Programming and Parameters
3-39
Advance Program Group
(continued)
A171 [Start Boost]
Related Parameter(s):
,
,
,
,
[Motor NP Volts]) and redefines the Volts per Hz curve when A170
[Boost Select] = 0 “Custom V/Hz”.
Values
Default:
2.5%
Min/Max:
0.0/25.0%
Display:
1.1%
Frequency
Voltage
A173 [Break Frequency]
P032 [Motor NP Hertz]
P035 [Maximum Freq]
A171 [Start Boost]
P031 [Motor NP Volts]
A174 [Maximum Voltage]
A172 [Break Voltage]
A034 [Minimum Freq]
A172 [Break Voltage]
Related Parameter(s):
,
,
,
,
Sets the break voltage applied at the break frequency when A170 [Boost Select] = 0 “Custom V/Hz”.
Values
Default:
25.0%
Min/Max:
0.0/100.0%
Display:
0.1%
A173 [Break Frequency]
Related Parameter(s):
,
,
,
,
Sets the frequency where break frequency is applied when A170 [Boost Select] = 0 “Custom V/Hz”.
Values
Default:
15.0 Hz
Min/Max:
0.0/320.0 Hz
Display:
0.1 Hz