AT-SBx908 GEN2 Installation Guide for Virtual Chassis Stacking
101
Installing the Blank Power Supply Slot Cover
If you installed only one power supply in the chassis, check that the empty
power supply slot is covered with the blank power supply slot cover
included with the chassis. Do one of the following:
If the chassis has two power supplies or if the empty power supply
is already covered, go to “Installing the Power Cord Retaining
Clips” on page 103.
If a power supply slot is uncovered, continue with the procedure in
this section.
To install the bank power supply slot cover, perform the following
procedure:
1. Lift the locking handle on the bank power supply slot cover. Refer to
Figure 56. Lifting the Locking Handle on the Blank Power Supply Slot
Cover
2. Align the cover in the empty power supply slot and carefully slide it into
the slot. Figure 57 on page 102 shows the cover being installed in the
PSU B slot.