![Allied 80G2UH070AV12 Скачать руководство пользователя страница 36](http://html.mh-extra.com/html/allied/80g2uh070av12/80g2uh070av12_installation-instructions-manual_2901735036.webp)
507335-02
Page 36 of 39
Issue 2001
Control Diagnostics
Troubleshooting
Make the following visual checks before troubleshooting:
1. Check to see that the power to the furnace and the
integrated ignition/blower control board is ON.
2. The manual shutoff valves in the gas line to the furnace
must be open.
3. Make sure all wiring connections are secure.
4. Review the Sequence of Operation.
Start the system by setting thermostat above room
temperature. Observe system response. Then use the
information provided in this section to check the system
operation.
The furnace has a built-in, self-diagnostic capability. If a
system problem occurs, a fault code is shown by a red LED
on the control board. The control continuously monitors its
own operation and the operation of the system. If a failure
occurs, the LED will indicate the failure code. The flash
codes are presented in Table 17.
Fault Code History Button
The control stores the last five fault codes in memory. A
pushbutton switch is located on the control (see Figure 43).
When the pushbutton switch is pressed and released, the
control flashes the stored fault codes. The most recent fault
code is flashed first; the oldest fault code is flashed last. To
clear the fault code history, press and hold the pushbutton
switch in for more than 5 seconds before releasing.
High Heat State LED
On
80G2UH-V models, a green LED is provided on the
control board to indicate high heat state (see Table 18).
CFM LED
On
80G2UH-V models equipped with a variable speed
motor, an amber LED is provided on the control board to
display CFM. To determine what CFM the motor is delivering
at any time, count the number of times the amber LED
flashes. Each flash signifies 100 CFM; count the flashes
and multiply by 100 to determine the actual CFM delivered
(for example: 10 flashes x 100 = 1000 CFM).
Table 17. Failure Codes - Red LED
LED Status
Fault Description
LED Off
No power to control or control hardware
fault detected
LED On
Normal operation
1 Flash
Flame present with gas valve off
2 Flashes
Pressure switch closed with inducer off
3 Flashes
Low-fire pressure, rollout, or aux limit switch
open
4 Flashes
High limit switch open
5 Flashes
Not used
6 Flashes
Pressure switch cycle lockout
7 Flashes
Lockout due to no ignition
8 Flashes
Lockout due to too many flame dropouts
9 Flashes
Incorrect polarity and phasing
Table 18. High Heat State - Green LED
LED Status
Fault Description
LED Off
No demand for high heat
LED On
High heat demand, operating normally
LED Flashing
High heat demand, high pressure switch
not closed