60
Rockwell Automation Publication 1560F-UM001A-EN-P - June 2019
Chapter 2
Installation
Bulletin 1503E
For 1503E, refer to applicable documentation from the OEM for installation,
grounding, interlocking and wiring. This manual should be utilized in
conjunction with the OEM supplied documentation, and is suitable for
commissioning, programming, calibration, metering, serial communications,
diagnostics, troubleshooting and maintenance of a standard solid-state controller.
Line and Load Power Wiring
The wire sizes must be selected individually, observing all applicable safety and
CEC or NEC regulations. The minimum permissible wire size does not
necessarily result in the best operating economy. The minimum recommended
size for the wires between the controller and the motor is the same as that used if
a main voltage source connection to the motor was used. The distance between
the controller and motor may affect the size of the conductors used.
Consult the wiring diagrams and appropriate CEC or NEC regulations to
determine correct power wiring. If assistance is needed, contact your area
Rockwell Automation Sales Office.
Interlocking
Hinged doors and panels, which provide access to medium voltage components,
must be mechanically interlocked to ensure circuit isolation. If a combination
SMC-50 (1562F) is purchased from Rockwell Automation, all medium voltage
compartments will be mechanically interlocked such that they cannot be opened
unless the isolating switch for the unit is open. Each medium voltage door is
interlocked to the isolating switch handle. To open the doors, move the isolating
switch to the OFF position and loosen the two retaining bolts on the main power
cell door. Once this door is open, the other doors may be opened in sequence,
depending on the specific interlock scheme provided. The retrofit-type SMC-50
(1560F) is intended to be added to an existing motor controller, and has no
isolating means included.
IMPORTANT
The control and signal wires should be positioned at least six (6) inches
(150 mm) from medium voltage power cables. Additional noise suppression
practices (including separate steel conduits for signal leads, etc.) are
recommended.
ATTENTION:
For 1503E and 1560F, it is the responsibility of the installer/user to
ensure the equipment interlocking scheme is in place and functional before
energizing the equipment. Inadequate interlocking could expose personnel to
energized parts which could result in severe burns, injury or death.
Содержание SMC-50
Страница 10: ...10 Rockwell Automation Publication 1560F UM001A EN P June 2019 Table of Contents Notes ...
Страница 12: ...12 Rockwell Automation Publication 1560F UM001A EN P June 2019 Preface Notes ...
Страница 68: ...68 Rockwell Automation Publication 1560F UM001A EN P June 2019 Chapter 2 Installation Notes ...
Страница 120: ...120 Rockwell Automation Publication 1560F UM001A EN P June 2019 Chapter 4 Programming Notes ...
Страница 130: ...130 Rockwell Automation Publication 1560F UM001A EN P June 2019 Chapter 5 Metering Notes ...
Страница 134: ...134 Rockwell Automation Publication 1560F UM001A EN P June 2019 Chapter 6 Optional HIM Operation Notes ...
Страница 144: ...144 Rockwell Automation Publication 1560F UM001A EN P June 2019 Chapter 7 Communications Notes ...
Страница 156: ...156 Rockwell Automation Publication 1560F UM001A EN P June 2019 Chapter 8 Diagnostics Notes ...
Страница 198: ...198 Rockwell Automation Publication 1560F UM001A EN P June 2019 Chapter 10 Maintenance Notes ...
Страница 240: ...240 Rockwell Automation Publication 1560F UM001A EN P June 2019 Appendix A Parameter Information Notes ...
Страница 242: ...242 Rockwell Automation Publication 1560F UM001A EN P June 2019 Appendix B Controller Duty Cycle Ratings Notes ...
Страница 250: ...250 Rockwell Automation Publication 1560F UM001A EN P June 2019 Appendix C 1560F and 1562F Relay Control Notes ...
Страница 280: ...280 Rockwell Automation Publication 1560F UM001A EN P June 2019 Appendix G Using DeviceLogix Notes ...
Страница 284: ...284 Rockwell Automation Publication 1560F UM001A EN P June 2019 Appendix H Spare Parts Notes ...
Страница 286: ...286 Rockwell Automation Publication 1560F UM001A EN P June 2019 Appendix I Accessories Notes ...
Страница 291: ......