50
Rockwell Automation Publication 750-UM006C-EN-P - March 2022
Chapter 4
Configure and Start Up the Drive
Set the Network IP Address
of the 1783-ETAP
This section provides instructions and information for setting the parameters
to properly configure the embedded EtherNet/IP adapter on the PowerFlex
755 drive. The On-Machine™ drive connects to the network through the1783-
ETAP dual-port Ethernet adapter and supports Device Level Ring (DLR),
linear, or star topology using the ETH1 and ETH2 receptacles. The 24V DC
control power must be present (via the CP receptacle) to configure the 1783-
ETAP dual-port adapter.
Out of box, the ETAP is configured to be a non-supervisor ring node and
responds to the default IP address of 169.254.1.1. If your application does not
require access to the taps diagnostic information or configuration, no further
action is required. Otherwise, set the IP address by using RSLinx® Classic
software, the Logix Designer application, or a BOOTP or DHCP server.
See the Ethernet Tap Product Information, publication
for more
information on the 1783-ETAP adapter.
Volts
(C) S4 Integrated Safe
Speed Monitoring with
Source Brake
Horizontal /
Vertical
Amps
Mechanical Motor
Brake Data
(N) None
Port Assignment
Max Velocity
# Motor Poles
Current
Position Loop
Amps
Speed Loop
Motor Polarity
Voltage
24V DC or
400/480 V AC
Universal
Feedback Port
Forward
Direction
Ethernet/IP address
Reverse
Direction
Firmware Revision
Drive Catalog Number
Drive Rating
(4)
Add-on Profile Version
HIM
20-HIM-C6S
Option
Module Port
Assignment
(5)
Port 2
Port 4
Port 5
Port 6
Port 7
Port 8
HIM
20-750-2263C-1R2T
20-750-APS
(1) The motor data must be entered in kW when doing installation for integrated motion. (kW=Hp*0.746)
(2) If an Allen Bradley permanent magnet servo motor is being used (versus an induction motor), you must look up the AB servo motor part number. Refer to PowerFlex 750-Series AC Drives Technical Data,
publication
to obtain proper VFD drive settings for the motor being controlled.
(3) Get help determining how products interact, check features and capabilities, and find associated firmware
https://compatibility.rockwellautomation.com/Pages/home.aspx
. For additional information
on how to update drive firmware, see the
of this manual.
(4) Firmware version, drive catalog number, and drive ratings are located on the data name plate. Additional information about the option modules and their slots are located in the electrical schematics.
(5) Slot 4, 5, and 6 are specific to your application. The option module used is identified in the catalog string definition. See
Catalog Number Explanation on page 16
for more information.
IMPORTANT
If you use BOOTP or DHCP to set the IP address, only the IP address of the
1783-ETAP module is set. It does not affect the setting of the PowerFlex
drive.
Содержание The PowerFlex 755 On-Machine
Страница 1: ...User Manual Original Instructions PowerFlex 755 On Machine Drive Bulletin Number 26G...
Страница 208: ...208 Rockwell Automation Publication 750 UM006C EN P March 2022 Appendix B Startup Information Notes...
Страница 216: ...216 Rockwell Automation Publication 750 UM006C EN P March 2022 Index Notes...
Страница 217: ...Rockwell Automation Publication 750 UM006C EN P March 2022 217 PowerFlex 755 On Machine Drive User Manual...