Rockwell Automation Publication 1732IL-IN001B-EN-P - April 2019
7
ArmorBlock 16-Channel IO-Link Hubs
M12 Style, 5-pin, A-Coded I/O Female Connector — 1732IL-10X6M12 Output
Auxiliary Power Connectors
M12 Style, 5-pin, L-Coded Power Male Connector — 1732IL-16CFGM12M12L
ATTENTION:
Only use power supply units for the system/sensor and actuator supply that correspond to PELV (protective extra low voltage) or SELV (safety extra
low voltage). Power supplies according to EN 61558-2-6 (transformers) or EN 60950-1 (switching power supply units) fulfill these requirements.
3
4
1
2
5
Pin
Value
Function
1
NC
Not connected
2
Out B
Digital output (Odd channels)
3
GND AUX
Reference potential to L+
4
Out A
Digital output (Even channels)
5
FE
Functional earth
View into Connector
5
1
4
3
2
Pin
Value
Function
1
+24V US
Sensor power +
2
GND UL
Output power -
3
GND 0V
Sensor power -
4
+24V UL
Output power +
5
FE
Functional earth
View into Connector