Watchguard Pressure switch opened 5 times during one heat demand 11 Flashes Pressure switch stuck closed prior to activation of combustion air inducer 12 Flashes Flame sensed without gas valve energized 13 Flashes Low line voltage 1 A heartbeat...

Страница 47: ...s Problems detected during the inspection may make it necessary to temporarily shut down the furnace until the items can be repaired or replaced Instruct the homeowners to pay attention to their furnace Situations can arise between annual furnace inspections that may result in unsafe operation For instance items innocently stored next to the furnace may obstruct the combustion air supply This coul...

Страница 48: ...m height of eight 8 feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OBSTRUCTIONS 4 INSPECTION The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not app...

Отзывы: