Publication 1764-UM001A-US-P
C-2
Troubleshooting Your System
When Operating Normally
The POWER and RUN LEDs are on. If a force condition is active, the FORCE
LED turns on and remains on until all forces are removed.
When an Error Exists
If an error exists within the controller, the controller LEDs operate as described in
the following tables.
If the LEDS
indicate:
The Following
Error Exists
Probable Cause
Recommended Action
All LEDS off No input power or
power supply error
No Line Power
Verify proper line voltage and
connections to the controller.
Power Supply
Overloaded
This problem can occur intermittently if
power supply is overloaded when output
loading and temperature varies.
Power and
FAULT LEDs
on solid
Hardware faulted
Processor
Hardware Error
Cycle power. Contact your local
Rockwell Automation representative if
the error persists.
Loose Wiring
Verify connections to the controller.
Power LED
on and
FAULT LED
flashing
Application fault
Hardware/
Software Major
Fault Detected
4. Monitor Status File Word S:6 for
major error code. See page C-4 for
more information.
5. Remove hardware/software
condition causing fault.
6. Clear Major Error Halted flag, bit
S2:1/13.
7. Attempt a controller Run mode entry.
If unsuccessful, repeat recommended
action steps above or contact your
local Rockwell Automation
distributor.
Содержание micrologix 1500
Страница 1: ...MicroLogix 1500 Programmable Controllers Bulletin 1764 User Manual AB Spares...
Страница 6: ...Publication 1762 RM001A US P Preface P 4...
Страница 52: ...Publication 1764 UM001A US P 3 16 Wiring Your Controller...
Страница 78: ...Publication 1764 UM001A US P 5 10 Using Trim Pots and the Data Access Tool DAT...
Страница 96: ...Publication 1764 UM001A US P B 6 Replacement Parts...
Страница 102: ...Publication 1764 UM001A US P C 6 Troubleshooting Your System...
Страница 132: ...Publication 1764 UM001A US P F 10 System Loading and Heat Dissipation...
Страница 147: ...AB Spares...
Страница 149: ...AB Spares...