Rockwell Automation Publication 1756-RM100F-EN-P - October 2018
141
Chapter
7
Diagnostics and Status Indicators with
ControlLogix Systems
This chapter features these controllers, and where applicable, the controllers
are known as:
You can diagnose and troubleshoot the 5580 Controllers with:
•
Controller Status Display and Indicators on page 141
•
Controller Web Pages on page 143
Controller Status Display
and Indicators
The 5580 controllers have a 4-character display, four status indicators, and two
Ethernet indicators.
4-Character Display
The 4-character display on the 5580 controllers shows the same messages as the
5570 controllers, along with these updates.
This table lists the general status messages that can scroll across the display. For
information about more detailed controller conditions, see the
ControlLogix 5580 Controllers User Manual, publication
Controller Family
Includes these controllers
5580 controllers
ControlLogix® 5580 and GuardLogix® 5580 controllers
5570 controllers
ControlLogix® 5570 and GuardLogix 5570 controllers
Message on 4-character Display
5580 Controller Behavior
Link Down
Message appears when an Ethernet port does not have a connection. Message scrolls continuously during operation.
Link Disabled
Message appears when you have disabled the Ethernet port. Message scrolls continuously during operation.
DHCP- XX:XX:XX:XX:XX:XX
Message appears when the controller is set for DHCP, but not configured on a network. The message shows the MAC address of the
controller. Message scrolls continuously during operation if no IP address is set.
Ethernet Port Rate/Duplex State
The current port rate and duplex state when the port has a connection (for example, 1Gb/FULL). Message scrolls continuously during
operation. If not connected directly to another 1 Gb device, then the message shows 100/FULL.
IP Address
The IP address of the controller. Appears on powerup, then scrolls continuously during operation. If the IP address is not yet set, then
the MAC address appears.
Duplicate IP - XX:XX:XX:XX:XX:XX
Message appears when the controller detects a device with the same IP address on the network. The message shows the MAC address
of the device with the duplicate IP address. Message scrolls continuously during operation.
Backup Energy HW Failure - Save Project
A failure with the embedded storage module has occurred. If a power is lost to the controller, the controller cannot save the program.
If you see this message, save your program to SD card before you remove power and then replace the module.
Backup Energy Low - Save Project
The embedded storage module does not have sufficient energy to enable the controller to save the program if power is lost to the
controller. If you see this message, save your program to SD card before you remove power and then replace the module.