1–7
Installing Your DeviceNet Adapter Module
Publication 17946.5.5 - October 1996
Connect external wiring to the DeviceNet adapter as shown below.
D
F
G
E
20131
24V
COM
DeviceNet Connector
1. Connect the DeviceNet cable to the removable connector as
shown.
Connect
To
BLK Wire
-V
BLU Wire
CAN* Low
Bare Wire
Drain
WHT Wire
CAN High
RED Wire
+V
CAN = Controller Area Network
NOTE: Cable colors are shown on the wiring label on the front of the
module.
2. Insert connector into mating connector on DeviceNet adapter
module.
3. C24V dc input to the left side of the lower connector E.
4. Connect 24V common to the left side of the upper connector D.
5. Connections G and F are used to pass 24V dc power (G) and 24V
common (F) to the next module in the series (if required).
For example:
Wiring when total current draw is less than 10A
Daisychaining
24V dc
Wiring