Allen-Bradley Rockwell Automation 1606-XLP60EQT Скачать руководство пользователя страница 11

All parameters are specified at 24V, 2.5A, 230Vac input, 25°C ambient and after a 5 minutes run-in time unless noted otherwise.

Rockwell Automation Publication 1606-RM014A-EN-P — March 2014

11

Bulletin 1606 Switched Mode Power Supplies

 

13. EMC

The power supply is suitable for applications in industrial environment as well as in residential, commercial and light 
industry environment without any restrictions. A detailed EMC report is available upon request. 

 

EMC Immunity 

Generic standards: EN 61000-6-1 and EN 61000-6-2 

Electrostatic discharge  

EN 61000-4-2 

Contact discharge 
Air discharge 

8kV 
8kV 

Criterion A 
Criterion A 

Electromagnetic RF field 

EN 61000-4-3 

80MHz-2.7GHz 

10V/m 

Criterion A 

Fast transients (Burst) 

EN 61000-4-4 

Input lines 
Output lines 

4kV 
2kV 

Criterion A 
Criterion A 

Surge voltage on input 

EN 61000-4-5 

 N 

 PE, L 

 PE 

2kV 
4kV 

Criterion A 
Criterion A 

Surge voltage on output 

EN 61000-4-5 

 - 

 PE, - 

 PE 

1kV 
2kV 

Criterion A 
Criterion A 

Conducted disturbance 

EN 61000-4-6 

0.15-80MHz 

10V 

Criterion A 

Mains voltage dips 

EN 61000-4-11 

0% of 100Vac 
40% of 100Vac 
70% of 100Vac 
0% of 200Vac

 

40% of 200Vac 
70% of 200Vac 

0Vac, 20ms 
40Vac, 200ms 
70Vac, 500ms 
0Vac, 20ms 
80Vac, 200ms 
140Vac, 500ms 

Criterion A *) 
Criterion C  
Criterion A 
Criterion A 
Criterion A 
Criterion A 

Voltage interruptions 

EN 61000-4-11  

0Vac, 

5000ms  Criterion 

Input voltage swells 

RA internal standard

300Vac, 500ms 

Criterion A 

Powerful transients 

VDE 0160 

over entire load range 

750V, 1.3ms 

Criterion A 

Criteria:

 

A:

    Power supply shows normal operation behavior within the defined limits. 

B:

 

The power supply operates continuously during and after the test. During the test minor temporary impairments may occur, which will be 
corrected by the power supply itself. 

C:

    Temporary loss of function is possible. Power supply may shut-down and restarts by itself. No damage or hazards for the power supply 

will occur. 

*)

 

Up to 1.8A output current criterion A, above 1.8A output current criterion B

 

 

EMC Emission 

Generic standards: EN 61000-6-3 and EN 61000-6-4 

Conducted emission  

EN 55011, EN 55022, FCC Part 15, CISPR 11, CISPR 22 

Class B, input lines 

Radiated emission 

EN 55011, EN 55022, CISPR 11, CISPR 22 

Class B 

Harmonic input current 

EN 61000-3-2 

Not applicable below 75W 
input power 

Voltage fluctuations,  
flicker *) 

EN 61000-3-3 

Fulfilled 

This device complies with FCC Part 15 rules. 
Operation is subjected to following two conditions: (1) this device may not cause harmful interference, and (2) this 
device must accept any interference received, including interference that may cause undesired operation. 

*) tested with constant current loads, non pulsing 

 

Switching frequency 

 

 

Converter frequency 

variable, typ. 100kHz, min. 45kHz, max. 160kHz 

Input voltage and output 
load dependent 

Содержание Rockwell Automation 1606-XLP60EQT

Страница 1: ...2 Use in a Tightly Sealed Enclosure 22 21 13 Mounting Orientations 23 Bulletin 1606 Switched Mode Power Supplies Catalog Number 1606 XLP60EQT Index PE and symbol PE is the abbreviation for Protective...

Страница 2: ...or exposed to a critical industrial environment This series of power supplies offers output voltages from 5 to 56Vdc and power ratings from 15W to 120W Principal characteristics of the 1606 XLP60EQT a...

Страница 3: ...signed for convection cooling and does not require an external fan Do not obstruct airflow and do not cover ventilation grid e g cable conduits by more than 30 Keep the following installation clearanc...

Страница 4: ...5A see Fig 3 4 Crest factor typ 3 4 3 7 4 0 at 24V 2 5A Start up delay typ 170ms 110ms 90ms see Fig 3 2 Rise time typ 50ms 50ms 60ms at 24V 2 5A 0mF see Fig 3 2 120ms 110ms 140ms at 24V 2 5A 2 5mF Tu...

Страница 5: ...ter turn on of the input voltage The inrush current is input voltage and ambient temperature independent The charging current into EMI suppression capacitors is disregarded in the first microseconds a...

Страница 6: ...mum output voltage which can occur at the clockwise end position of the potentiometer due to tolerances There is no guarantee this value will be achieved The typical value is about 28 6V Fig 5 1 Outpu...

Страница 7: ...ld up Time Zero Transition Output Voltage Input Voltage 7 DC Input The power supply can also be supplied from a DC source Use a battery or similar DC source For other sources contact RA Connect the po...

Страница 8: ...1 25A half load typ 8 6W 7 8W 6 4W at 24V 2 5A full load Fig 8 1 Efficiency vs output current at 24V typ Fig 8 2 Losses vs output current at 24V typ Efficiency 0 82 86 90 80 92 2 5A 0 5 1 5 2 0 Outpu...

Страница 9: ...sh Limiter Power Converter Output Voltage Regulator Output Filter VOUT DC on PE 10 Front Side and User Elements Fig 10 1 Front side A Output Terminals Screw terminals Dual terminals for the negative a...

Страница 10: ...olytic capacitors has been reduced AC 100V AC 120V AC 230V Lifetime expectancy 50 000h 66 000h 90 000h at 24V 2 5A and 40 C 122 000h 132 000h 104 000h at 24V 1 25A and 40 C 142 000h 188 000h 255 000h...

Страница 11: ...A Voltage interruptions EN 61000 4 11 0Vac 5000ms Criterion C Input voltage swells RA internal standard 300Vac 500ms Criterion A Powerful transients VDE 0160 over entire load range 750V 1 3ms Criteri...

Страница 12: ...e Fig 14 2 IEC 62103 EN 50178 overvoltage category II Altitude de rating 4W 1000m or 5 C 1000m 2000m 6500ft see Fig 14 2 Over voltage category III IEC 62103 EN 50178 altitudes up to 2000m II altitudes...

Страница 13: ...tion protection 2 5mm in diameter e g screws small parts Over temperature protection Not included Input transient protection MOV Metal Oxide Varistor Internal input fuse T3 15A H B C not user replacea...

Страница 14: ...down Connect all phase terminals together as well as all output poles before conducting the test When testing set the cut off current settings to the value in the table below Fig 17 1 Dielectric stre...

Страница 15: ...ED E168663 for use in the U S A UL 60950 1 and Canada C22 2 No 60950 Information Technology Equipment Level 3 NEC Class 2 NEC CLASS 2 Listed as Limited Power Source LPS in the UL 60950 1 UL report Acc...

Страница 16: ...ch 2014 Bulletin 1606 Switched Mode Power Supplies 19 Physical Dimensions and Weight Weight 250g 0 55lb DIN Rail Use 35mm DIN rails according to EN 60715 or EN 50022 with a height of 7 5 or 15mm The D...

Страница 17: ...tends the hold up time after turn off of the AC power In times when the power supply provides sufficient voltages the buffer module stores energy in integrated electrolytic capacitors In case of mains...

Страница 18: ...n before such an event the built in large sized output capacitors inside the power supply can deliver extra current Discharging this capacitor causes a voltage dip on the output The following two exam...

Страница 19: ...al regulations might apply If an external fuse is necessary or utilized minimum requirements need to be considered to avoid nuisance tripping of the circuit breaker A minimum value of 6A B or 3A C Cha...

Страница 20: ...next is allowed as long as the average output current through one terminal pin does not exceed 25A If the current is higher use a separate distribution terminal block Fig 21 3 Daisy chaining of output...

Страница 21: ...EMI inrush current and harmonics will increase when using multiple power supplies in series Earth Unit A AC DC Unit B AC DC Load 21 9 Operation on Two Phases 240V 10 max Fuse L2 L1 L3 L N PE Power Sup...

Страница 22: ...tempts 21 12 Use in a Tightly Sealed Enclosure When the power supply is installed in a tightly sealed enclosure the temperature inside the enclosure will be higher than outside In such situations the...

Страница 23: ...put current Curve A2 Max allowed output current results in approximately half the lifetime expectancy of A1 Fig 21 7 Mounting Orientation A Standard orientation Power Supply OUTPUT INPUT Output Power...

Страница 24: ...ial help in getting your product up and running New Product Satisfaction Return Rockwell Automation tests all of its products to help ensure that they are fully operational when shipped from the manuf...

Отзывы: