Rockwell Automation Publication 520-UM002B-EN-E - December 2017
11
Overview
Preface
General Precautions
At the end of its life, this equipment should be collected separately from any
unsorted municipal waste
ATTENTION:
The drive contains high voltage capacitors which take time to
discharge after removal of mains supply. Before working on drive, ensure
isolation of mains supply from line inputs [R, S, T (L1, L2, L3)]. Wait three
minutes for capacitors to discharge to safe voltage levels (DC Bus voltage is less
than 50V DC). Failure to do so may result in personal injury or death.
Darkened display LEDs is not an indication that capacitors have discharged to
safe voltage levels.
ATTENTION:
Only qualified personnel familiar with adjustable frequency AC
drives and associated machinery should plan or implement the installation,
start-up and subsequent maintenance of the system. Failure to comply may
result in personal injury and/or equipment damage.
ATTENTION:
This drive contains ESD (Electrostatic Discharge) sensitive parts
and assemblies. Static control precautions are required when installing, testing,
servicing or repairing this assembly. Component damage may result if ESD
control procedures are not followed. If you are not familiar with static control
procedures, reference A-B publication
, “Guarding Against
Electrostatic Damage” or any other applicable ESD protection handbook.
ATTENTION:
An incorrectly applied or installed drive can result in component
damage or a reduction in product life. Wiring or application errors, such as
undersizing the motor, incorrect or inadequate AC supply, or excessive ambient
temperatures may result in malfunction of the system.
ATTENTION:
The bus regulator function is extremely useful for preventing
nuisance overvoltage faults resulting from aggressive decelerations,
overhauling loads, and eccentric loads. However, it can also cause either of the
following two conditions to occur.
1. Fast positive changes in input voltage or imbalanced input voltages can cause
uncommanded positive speed changes.
2. Actual deceleration times can be longer than commanded deceleration times.
However, a “Decel Override” fault is generated if the drive remains in this state for
one minute. If this condition is unacceptable, the bus regulator must be disabled by
setting the Bus Regulator Action in Logix Designer. In addition, installing a properly
sized dynamic brake resistor will provide equal or better performance in most
cases. See
Dynamic Brake Resistors on page 142
to select an appropriate resistor for
your drive rating.
ATTENTION:
Risk of injury or equipment damage exists. Drive does not contain
user-serviceable components. Do not disassemble drive chassis.
Содержание PowerFlex 527
Страница 1: ...PowerFlex 527 Adjustable Frequency AC Drive Catalog Number 25C User Manual Original Instructions...
Страница 4: ...4 Rockwell Automation Publication520 UM002B EN E December 2017 Summary of Changes Notes...
Страница 8: ...8 Rockwell Automation Publication 520 UM002B EN E December 2017 Table of Contents Notes...
Страница 102: ...102 Rockwell Automation Publication520 UM002B EN E December 2017 Chapter 5 Hardwired Control of Safe Torque Off Notes...
Страница 162: ...162 Rockwell Automation Publication520 UM002B EN E December 2017 Appendix B Accessories and Dimensions Notes...
Страница 173: ...Rockwell Automation Publication520 UM002B EN E December 2017 173 Notes...
Страница 174: ...174 Rockwell Automation Publication 520 UM002B EN E December 2017 Notes...
Страница 175: ......