C-6
DeviceNet Objects
Class Code
Instances
Class Attributes
Not supported.
Register Object
Hexadecimal Decimal
0x07
7
Instance
Description
1
All polled data being read from the DPI device (read-only)
2
All polled data written to the DPI device (read/write)
3
Logic Status and Feedback data (read-only)
4
Logic Command and Reference data (read/write)
5
Datalink A (input data from device to scanner) (read only)
6
Datalink A (output data from scanner to device) (read/write)
7
Datalink B (input data from device to scanner) (read only)
8
Datalink B (output data from scanner to device) (read/write)
9
Datalink C (input data from device to scanner) (read only)
10
Datalink C (output data from scanner to device) (read/write)
11
Datalink D (input data from device to scanner) (read only)
12
Datalink D (output data from scanner to device) (read/write)
13
Logic Status and Feedback Data (read-only)
14
Mask
(1)
(read/write)
(1)
The mask command word is set to the value of the first word of the data where
there are ones in the second word of the data. Command = (word 1 and not
word 2) or (word 1 and word 2). This only controls specified bits in the Logic
Command data to the DPI product and does not change the Reference value.
Содержание PowerFlex 20-COMM-D
Страница 1: ...DeviceNet Adapter 20 COMM D FRN 1 xxx User Manual...
Страница 6: ...iv Table of Contents Notes...
Страница 72: ...6 14 Using Explicit Messaging Notes...
Страница 90: ...B 8 Adapter Parameters Notes...
Страница 122: ...C 32 DeviceNet Objects Notes...
Страница 132: ...E 8 Master Slave I O Configuration Notes...
Страница 148: ......