1
Publication 1747-6.5.5 - August 2000
Chapter
7
Troubleshooting
The 1747-SDN interface module is provided with LED diagnostic
indicators on its front panel. The diagnostics provided by these
indicators are described in this chapter.
Module Status Indicator
The bicolor (green/red) Module Status indicator (MODULE) indicates
whether the 1747-SDN module has power and is functioning properly.
For information about
See page
Table 7.A - Module Status Indicator
If the MODULE
indicator is:
Then:
Take this action:
Off
There is no power applied to the
module.
Verify power connections and
apply power.
Green
The module is operating normally.
No action required.
Flashing Green
The module is not configured.
Configure the module.
Flashing Red
There is an invalid configuration.
Check configuration setup.
Red
The module has an unrecoverable
fault.
Replace the module.
Содержание SLC 500 DeviceNet
Страница 1: ...SLC 500 DeviceNet Scanner Module 1747 SDN User Manual...
Страница 4: ......
Страница 52: ...Publication 1747 6 5 5 August 2000 3 16 Hardware Setup...
Страница 68: ...Publication 1747 6 5 5 August 2000 4 16 Configuring the DeviceNet Network...
Страница 86: ...Publication 1747 6 5 5 August 2000 5 18 Communicating with DeviceNet from Another Network...
Страница 96: ...Publication 1747 6 5 5 August 2000 6 10 Creating and Running the Example Application Program...
Страница 106: ...Publication 1747 6 5 5 August 2000 A 6 Data Map Example...
Страница 112: ...Publication 1747 6 5 5 August 2000 C 4 Configuring the Processor s RS 232 Port for the ControlNet Interface...
Страница 118: ...Publication 1747 6 5 5 August 2000 E 4 Configuring SLC 5 05 Ethernet Communications...
Страница 124: ...Publication 1747 6 5 5 August 2000 F 6 Configuring the SLC 500 Processor s Communication Channels Using a DF1 Driver...
Страница 128: ...Publication 1747 6 5 5 August 2000 G 4 Installing and Configuring the DH Communications Driver...
Страница 137: ......
Страница 139: ...SLC500 DeviceNet Scanner Module User Manual...