6

Installation and Connection

3.4 Swimming Pool Heat Pumps Plumbing 

Location: Connect the unit in the pool pump discharge (return) line downstream of all filter 
and pool pumps, and upstream of any chlorinators, ozonators or chemical pumps.

Standard model have slip glue fittings which accept  40mm NB PVC pipe for connection to 
the pool or Swimming Pool filtration piping. By using a 50 NB to 40NB you can plumb 50NB 
PVC piping straight into the unit. 

Give serious consideration to adding a quick coupler fitting at the unit inlet and outlet to allow 
easy draining of unit for winterizing and to provide easier access should servicing be 

required. 

Condensation: Since the Heat pump cools down the air about 4 -5

, water may condense on 

the fins of the horseshoe shaped evaporator. If the relative humidity is very high, this could 
be as much as several litres an hour. The water will run down the fins into the basepan and 
drain out through the barbed plastic condensation drain fitting on the side of the basepan. 

This fitting is designed to accept 3/4" clear vinyl tubing which can be pushed on by hand and 
run to a suitable drain. It is easy to mistake the condensation for a water leak inside the unit. 

NB: A quick way to verify that the water is condensation is to shut off the unit  and keep the 

pool pump running. If the water stops running out of the basepan, it is condensation. AN 
EVEN QUICKER WAY IS to TEST THE DRAIN WATER FOR CHLORINE - if the is no chlorine 
present, then it's condensation. 

3.INSTALLATION AND CONNECTION

The Swimming Pool Heat Pumps exclusive rated flow titanium heat exchanger requires no 
special plumbing arrangements except bypass(please set the flow rate according to the 

nameplate). The water pressure drop is less than 10kPa  at max. Flow rate. Since there is no 
residual heat or flame Temperatures, The unit does not need copper heat sink piping. PVC  

pipe can be run straight into the unit.

6

To  pool

From pump

PVC COUPLER

RECOMMENDED(Provided)

CONDENSATION

DRAIN

BARB FTG

3.INSTALLATION AND CONNECTION

7

3.5 Swimming Pool Heat Pumps Electrical Wiring 

NOTE: Although the unit heat exchanger is electrically isolated from the rest of the unit, it 
simply prevents the flow of electricity to or from the pool water. Grounding the unit is still 
required to protect you against short circuits inside the unit. Bonding is also required.

3.6 Initial startup of the Unit  

NOTE- In order for the unit to heat the pool or spa, the filter pump must be running to 
circulate water through the heat exchanger.

Start up Procedure - After installation is completed, you should follow these steps: 
1. Turn on your filter pump. Check for water leaks and verify flow to and from the pool.
2. Turn on the electrical power supply to the unit, then press the key ON/OFF of wire  
controller, It should start in  several seconds.
3. After running a few minutes make sure the air leaving the top(side) of the unit is 
cooler(Between 5-10 

)

4. With the unit operating turn the filter pump off. The unit should also turn off automatically, 
5. Allow the unit and pool pump to run 24 hours per day until desired pool water emperature is 
reached. When the water-in temperature reach setting, The unit just shuts off. The unit  will 

now automatically restart (as long as your pool pump is running)when the pool temperature 

drops more than 2

below set temperature.  

Time Delay- The unit is equipped with a 3 minute built-in solid state restart delay included to 
protect control circuit components and to eliminate restart cycling and contactor chatter. 
This time delay will automatically restart the unit approximately 3 minutes after each control 

circuit interruption. Even a brief power interruption will activate the solid state 3 minute 
restart delay and prevent the unit from starting until the 5 minute countdown is completed. 

Power interruptions during the delay period will have no effect on the 3 minute countdown. 

The unit has a separate molded-in junction box with a standard electrical conduit nipple 
already in place. Just remove the screws and the front panel, feed your supply lines in 

through the conduit nipple and wire-nut the electric supply wires to the three connections  
already in the junction box (four connections  if three phase). To complete electrical hookup, 

connect Heat Pump by electrical conduit, UF cable or other suitable means as specified (as 
permitted by local electrical authorities) to a dedicated AC power supply branch circuit 

equipped with the proper circuit breaker, disconnect or time delay fuse protection. 

Disconnect - A disconnect means (circuit breaker , fused or un-fused switch) should be 
located within sight of and readily accessible from the unit, This is common practice on 

commercial and residential air conditioners and heat pumps. It prevents remotely-energizing 
unattended equipment and permits turning off power at the unit while the unit is being 

serviced. 

Содержание ALLPH 91Kw

Страница 1: ...Swimming Pool Heat Pump Installation Operation Manual Model ALLPH 91Kw ...

Страница 2: ...Initial Start up of the Unit 4 Usage and Operation 4 1 Function of the controller 4 2 Usage of the controller 4 3 The operation of mode switching 4 4 The operation of system state checking 4 5 The operation of parameter setting 4 6 The operation of clock setting 4 7 The operation of timer setting 4 8 Keyboard lock 4 9 Malfunction display 4 10 Parameter table 5 Maintenance and Inspection 5 1 Malfun...

Страница 3: ...ut according to the recommended time and frequency as stated in this manual Use genuine standard spare parts only Failure to comply with these recommendations will invalidate the warranty Swimming Pool Heat Pump Unit heats the swimming pool water and keeps the temperature constant For split type unit The indoor unit can be Discretely hidden or semi hidden to suit a luxury house Our heat pump has f...

Страница 4: ... Speed Fan Direction Noise Water Connection Water Flow Volume Water Pressure Drop MAX Unit Net Dimensions L W H Unit Shipping Dimensions L W H Net Weight Shipping Weight Model kW BTU h kW A W RPM dB A mm kPa mm mm kg kg 3 m h ALLPH91Kw 91 310000 17 5 31 2 380 415V 3N 50Hz 4 scroll 3 200 3 830 vertical 61 63 28 16 see the drawing of the units see package label see nameplate see package label Heatin...

Страница 5: ...3 Unit Structure and Dimensions 2 2 The dimensions for Swimming Pool Heat Pump Unit 2 SPECIFICATION Models ALLPH91Kw Airflow direction 1920 Water Inlet φ110 Water Outlet φ110 240 160 1070 2170 174 ...

Страница 6: ...necessary spare parts for the water system that provided by users or the installer Attention Please follow these steps when using for the first time 1 Open valve and charge water 2 Make sure that the pump and the water in pipe have been filled with water 3 Close the valve and start the unit Chlorinator cell Water outlet Pool Valve Water supply Water inlet Water pump Sand filter or other type filte...

Страница 7: ...ir which reduces it efficiency and may prevent adequate heat delivery 3 2 Swimming Pool Heat Pumps Location Normally the pool heat pump is installed within 7 5 metres of the pool The longer the distance from the pool the greater the heat loss from the piping For the most part the piping is buried Therefore the heat loss is minimal for runs of up to15 meters 15 meters to and from the pump 30 meters...

Страница 8: ...into the basepan and drain out through the barbed plastic condensation drain fitting on the side of the basepan This fitting is designed to accept 3 4 clear vinyl tubing which can be pushed on by hand and run to a suitable drain It is easy to mistake the condensation for a water leak inside the unit NB A quick way to verify that the water is condensation is to shut off the unit and keep the pool p...

Страница 9: ...set temperature Time Delay The unit is equipped with a 3 minute built in solid state restart delay included to protect control circuit components and to eliminate restart cycling and contactor chatter This time delay will automatically restart the unit approximately 3 minutes after each control circuit interruption Even a brief power interruption will activate the solid state 3 minute restart dela...

Страница 10: ...rent mode page up or confirm current operation ON OFF Press this button to start up shut off the unit cancel current operation or back to upper interface HELP MODE CLOCK Button Name Function 4 1Function of wire controller Press this key to select the upward option or increase the parameter value Press this key to select the downward option or decrease the parameter value Up Down 4 USAGE AND OPERAT...

Страница 11: ...means you can page up 2 Pressing this key could select the upward option or increase the value of a certain parameter 3 Pressing this key could select the downward option or decrease the value of a certain parameter 4 Pressing this key could switch unit mode enter into the next interface or save settings 5 Pressing this key could set the system time or time for regular shutdown or restart 6 Pressi...

Страница 12: ...shutting down Press in the shutdown state for 1s to start up the system Press in the startup state for 1s to shut down the system For example Press for 1s Running state MODE By actual state Month Date Time Week ON Eco heating Inlet temp 25 0 Outlet temp 25 0 31 03 2011 09 10 THU ON Eco heating Inlet temp 25 0 Outlet temp 25 0 31 03 2011 09 10 THU OFF Heating Inlet temp 25 0 Outlet temp 25 0 31 03 ...

Страница 13: ...ss pageup or pagedown to select the needing parameter press to enter and press to exit For example Press Temperature Switch Output Press T01 Inlet water 25 0 T02 Outlet water 25 0 T03 Coil 1 30 5 T04 Coil 2 32 5 T05 Ambient 23 5 T06 Deice 1 4 5 T07 Deice 2 4 5 T08 Suction 1 20 5 Press Press Press ON Cooling Inlet temp 25 0 Outlet temp 25 0 31 03 2011 09 10 THU ON Eco heating Inlet temp 25 0 Outlet...

Страница 14: ...f clock setting At main interface press to enter clock setting interface select the needing parameter and press at this time parameter value flashing press increasing or Decreasing can change parameter value then press to save press can cancel the setting or back to the main interface timer setting refer to timer operation Press to enter clock interface ON Cooling Inlet temp 25 0 Outlet temp 25 0 ...

Страница 15: ...ing automatic and back to the main interface As follows Date 31 01 2011 Time 05 55 Week Thursday Timer Date format Date 31 0 2011 Time 05 55 Week Thursday Timer Date format Date 31 01 20 Time 06 55 Week Thursday Timer Date format Date 31 0 2011 Time 06 55 Week Thursday Timer Date format Date 31 01 2011 Time 06 41 Week Thursday Timer Date format Date 31 01 2011 Time 06 41 Week Thursday Timer Date f...

Страница 16: ...to Sunday the operation is the same with clock setting For example Hour bit flashing No operation in 10s It has been changed Press to enter clock interface Press to select Timer Timer zone Daily timer Press to enter Timer interface A Timer setting Date 31 01 2011 Time 06 55 Week Thursday Timer Date format ON Cooling Inlet temp 25 0 Outlet temp 25 0 31 01 2011 06 55 THU ON Cooling Inlet temp 25 0 O...

Страница 17: ...mer1 00 00 00 00 Timer2 00 00 00 00 Timer3 00 00 00 00 Timer4 00 00 00 00 Timer1 07 00 00 00 Timer2 00 00 00 00 Timer3 00 00 00 00 Timer4 00 00 00 00 Timer1 07 00 00 00 Timer2 00 00 00 00 Timer3 00 00 00 00 Timer4 00 00 00 00 Timer1 07 30 00 00 Timer2 00 00 00 00 Timer3 00 00 00 00 Timer4 00 00 00 00 Timer1 07 30 22 00 Timer2 00 00 00 00 Timer3 00 00 00 00 Timer4 00 00 00 00 Timer1 07 30 22 00 Tim...

Страница 18: ...enter clock interface Press to select Timer Press to enter timer interface B The operation of daily timer Timer1 07 30 22 00 Timer2 00 00 00 00 Timer3 00 00 00 00 Timer4 00 00 00 00 Timer zone Daily timer ON Cooling Inlet temp 25 0 Outlet temp 25 0 31 01 2011 06 55 THU Date 31 01 2011 Time 05 55 Week Thursday Timer Date format ON Cooling Inlet temp 25 0 Outlet temp 25 0 31 01 2011 06 55 THU Date 3...

Страница 19: ...i Timer4 Sat Timer2 Timer4 Sun OFF Mon Timer1 Tue Timer1 Timer3 Wed ON Thu Timer3 Timer1 Fri Timer4 Sat Timer2 Timer4 Sun OFF Mon Timer1 Tue Timer1 Timer3 Wed ON Thu Timer3 Timer1 Fri Timer2 Sat Timer2 Timer4 Sun OFF Mon Timer1 Tue Timer1 Timer3 Wed ON Thu Timer3 Timer1 Fri Timer2 Timer4 Sat Timer2 Timer4 Sun OFF Mon Timer1 Tue Timer1 Timer3 Wed ON Thu Timer3 Timer1 Fri Timer2 Timer3 Sat Timer2 Ti...

Страница 20: ...t 24 00 on Sunday then it will be running the whole day on Monday and vice versa Wednesday ON means system will be running the whole day on Wednesday Thursday OFF means system will be off the whole day on Thursday Saturday Timer1 Timer2 means the time to start up and to shut down is according to Timer1 and Timer2 If there is no operation in 10s system will memory the parameter setting automaticly ...

Страница 21: ...ill be malfunction code showing on the controller screen when relative malfunction occurs You can refer to the malfunction table to find out the failure cause and solution For example P01 Inlet water temp Failure Failure number 1 Malfunction code Malfunction Failure number press or can check next malfunction ON Cooling Inlet temp 25 0 Outlet temp 25 0 31 01 2011 06 55 THU ON Cooling Inlet temp 25 ...

Страница 22: ...Check each protection point of the system Check the wire connection between remote wire controller and main board The temp Sensor is broken or short circuit The temp Sensor is broken or short circuit The temp Sensor is broken or short circuit The temp Sensor is broken or short circuit The temp Sensor is broken or short circuit The temp Sensor is broken or short circuit The temp Sensor is broken or...

Страница 23: ...r too heavy Water flow volume not enough Check the flow volume water system is jammed or not The sensor is open or short circuit Check or change the sensor The sensor is open or short circuit Check or change the sensor The sensor is open or short circuit Check or change the sensor The sensor is open or short circuit Check or change the sensor The sensor is open or short circuit Check or change the...

Страница 24: ...t System 4 low pressure protection input Water flow switch protection input Electric heater overload protection input Symbol L N RO 01 RO 02 RO 03 RO 04 RO 05 RO 06 RO 07 RO 08 RO 09 RO 10 RO 11 DI DO 1 DI DO 2 DI DO 3 DI 01 DI 02 DI 03 DI 04 DI 05 DI 06 DI 07 DI 08 DI 09 DI 10 NO 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 Meaning System protection signal Water input temp...

Страница 25: ...RLY3 RLY4 CN5 CN6 12V NET GND DI01 AI01 AI02 AI03 AI04 AI05 AI06 AI07 AI08 CT1 CN4 GND GND GND GND GND GND GND GND GND CC01 AI09 GND CC02 RO01 RO02 RO03 RO04 CC03 CC04 CT2 CN2 Wire controller NET GND 12V DI01 GND AI01 GND AI02 GND AI03 GND AI04 GND AI05 GND System 2 economizer inlet temp failure input System 1 economizer inlet temp failure input System 1 economizer outlet temp failure input System...

Страница 26: ...cting a crossed out waste bin that is underneath the appliance indicates that this product at the end of its useful life must be handled separately from domestic waste must be taken to a recycling centre for electric and electronic devices or handed back to the dealer when purchasing an equivalent appliance 6 Directive 2002 95 EC RoHs This product is compliant with directive 2002 95 EC RoHs concer...

Страница 27: ...ase line MCB Creepage protector Signal line 2 n 0 5mm Nameplate maximum current Earth line No more than 10A 20A 32A 40A 40A 63A 80A 100A 125A 160A 225A 250A 280A 2 1 5mm 2 2 5mm 2 4mm 2 6mm 2 10mm 2 16mm 2 mm 25 2 mm 25 2 35mm 2 50mm 2 70mm 2 95mm 2 Three phas nit 2 3 1 5mm 2 3 2 5mm 2 3 4mm 2 3 6mm 2 3 10mm 2 16mm 3 2 25mm 3 2 3 25mm 2 3 35mm 2 3 50mm 2 3 70mm 2 3 95mm 30mA less than 0 1 sec 30mA...

Страница 28: ...Code 20160606 0009 ...

Отзывы: