6. Compare the approach value with those shown in Table
7. If the values do not agree with those provided in Table 7,
add refrigerant to lower the approach temperature or recover
refrigerant from the system to increase the approach
temperature.
Check Charge Using Normal Operating Pressures
Use Table 8 to perform maintenance checks. Table 8 is not
a procedure for charging the system. Minor variations in
these pressures may be due to differences in installations.
Significant deviations could mean that the system is not
properly charged or that a problem exists with some
component in the system.
=
_
Outdoor Ambient Temperature °F
Liquid Line Temperature °F
Approach Temperature °F
°
°
°
=
_
Liquid Line Temperature °F
Saturation Temperature °F
Subcooling Value °F
°
°
°
Table 7
Subcooling Values
Table 8
Approach Values for TXV Systems
Approach value is the liquid line temperature minus
the outdoor ambient temperature (± 1°F).
Note: For best results, use the same digital
thermometer to check both outdoor ambient and
liquid temperatures.
Table 6
T e m p .
(
F
P re s s u re
P s ig
T e m p .
(
F
P re s s u re
P s ig
T e m p .
(
F
P re s s u re
P s ig
3 2 1 0 0 .8 7 4 2 1 4 .0 1 1 6 3 9 6 .0
3 3 1 0 2 .9 7 5 2 1 7 .4 1 1 7 4 0 1 .3
3 4 1 0 5 .0 7 6 2 2 0 .9 1 1 8 4 0 6 .7
3 5 1 0 7 .1 7 7 2 2 4 .4 1 1 9 4 1 2 .2
3 6 1 0 9 .2 7 8 2 2 8 .0 1 2 0 4 1 7 .7
3 7 1 1 1 .4 7 9 2 3 1 .6 1 2 1 4 2 3 .2
3 8 1 1 3 .6 8 0 2 3 5 .3 1 2 2 4 2 8 .8
3 9 1 1 5 .8 8 1 2 3 9 .0 1 2 3 4 3 4 .5
4 0 1 1 8 .0 8 2 2 4 2 .7 1 2 4 4 4 0 .2
4 1 1 2 0 .3 8 3 2 4 6 .5 1 2 5 4 4 5 .9
4 2 1 2 2 .6 8 4 2 5 0 .3 1 2 6 4 5 1 .8
4 3 1 2 5 .0 8 5 2 5 4 .1 1 2 7 4 5 7 .6
4 4 1 2 7 .3 8 6 2 5 8 .0 1 2 8 4 6 3 .5
4 5 1 2 9 .7 8 7 2 6 2 .0 1 2 9 4 6 9 .5
4 6 1 3 2 .2 8 8 2 6 6 .0 1 3 0 4 7 5 .6
4 7 1 3 4 .6 8 9 2 7 0 .0 1 3 1 4 8 1 .6
4 8 1 3 7 .1 9 0 2 7 4 .1 1 3 2 4 8 7 .8
4 9 1 3 9 .6 9 1 2 7 8 .2 1 3 3 4 9 4 .0
5 0 1 4 2 .2 9 2 2 8 2 .3 1 3 4 5 0 0 .2
5 1 1 4 4 .8 9 3 2 8 6 .5 1 3 5 5 0 6 .5
5 2 1 4 7 .4 9 4 2 9 0 .3 1 3 6 5 1 2 .9
5 3 1 5 0 .1 9 5 2 9 5 .1 1 3 7 5 1 9 .3
5 4 1 5 2 .8 9 6 2 9 9 .4 1 3 8 5 2 5 .8
5 5 1 5 5 .5 9 7 3 0 3 .8 1 3 9 5 3 2 .4
5 6 1 5 8 .2 9 8 3 0 8 .2 1 4 0 5 3 9 .0
5 7 1 6 1 .0 9 9 3 1 2 .7 1 4 1 5 4 5 .6
5 8 1 6 3 .9 1 0 0 3 1 7 .2 1 4 2 5 5 2 .3
5 9 1 6 6 .7 1 0 1 3 2 1 .8 1 4 3 5 5 9 .1
6 0 1 6 9 .6 1 0 2 3 2 6 .4 1 4 4 5 6 5 .9
6 1 1 7 2 .6 1 0 3 3 3 1 .0 1 4 5 5 7 2 .8
6 2 1 7 5 .5 1 0 4 3 3 5 .7 1 4 6 5 7 9 .8
6 3 1 7 8 .5 1 0 5 3 4 0 .5 1 4 7 5 8 6 .8
6 4 1 8 1 .6 1 0 6 3 4 5 .3 1 4 8 5 9 3 .8
6 5 1 8 4 .3 1 0 7 3 5 0 .1 1 4 9 6 0 1 .0
6 6 1 8 7 .7 1 0 8 3 5 5 .0 1 5 0 6 0 8 .1
6 7 1 9 0 .9 1 0 9 3 6 0 .0 1 5 1 6 1 5 .4
6 8 1 9 4 .1 1 1 0 3 6 5 .0 1 5 2 6 2 2 .7
6 9 1 9 7 .3 1 1 1 3 7 0 .0 1 5 3 6 3 0 .1
7 0 2 0 0 .6 1 1 2 3 7 5 .1 1 5 4 6 3 7 .5
7 1 2 0 3 .9 1 1 3 3 8 0 .2 1 5 5 6 4 5 .0
7 2 2 0 7 .2 1 1 4 3 8 5 .4
7 3 2 1 0 .6 1 1 5 3 9 0 .7
7 2 2 0 7 .2 1 1 4 3 8 5 .4
7 3 2 1 0 .6 1 1 5 3 9 0 .7
R410A Temperature/Pressure Chart
Содержание 4AC18LT Series
Страница 16: ...506469 01 Issue 1008 Page 16 of 24 Table 8...
Страница 18: ...506469 01 Issue 1008 Page 18 of 24 Table 9 Flash Codes...
Страница 19: ...506469 01 Issue 1008 Page 19 of 24 Table 10 Flash Codes cont...
Страница 20: ...506469 01 Issue 1008 Page 20 of 24 Table 11 Miswired Module Troubleshooting...
Страница 23: ...506469 01 Issue 1008 Page 23 of 24 WIRE DIAGRAM...
Страница 24: ...506469 01 Issue 1008 Page 24 of 24 NOTES...