Installation
1800001
12
Electrical Connection
Electrical connections should be made by a qualified
electrical contractor in accordance with all applicable
local and national requirements. A differential circuit
breaker (obtain locally), correctly sized for the power
consumption of the finisher, must be installed near
finisher. Refer to
IMPORTANT: Electrical specifications in
and
are subject to change without notice.
Always refer to product serial plate for most
current specifications of product being installed.
NOTE: Use copper conductors only.
NOTE: Connect to individual branch circuit.
Before preceding, check for proper rotation of exhaust
fan, hydraulic pump, and circulation pump. All three
should be moving in the direction indicated by the
arrow on part. If all three are rotating properly
proceed. If they are not, reverse polarity of component
not rotating properly.
Electrical Models
(CE Approved)
Serial Plate Rating
Model
Recommended
Circuit Breaker
Heater Element
All Voltages
UL15*069
50 Amp
40 hp (30 kW)
UL15*079
50 Amp
40 hp (30 kW)
UL15*099
57 Amp
47 hp (35 kW)
UL15*118
63 Amp
54 hp (40 kW)
UL20*079
50 Amp
40 hp (30 kW)
UL20*099
63 Amp
54 hp (40 kW)
UL20*118
70 Amp
60 hp (45 kW)
UL20*130
70 Amp
60 hp (45 kW)
Table 3
All Gas Models
(CSA and CE Approved)
Serial Plate Rating
Recommended
Circuit Breaker
Full Load Amps
230/50/3
208-240/60/3
30 Amp
28 Amp
400/50/3
20 Amp
16 Amp
440-480/60/3
15 Amp
14 Amp
Table 4