Allied 4AC13 Скачать руководство пользователя страница 5

507043-03

Page 5 of 9

Issue  1337

ELECTRICAL SHOCK HAZARD!

  WARNING

Electrical Connections

Turn OFF electric power before connecting unit,  

performing any maintenance or removing panels or 

doors. More than one disconnect may be required to 

turn off all power.

FAILURE TO DO SO COULD RESULT IN BODILY 

INJURY OR DEATH.

  Be sure to check all local codes to determine that the 

unit is installed in accordance with local requirements. 

Consult the National Electric Code for wire size require-

ments. Use 60° C or higher copper wires only. Always 

provide ground connections to the outdoor unit. Power 

supply must agree with the rating on the unit nameplate.

  Provide line voltage power supply to unit from a  

properly sized disconnect switch. Route power and 

ground wires from disconnect switch to unit. Line voltage 

connections are made at the line side of the contactor 

in the control box of the outdoor unit. Follow the wiring 

diagram attached to inside of the access panel.

  Proper circuit protection recommendations are  

indicated on Unit Rating Plate. Time delay fuses are 

required to prevent blowing due to starting current (the 

current in rush when equipment starts is reffered to as the 

Locked Rotor Amps or LRA) .

  Remove access panel to gain access to unit wiring. 

Extend wires from disconnect through power wiring hole 

provided and into unit control box. Flexible conduit is 

required for the swing out control box feature.

  WARNING

The unit cabinet must have an uninterrupted or  

unbroken ground. The ground must be installed in  

accordance with all electrical codes. Failure to follow 

this warning can result in an injury, fire, or death.

  Connect ground wire to ground connection in control 

box for safety. Connect power wiring to contactor.

  High voltage power connections to 3-phase models is 

made to “Pig Tail” leads with field supplied splice 

 

connectors.

Contol Wiring

  The control voltage is 24 VAC. NEC Class I insulated  

18 AWG is required for control wiring. For lengths longer 

than 150 feet, contact your local distributor for technical 

service.

  Ensure the room thermostat is properly installed per 

instructions shipped with room thermostat. Generally the 

thermostat should not be exposed to sunlight, drafts or 

vibration and should not be mounted on exterior walls.

  WARNING

Low voltage wiring must be separated from high voltage 

wiring.

  Low voltage connections should be in accordance to 

the wiring diagram.

Start-Up Procedure

  1. Close electrical disconnects to energize system.

  2.  Set room thermostat at desired temperature. Be sure 

set point is below indoor ambient temperature.

  3.  Set the system switch of the thermostat on COOL 

and fan switch for continuous operation (ON) or 

AUTO, as desired.

  4.  Adjust refrigerant charge per “Adjusting Charge”  

section.

Adjusting Charge

  Factory charge is shown on the rating label located on 

the access panel.

  All units are factory charged for 15 feet of con-

necting line set.

 Charge should be adjusted for line set 

lengths other than 15 feet. For line sets shorter than 15 

feet in length, remove charge. For line sets longer than 

15 feet, add charge. Oil charge is suffficent for all line 

lengths.

  Before final adjustment is made to the refrigerant 

charge, check for proper indoor airflow. Recommended 

airflow is 

350-450 CFM per ton

 (12,000 Btuh) through a 

wet coil

. Refer to indoor unit instructions for methods of 

determining air flow and blower performance.

Typical Low Voltage Connection

Refrigeration Charge Adjustment

Liquid Line Diameter

Oz. Per Linear Foot

3/8”

.6

Содержание 4AC13

Страница 1: ...SI C1 1993 or current edition and Canadian Electrical Code Part 1 CSA WARNING These instructions are intended as a general guide and do not supersede national state or local codes in any way These instructions must be left with the property owner NOTE Safety Precautions 2 Unit Location Installation 2 Rooftop Installation Recommendations 3 Indoor Coil Piston Selection 3 Refrigeration Line Sets 3 In...

Страница 2: ... In some cases noise in the living area has been traced to gas pulsations from improper installation of equipment 1 Locate unit away from windows patios decks etc where unit operation sounds may disturb customer 2 Ensure that vapor and liquid tube diameters are appropriate to capacity of unit 3 Run refigerant tubes as directly as possible by avoiding unecessary turns and bends 4 Leave some slack b...

Страница 3: ... On brick concrete blocks or unstable surfaces Near clothes dryer exhaust vents Near sleeping area or near windows Under eaves where water snow or ice can fall directly on the unit With clearance less than 2 ft from a second uni With clearance less than 4 ft on top of unit Indoor Coil Piston Selection The outdoor section must be matched to a factory approved indoor section It is mandatory that the...

Страница 4: ... for leaks after brazing and before evacuation The recommended procedure is to apply a trace amount of vapor refrigerant approximately two ounces or 3 psig into the line set and indoor coil then pressurize with 150 psig of dry nitrogen Use a refrigerant leak detector to check all joints The system may also be checked for leaks using a halide torch or pressure and soapy solution After completion of...

Страница 5: ... wire to ground connection in control box for safety Connect power wiring to contactor High voltage power connections to 3 phase models is made to Pig Tail leads with field supplied splice connectors Contol Wiring The control voltage is 24 VAC NEC Class I insulated 18 AWG is required for control wiring For lengths longer than 150 feet contact your local distributor for technical service Ensure the...

Страница 6: ...its with Indoor TXV Units installed with cooling mode TXV require charging with the subcooling method 1 Operate unit a minimum of 10 minutes before checking charge 2 Measure liquid service valve pressure by attaching an accurate gage to service port Determine saturation temp from T P chart 3 Measure liquid line temperature by attaching an accurate thermistor type or electronic thermometer to liqui...

Страница 7: ...507043 03 Page 7 of 9 Issue 1337 534773W A C SINGLE PHASE WIRING DIAGRAM Single speed condenser fan ...

Страница 8: ...Page 8 of 9 507043 03 Issue 1337 A C SINGLE PHASE WIRING DIAGRAM Multi speed condenser fan 537511 01 ...

Страница 9: ...rees can be drawn into coils by movement of the air Clogged condenser coils will lower the efficiency of your unit and cause damage to the condenser Periodically debris should be brushed from the condenser coils SHARP OBJECT HAZARD WARNING Condenser coils have sharp edges Wear adequate body protection on body extremities e g gloves FAILURE TO FOLLOW THIS WARNING COULD RESULT IN BODILY INJURY Use a...

Отзывы: