58
Rockwell Automation Publication 750-IN020D-EN-P - May 2017
PowerFlex 755 IP00, NEMA/UL Open Type Drive
Cable Routing
Control Pod Cable Routing
Supports, clips, and cable ties are provided to help route and secure cabling inside
the Control Pod.
Figure 20 - Frame 8 Control POD Detail
IMPORTANT
•
When routing cabling into the control Pod, do not block the cooling fan
outlet.
•
Do not ground shield wires to inner sheet metal bucket supporting option
modules.
No.
Description
1
I/O signal cable shield termination points. Use M4 screws and ring terminals provided to tie together and
terminate drain wires and shields.
2
Ground shield wires to outer sheet metal bucket. Strip cable insulation 25 mm (1 in.) to expose braid. Attach cable
ties around shield and through slots. Pull tight.
3
Attachment points for cable management devices provided (6 places).
4
Cable support ladder.
5
Fan outlet. Keep clear to help ensure proper cooling.
6
Control cable entry and routing.
7
Human Interface Module (HIM) cable entry and routing.
8
Shield termination points.
9
Inverter Fiber-optic connection
10
Internal 24V power connection
1
3
5
2
6
7
7
6
9
8
10
4