IE048-480 Power Supply Installation Guide
47
Figure 9. Wrapping Wire Strands
For added protection against loose strands, tin stranded wires with
solder or use electric wire ferrules.
Do not route wires on the floor or other areas where they might
pose a hazard.
After installing wires, visually inspect them for exposed wires or
loose wire strands. Refer to Figure 10.
Figure 10. Verifying Wire Installation
Warning
Check to see if there are any exposed copper strands coming from
the installed wires. When the installation is done correctly there
should be no exposed copper wire strands extending from the
terminal block. Any exposed wiring can conduct harmful levels of
electricity to persons touching the wires.
E12
Correct
Incorrect -
Exposed Wire
Incorrect - Loose
Wire Strands
Содержание IE048-480
Страница 1: ...613 002833 Rev A IE048 480 Industrial AC DC Power Supply Installation Guide...
Страница 6: ...6 I PDF Allied Telesis alliedtelesis com library...
Страница 8: ...Contents 8...
Страница 10: ...Figures 10...
Страница 12: ...Tables 12...
Страница 16: ...Preface 16...
Страница 21: ...IE048 480 Power Supply Installation Guide 21 Figure 3 Bottom Panel AC Input Connectors Ground Connector...
Страница 42: ...Chapter 2 Beginning the Installation 42...
Страница 51: ...IE048 480 Power Supply Installation Guide 51 Figure 12 Installing the Ground Wire...
Страница 53: ...IE048 480 Power Supply Installation Guide 53 Figure 13 Installing the AC Power Wires...
Страница 60: ...Chapter 3 Installing the Power Supply 60...
Страница 72: ...Appendix A Technical Specifications 72...