148
Rockwell Automation Publication 750-IN001O-EN-P - October 2014
Chapter 4
Power Wiring
Table 8 - Wall Mount Frames 6 and 7 Power Terminal Block
Table 9 - Wall Mount Frames 1…7 PE Grounding Stud
Frame
Maximum Lug
Width
(1)
(1) Lugs are supplied by the user.
Recommended
Torque
Terminal Bolt Size
Recommended Tool
6
34.6 mm (1.36 in.)
11.3 N•m (100 lb•in)
M8 x 1.25
13 mm Hex Socket
7
43.5 mm (1.71 in.)
11.3 N•m (100 lb•in)
M8 x 1.25
13 mm Hex Socket
Frame
Recommended Torque
Terminal Bolt/Screw Size
Recommended Tool
1
1.36 N•m (12 lb•in)
M4
T20 hexalobular (Torx)
#1 Flat Screwdriver
2
1.36 N•m (12 lb•in)
M4
7 mm Hex Deep Socket
3
3.4 N•m (30 lb•in)
M6
10 mm Hex Deep Socket
4
3.4 N•m (30 lb•in)
M6
10 mm Hex Deep Socket
5
3.4 N•m (30 lb•in)
M6
10 mm Hex Deep Socket
6
11.3 N•m (100 lb•in)
M8
13 mm Hex Socket
7
11.3 N•m (100 lb•in)
M8
13 mm Hex Socket
Содержание PowerFlex 20-750-20COMM
Страница 1: ...PowerFlex 750 Series AC Drives Catalog Numbers 20F 20G 21G Installation Instructions...
Страница 6: ...6 Rockwell Automation Publication 750 IN001O EN P October 2014 Notes...
Страница 10: ...10 Rockwell Automation Publication 750 IN001O EN P October 2014 Preface Notes...
Страница 34: ...34 Rockwell Automation Publication 750 IN001O EN P October 2014 Chapter 2 Prepare for Installation Notes...
Страница 218: ...218 Rockwell Automation Publication 750 IN001O EN P October 2014 Chapter 4 Power Wiring Notes...
Страница 300: ...300 Rockwell Automation Publication 750 IN001O EN P October 2014 Chapter 6 Integrated Motion Drives Notes...
Страница 301: ......