Connecting Bare
DC Power Wires
To attach bare lead wires to the positive and negative terminals on the
power supply, perform the following procedure:
1. Prepare adequate lengths of two solid or stranded 8 AWG DC power
wires by stripping them as shown in Figure 123.
Figure 123. Stripping Solid or Stranded DC Power Wires
2. Use a #1 Phillips-head screwdriver to loosen the two screws on the
plastic cover over the positive and negative terminals on the power
supply and slide the cover to the right, as shown in Figure 110 on page
171. You may need to lift the locking handle slightly to access the
bottom screw.
3. Use a #3 Phillips-head screwdriver to remove the two screws from the
positive and negative terminals, as shown in Figure 111 on page 172.
4. Wrap the positive lead wire clockwise around one of the terminal
screws and secure the screw and wire to the positive terminal
connection on the terminal block with a #3 Phillips-head screwdriver.
The positive terminal is on the left.
You may attach the wire to the terminal so that it extends either above
or below the terminal block. Figure 124 on page 184 shows the wire
above the terminal block. Allied Telesis recommends tightening the
screw to 30 to 40 inch-lbs.
Содержание AT-SBx8
Страница 8: ...Contents 8...
Страница 12: ...List of Figures 12...
Страница 14: ...List of Tables 14...
Страница 18: ...Preface 18...
Страница 32: ...Chapter 1 Chassis and Power Supplies 32...
Страница 118: ...Chapter 6 Installing the Power Supplies 118...
Страница 134: ...Chapter 7 Installing the AT SBx81CFC400 Controller and Ethernet Line Cards 134...
Страница 152: ...Chapter 8 Installing the Transceivers and Cabling the Ports 152...
Страница 190: ...Chapter 9 Powering On the Chassis 190...
Страница 212: ...Chapter 11 Troubleshooting 212...
Страница 230: ...Chapter 12 Replacing Modules 230 Figure 146 Lowering the Locking Handle on the Power Supply Slot Cover...