Publication 1764-UM001A-US-P
A-6
Specifications
Transistor Output Transient Pulses
Refer to page 3-15 for “Transistor Output Transient Pulses”.
Table A.9 Working Voltage (1764-24BWA)
Specification
1764-24BWA
Power Supply Input to Backplane
Isolation
Verified by one of the following dielectric tests: 1836V
ac for 1 second or 2596V dc for 1 second
265V Working Voltage (IEC Class 2 reinforced insulation)
Power Supply User 24V Output to
Backplane Isolation
Verified by one of the following dielectric tests: 600V ac
for 1 second or 848V dc for 1 second
50V Working Voltage (IEC Class 2 reinforced insulation)
Input Group to Backplane Isolation and
Input Group to Input Group Isolation
Verified by one of the following dielectric tests: 1200V
ac for 1 second or 1697V dc for 1 second
75V dc Working Voltage (IEC Class 2 reinforced
insulation)
Output Group to Backplane Isolation
Verified by one of the following dielectric tests: 1836V
ac for 1 second or 2596V dc for 1 second
265V Working Voltage (IEC Class 2 reinforced
insulation).
Output Group to Output Group
Isolation.
Verified by one of the following dielectric tests: 1836V
ac for 1 second or 2596V dc for 1 second
265V Working Voltage (basic insulation) 150V Working
Voltage (IEC Class 2 reinforced insulation)
Table A.10 Working Voltage (1764-28BXB)
Specification
1764-28BXB
Input Group to Backplane Isolation and
Input Group to Input Group Isolation
Verified by one of the following dielectric tests: 1200V
ac for 1 second or 1697V dc for 1 second
75V dc Working Voltage (IEC Class 2 reinforced
insulation)
FET Output Group to Backplane
Isolation and FET Outputs Group to
Group
Verified by one of the following dielectric tests: 1200V
ac for 1 second or 1697V dc for 1 second
75V dc Working Voltage (IEC Class 2 reinforced
insulation)
Relay Output Group to Backplane
Isolation
Verified by one of the following dielectric tests: 1836V
ac for 1 second or 2596V dc for 1 second
265V Working Voltage (IEC Class 2 reinforced insulation)
Relay Output Group to Relay and FET
Output Group Isolation
Verified by one of the following dielectric tests: 1836V
ac for 1 second or 2596V dc for 1 second
265V Working Voltage (basic insulation) 150V Working
Voltage (IEC Class 2 reinforced insulation)
Содержание micrologix 1500
Страница 1: ...MicroLogix 1500 Programmable Controllers Bulletin 1764 User Manual AB Spares...
Страница 6: ...Publication 1762 RM001A US P Preface P 4...
Страница 52: ...Publication 1764 UM001A US P 3 16 Wiring Your Controller...
Страница 78: ...Publication 1764 UM001A US P 5 10 Using Trim Pots and the Data Access Tool DAT...
Страница 96: ...Publication 1764 UM001A US P B 6 Replacement Parts...
Страница 102: ...Publication 1764 UM001A US P C 6 Troubleshooting Your System...
Страница 132: ...Publication 1764 UM001A US P F 10 System Loading and Heat Dissipation...
Страница 147: ...AB Spares...
Страница 149: ...AB Spares...